background image

4

Surface-mounted installation

A back box 110A is available for surface mounted installation 

(see accessories).

7.  Switching

The presence detectors can be combined as Master and Slave: 

Master in individual switching, Master in parallel switching, 

Master-Slave parallel switching. 

Several push buttons can be connected to one control input. 

Illuminated push buttons can only be used with neutral con-

ductor connection.

Individual switching

In individual switching, the presence detector, as Master, 

detects presence and brightness and controls lighting.

AC / DC

H2

H1

L’

Master/Slave parallel switching

If the detection area covered by one presence detector is 

insuffi cient (larger rooms), then up to 10 detectors can be 

operated in parallel by connecting the P terminals. In the 

process, presence detection is performed by all detectors 

together. The Master measures the brightness, operates the 

buttons and controls the lighting. Slaves are used as further 

detectors. They only provide presence information.

AC / DC

Master

Slave

H2

H1

L’

 

Light measurement only with the Master

 

Parameters are only set on the Master

 

Switch up to 10 detectors in parallel

 

Use the phase with the same phase for all detectors.

Master: thePassa P360 -101 UP 

Slave: thePassa P360 Slave UP

Master/Master parallel switching (for several 

lighting groups)

Several Masters can be used in a parallel switching. Each 

Master controls its lighting group according to its own bright-

ness measurements. Delay times and brightness setpoint 

values are set individually on each Master. Presence continues 

to be detected by all detectors.

AC / DC

Master  1

Master  2

H2

H1

L’

H2

H1

L’

 

One Master with individual brightness measurement per 

lighting group.

 

Set potentiometer individually for each Master.

 

Switch up to 10 detectors in parallel.

 

Use the phase with the same phase for all detectors. 

 

The presence switch contact can be read by any Master.

8.  Settings

The presence detectors are supplied with basic settings 

ready for operation. The specifi cations are guidance values. 

Management remote control "SendoPro 868-A", service 

remote control "theSenda P" and app remote control "the-

Senda B" (with "theSenda Plug" app) are optionally available 

for start-up.

They allow the remote adjustment of the setting values.

Содержание thePassa P360-101 UP WH

Страница 1: ... control theSenda B option and corres ponding app theSenda Plug iOS Android 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the techni...

Страница 2: ...ple are present or it is dark Channel H presence Channel H presence is used for HVAC control The switching response of the floating contact is influenced only by pre sence and not by brightness If the contact is closed the time delay will be restarted at every movement Push buttons or switches do not influence the contact Switch on delay The switch on delay prevents instantaneous switching on The ...

Страница 3: ...ighting directly below the detector If the brightness measurement is deactivated chan nel A light only switches depending on presence brightness setpoint value set to on via potentiometer or set to mea surement off via remote control 1 8 m Suitable lamps The presence detector is designed for the operation of fluore scent compact fluorescent halogen and incandescent lamps as well as LEDs The maximu...

Страница 4: ... L Light measurement only with the Master Parameters are only set on the Master Switch up to 10 detectors in parallel Use the phase with the same phase for all detectors Master thePassa P360 101 UP Slave thePassa P360 Slave UP Master Master parallel switching for several lighting groups Several Masters can be used in a parallel switching Each Master controls its lighting group according to its own...

Страница 5: ... only closes when someone is present after expiry of the switch on delay 0 contact closes immediately if people are present Parameters and control commands via remote control The following parameters can be checked or changed via the remote control for support during start up as well as servicing Parameter Description Can be que ried by SendoPro 868 A theSenda B app Can be chan ged by SendoPro 868...

Страница 6: ... the furniture With the room correction factor the brightness measurement value of lighting channel A is adjusted to the conditions in the room and in this way can be matched to the lux meter value measured at the surface beneath the presence detector Room correction factor Brightness value at the ceiling brightness value at the working surface Using management SendoPro 868 A remote control and lu...

Страница 7: ...stable values 0 s no switch on delay 30 s 1 10 min Configuration type Fully automatic device The lighting is switched on and off automatically Due to presence absence and brightness SendoPro 868 A theSenda B app auto theSenda P Button A Semi automatic Lights must always be switched on manually Switching off occurs automatically by the presence detector due to absence or brightness SendoPro 868 A t...

Страница 8: ...ment occurs the light and presence switch contacts close y y When no one is present the light switch contact opens after 10 s y y Brightness measurement deactivated detector does not react to brightness y y The detector reacts as in configuration type fully auto matic device even if semi automatic is set y y Teach in cannot be activated in test mode y y Test mode ends automatically after 10 min Th...

Страница 9: ...e Flickering for 2 s The command sent from the remote control via infrared was accepted by the presence detector Lighting up briefly The command sent from the remote control via infrared was rejected by the presence detector The command is not valid Check the selected detector type or parameters on the SendoPro or in the app Fast flashing Error flashing The presence detector has found an error Fli...

Страница 10: ...Details www theben de en theSenda B Item no 9070985 Details www theben de en theSenda S Item no 9070911 Details www theben de en 12 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch www theben hts ch All countries except Switzerland Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 4...

Отзывы: