background image

9

Product overview

Type of 

installation

Chan-

nel

Operating 

voltage

Colour

Type

Item 

number

Ceiling 

installation

Light 

HVAC

110-230 

V AC

White

thePassa P360 

-101 UP WH

2010300

Ceiling 

installation

Light 

HVAC

110-230 

V AC

Grey

thePassa P360 

-101 UP GR

2010301

Ceiling 

installation

Light 

HVAC

110-230 

V AC

Special 

colour in 

thePassa P360 

-101 UP SF

2010303

Troubleshooting 

Fault

Cause

Light does not switch 

on or off if presence 

is detected and in 

darkness

Lux value is set too low; detector set on semi-

automatic; light was switched off manually via 

button or "theSenda S"; person not within detec-

tion area; obstruction(s) interrupting detection; 

time delay set too short

Light stays on with 

detection of presence 

despite sufficient 

brightness 

Lux value is set too high; light was briefly switched 

on manually via button or with "theSenda S" (wait 

30 min.); detector is in test mode

Light does not switch 

off, or light switches on 

spontaneously when 

no one is present 

Wait for time delay (self-learning);

thermal sources of interference in the detection 

area: fan heaters, incandescent lamps/halogen 

spotlights, moving objects (e.g. curtains hanging in 

open windows); 

Load (EBs, relays) not cleared

Push button does not 

work

Device still in the start-up phase; illuminated 

button was used without neutral conductor; 

Push button not fed to the Master

Light cannot be swit-

ched off with the push 

button

Push button not fed to the detector. Check wiring 

to the push button.

Device does not 

respond

Short circuit or several phases in parallel swit-

ching! Disconnect detector from the power supply 

for 5 min (thermal fuse)

Error flashing 

 

(4 x per second)

Error in self-test; 

device not functional!

LED display

LED

Description

Flashing at 1 second 

intervals

The presence detector is in the start-up phase.

Flickering for 2 s

The command sent from the remote control 

via infrared was accepted by the presence 

detector.

Lighting up briefly

The command sent from the remote control via 

infrared was rejected by the presence detector. 

The command is not valid. Check the selected 

detector type or parameters on the SendoPro 

or in the app.

Fast flashing

Error flashing; The presence detector has 

found an error.

Flickering for 20 s

Teach-in via potentiometer is activated. 

Lights up or flickers 

irregularly

The presence detector is in presence test 

mode or "LED display movement" is activated. 

The LED displays detection of movement.

Guarantee

Theben HTS presence detectors are manufactured with 

the utmost care using state-of-the-art technology and are 

quality-tested. Theben HTS AG therefore guarantees perfect 

operation when used correctly. Should a fault occur, Theben 

HTS AG will fulfil the guarantee within the scope of the gene

-

ral terms and conditions.

Please note in particular:

 

that the guarantee period lasts 24 months from the date 

of manufacture. 

 

that the guarantee is invalidated if you, or a third party, 

make changes to or undertake repairs on the devices.

 

that, insofar as the presence detectors are connected 
to a software-controlled system, the guarantee for this 
connection is only valid when the indicated interface 

specification is complied with.

We undertake to repair or replace as quickly as possible 

all components of the delivered device that have become 

defective or unusable through demonstrably poor material, 

faulty construction or incomplete delivery up to the end of the 

guarantee period. 

Returns

In the event of a guarantee claim, please return the device to 

the relevant dealer together with the delivery note and a brief 

description of the fault.

Industrial property rights

The design as well as hardware and software of these devices 

are protected by copyright.

Dimensions diagrams

11. Accessories

Back box 110A WH

Item no.: 9070912

Details > www.theben.de/en

Содержание thePassa P360-101 UP WH

Страница 1: ... control theSenda B option and corres ponding app theSenda Plug iOS Android 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the techni...

Страница 2: ...ple are present or it is dark Channel H presence Channel H presence is used for HVAC control The switching response of the floating contact is influenced only by pre sence and not by brightness If the contact is closed the time delay will be restarted at every movement Push buttons or switches do not influence the contact Switch on delay The switch on delay prevents instantaneous switching on The ...

Страница 3: ...ighting directly below the detector If the brightness measurement is deactivated chan nel A light only switches depending on presence brightness setpoint value set to on via potentiometer or set to mea surement off via remote control 1 8 m Suitable lamps The presence detector is designed for the operation of fluore scent compact fluorescent halogen and incandescent lamps as well as LEDs The maximu...

Страница 4: ... L Light measurement only with the Master Parameters are only set on the Master Switch up to 10 detectors in parallel Use the phase with the same phase for all detectors Master thePassa P360 101 UP Slave thePassa P360 Slave UP Master Master parallel switching for several lighting groups Several Masters can be used in a parallel switching Each Master controls its lighting group according to its own...

Страница 5: ... only closes when someone is present after expiry of the switch on delay 0 contact closes immediately if people are present Parameters and control commands via remote control The following parameters can be checked or changed via the remote control for support during start up as well as servicing Parameter Description Can be que ried by SendoPro 868 A theSenda B app Can be chan ged by SendoPro 868...

Страница 6: ... the furniture With the room correction factor the brightness measurement value of lighting channel A is adjusted to the conditions in the room and in this way can be matched to the lux meter value measured at the surface beneath the presence detector Room correction factor Brightness value at the ceiling brightness value at the working surface Using management SendoPro 868 A remote control and lu...

Страница 7: ...stable values 0 s no switch on delay 30 s 1 10 min Configuration type Fully automatic device The lighting is switched on and off automatically Due to presence absence and brightness SendoPro 868 A theSenda B app auto theSenda P Button A Semi automatic Lights must always be switched on manually Switching off occurs automatically by the presence detector due to absence or brightness SendoPro 868 A t...

Страница 8: ...ment occurs the light and presence switch contacts close y y When no one is present the light switch contact opens after 10 s y y Brightness measurement deactivated detector does not react to brightness y y The detector reacts as in configuration type fully auto matic device even if semi automatic is set y y Teach in cannot be activated in test mode y y Test mode ends automatically after 10 min Th...

Страница 9: ...e Flickering for 2 s The command sent from the remote control via infrared was accepted by the presence detector Lighting up briefly The command sent from the remote control via infrared was rejected by the presence detector The command is not valid Check the selected detector type or parameters on the SendoPro or in the app Fast flashing Error flashing The presence detector has found an error Fli...

Страница 10: ...Details www theben de en theSenda B Item no 9070985 Details www theben de en theSenda S Item no 9070911 Details www theben de en 12 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch www theben hts ch All countries except Switzerland Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 4...

Отзывы: