background image

28

ENGLISH

6

Maintenance and Repair

With the exception of a regular replacement of the batteries for the

RAMSES

®

811 top

, the room thermostats are maintenance-free.

Only clean the device with a dry or slightly damp, soft and lint-free
cloth. The interior of the device must remain free from water.

Only

RAMSES

®

811 top

:

Replace the two batteries at regular intervals every 1.5 years. Only
use new 1.5 V batteries of the type AA, Alkaline. Never mix old and
new batteries, as old batteries can leak.

7

Disposal

7.1

Disposal of Batteries

Used batteries must be disposed of according to the national regula-
tions with regard to the environment (e.g. at special battery collection
outlets). Never throw used batteries out with your usual rubbish.

7.2

Disposal of the Device

At the end of its life, the room thermostat must be dismounted profes-
sionally and disposed of according to the national regulations with re-
gard to the environment.

In case of doubts, please contact the manufacturer’s representative
in your country. Contact details can be found at the back of this man-
ual.

8

Technical Data

Control type:

RS type 2B acc. to EN 60730-1:1991

Contact:

Change-over contact, potential-free,
protective low voltage.
Max. 6 A / 250 V~, min. 1 mA / 5 V

Accuracy:

± 1 sec. per day at 20°C

Control accuracy:

± 0.2 K

Temperature meas. range:

0°C to 50°C, resolution 0.1°C

Temperature setting range:

6°C to 30°C in increments of 0.2°C

Control period:

5 to 30 min. (PD control)

Control lock-in range:

± 0.2 K to ± 5 K (PD control)

Switching hysteresis:

± 0.2 K to ± 1.0 K (hysteresis control)

Memory spaces:

22 temperature changes, programmable
for Mo-Fr, Sa-Su, each day or for individ-
ual days.

Class of protection:

II according to EN 60730-1

Type of enclosure:

IP 20 according to EN 60529-1

Only

RAMSES

®

812 top

Operating voltage:

230 V~ ± 10 %; 240 V~ + 6 %, - 14 %
50 to 60 Hz

Power reserve:

5 hours

Only

RAMSES

®

811 top

Batteries:

2 x alkaline batteries 1.5 V, type AA

Power reserve during
battery replacement:

10 minutes

6

Maintenance and Repair

The room thermostats 

RAMSES

®

818 top 

are maintenance-free.

Only clean the device with a dry or slightly damp, soft and lint-free
cloth. The interior of the device must remain free from water.

7

Disposal

At the end of its life, the room thermostat must be dismounted pro-
fessionally and disposed of according to the national regulations with
regard to the environment.

In case of doubts, please contact the manufacturer’s representative in
your country.

8

Technical Data

Control type:

RS type 1 B acc. to EN 60730-1:2001

Contact:

Change-over contact, potential-free,
protective low voltage.
Max. 6A (1)/ 250 V~, min. 1 mA / 5V

Accuracy:

± 1 sec. per day at 20 °C

Control accuracy:

± 0.2 K

Temperature meas. range:

O °C to 50 °C, resolution 0.1 °C

Temperature setting range:

6 °C to 30 °C in increments of 0.2 °C

Control period:

5 to 30 min. (PD control)

Control lock-in range:

± 0.2 K to ± 5 K (PD control)

Switching hysteresis:

± 0.2 K to ± 1 0 K (hysteresis control)

Memory spaces:

32 temperature changes, programmable
for Mo-Fr, Sa-Su, each day or for individual 
days.

Class of protection:

II in accordance with EN 60730-1 with 
correct installation

Type of enclosure:

IP 21 according to EN 60529-1

Operating voltage:

230 V-240 V; 50 to 60 Hz

Power reserve:

6 hours

Only 

RAMSES

®

818 top 16 A

Control type:

RS type 1 B acc. to EN 60730-1:2001

Contact:

Closing contact, max. 16 A (2)/250 V~

Class of protection:

II in accordance with EN 60730-1 for 
designated installation on a flush box

30

Содержание RAMSES 818 top 16 A

Страница 1: ...ing instructions 16 Clock thermostat Mode d emploi 31 Thermostat à horloge Instrucciones de servicio 46 Cronotermostato Istruzioni per l uso 61 Cronotermostato Gebruiksaanwijzing 76 Klokthermostaat RAMSES 818 top 6 A RAMSES 818 top 16 A 309 251 05 ...

Страница 2: ...cellation of the warranty Table of Contents 1 Designated Use 16 2 Safety Instructions 16 3 Description and Mounting 17 3 1 Device Overview 17 3 2 Mounting and Electrical Connection 18 4 Installation and Operation 19 4 1 Carrying out a Reset 19 4 2 Selecting the Language 19 4 3 Select the floor covering and or the control range 19 4 4 Setting the Time Date 19 4 5 Selecting the Temperature Profile 2...

Страница 3: ...lay PARTY or ECO program active Display of the switch phases RESET button Icon bar for display of the programming level rotary switch position MENU Change buttons Rotary switch for program selection Button OK confirmation of settings selection or programming Button ESC cancellation of programming entries Info button for checking the settings 17 ENGLISH ...

Страница 4: ...y be shortened before doing so make sure that the temperature regulator is disconnected We strongly recommend to implement on extra security for the regulator system through installing a personal protection switch RAMSES 818 top 16 A RAMSES 818 top 6 A 3 2 2 Connection examples RAMSES 818 top 6 A 3 2 3 Connection examples RAMSES 818 top 16 A flush mounted socket N L1 heating cable Regulation of an...

Страница 5: ...also be changed in the Service menu see chap 5 4 1 The display shows the time setting 2 Set the current time with the buttons and Set the hour and confirm with the OK button Set the minutes and confirm with the OK button 19 ENGLISH OK 4 2 Selecting the Language 1 The display automatically shows the selected language after Reset 2 Select your language with the buttons or The available languages are...

Страница 6: ... comes on when the room temperature falls below the programmed antifreeze temperature 4 6 Checking Current Room Temperature and Settings lnfo Button With the lnfo button you can display the current room temperature as well as all important settings of the program set at the rotary switch 1 Press the Info button The current room temperature is shown in the display for approx 3 seconds In order to c...

Страница 7: ...9 3 The check is completed The display automatically switches back to the original state 4 7 Quick heating function boost function This function allows you to rapidly heat the underfloor heating to the comfort temperature corresponds to Comfort 1 plus 2 C Once the temperature has been reached the Comfort mode will operate for 1 hour To do so press the Info key for approx 5 s boost appears 4 8 Temp...

Страница 8: ...ether you want the comfort the lower or the antifreeze temperature for the set period Confirm with the OK button 4 10 Party Eco Program With the Party Eco function you can cancel the temperature pro file of the set program for the next few hours up to 23 hours and 50 minutes 4 10 1 Setting the Party Eco Program 1 Press both buttons and at the same time for approx 2 seconds 2 The display changes an...

Страница 9: ...e display shows the target temperature and the text line holiday Note Checking clearing or cancelling a holiday program is des cribed in section 4 8 5 2 Changing the Settings for Target Temperatures For the temperature profiles of the individual programs you can choose between three temperature values Comfort lower and anti freeze temperature These temperature values are programmed ex works You ca...

Страница 10: ...ext day are dis played etc CHECK 7 6 5 4 3 2 1 PROG 6 00 0 3 6 9 12 15 18 21 24h 21 0 C END 3 sec Empty no program stored in memory back to Program see 5 3 1 OK OK back to Program see 5 3 1 CLEAR Single All END back to Single see 5 3 5 see 5 3 6 OK 5 3 2 Creating a new temperature profile P1 P2 P3 Display of the free memory areas 5 3 3 Checking the temperature profile 5 3 4 Clearing the temperatur...

Страница 11: ...mes 2 Clearing the desired switch times Clear All Empty no program stored in memory Confirm In order to cancel the clearing process press the ESC button back to Program see 5 3 1 OK OK OK back to Program see 5 3 1 5 3 5 Displaying individual switch times and clearing them 1 Displaying the switch times 2 Clearing the desired switch times 5 3 6 Clearing all switch times no program stored in memory I...

Страница 12: ...ical display 5 4 Service Settings 5 4 1 Overview Service menu T text line N numerical display 5 4 2 Selecting the display type Select the display type with the button or Confirm with the OK button Cancel with ESC Display Display 3 OK OK Note The factory setting is highlighted grey in the table Select the display type with the button or Confirm with the OK button Cancel with ESC Note The factory st...

Страница 13: ...5 30 0 1 C 5 0 C Set with buttons or 0 2 C 5 0 C back to or autom after 6 sec see 5 4 1 5 4 3 Selecting the language Select the language with the buttons or Confirm with the OK button Cancel with ESC 5 4 4 Setting the Correction In case of unfavourable conditions at the installation site installation at the exterior wall chimney etc there may be deviations in temperature between the temperature me...

Страница 14: ... Example 1 Comfort mode The setting is 10 minutes per C at a room temperature of 17 C However room temperature should reach 20 C by 7 00 hrs The 7 00 hrs switchover to comfort mode will occur at 6 30 hrs 7 00 3 x 10 min 6 30 hrs Example 2 Lower mode The system should be regulated to target temperature 1 C during optimisation time and before lower mode At 6 00 hrs we have a room temperature of 15 C...

Страница 15: ...e Month Weekend within month Hour for changeover e g from 2 a m to 3 a m Start of winter time Month Weekend within month OK Note Time for changeover to winter time is taken from summer time e g back from 3 a m to 2 a m OK 3 sec 5 5 Time Date and Summer Winter Time Setting the time and date hour minute year month day Description see chap 4 3 Start of summer time Month Weekend within month Weekend w...

Страница 16: ... Sa Su each day or for individ ual days Class of protection II according to EN 60730 1 Type of enclosure IP 20 according to EN 60529 1 Only RAMSES 812 top Operating voltage 230 V 10 240 V 6 14 50 to 60 Hz Power reserve 5 hours Only RAMSES 811 top Batteries 2 x alkaline batteries 1 5 V type AA Power reserve during battery replacement 10 minutes 6 Maintenance and Repair The room thermostats RAMSES 8...

Страница 17: ...Hohenbergstr 32 72401 Haigerloch DEUTSCHLAND Fon 49 0 74 74 6 92 0 Fax 49 0 74 74 6 92 150 Service Fon 49 0 74 74 6 92 369 Fax 49 0 74 74 6 92 207 hotline theben de Adresses telephone numbers etc at www theben de ...

Отзывы: