5.4.6 Optimisation
If the optimisation function (1-60 min.) is switched on, the thermostat
calculates the ideal switching time for toggling between lower and
comfort mode.
5.4.7 Reset operating hours
The
op hour reset
function in the "Service” menu indicates the
number of hours during which the device has been switched on.
The operating hours are requested using the
Info
key and reset in
the "Service” menu.
Example 1 (Comfort mode):
The setting is 10 minutes per °C at a room temperature of 17 °C.
However, room temperature should reach 20 °C by 7.00 hrs. The 7.00 hrs
switchover to comfort mode will occur at 6.30 hrs.
➡
7.00 - 3 x 10 min. = 6.30 hrs.
Example 2 (Lower mode):
The system should be regulated to target temperature (–1 °C) ) during
optimisation time and before lower mode.
At 6.00 hrs, we have a room temperature of 15 °C (24 °C). ). At 22.00
hrs, the temperature should be 17 °C.
➡
24 °C - 17 °C = 7 °C x 10 = 70 minutes
➡
22 hrs - 70 hrs = 20.50 hrs
From 20.50 hrs onwards, the system is regulated to 23 °C.