12
L
A video on configuration of the lighting groups is available
at: https://www.youtube.com/user/TheThebenAG
Switch-on behaviour (configured systems)
Every time the power supply is switched on, the presence
detector runs through two phases that are indicated by the
LED:
1. Start-up phase (30 s)
•
The red LED flashes at one second intervals and lighting
is switched on with switch-on dimming value.
•
The detector does not respond to push-button com-
mands or to the “theSenda S” user remote control.
•
The lighting is switched off after 30 s when the room is
unoccupied.
2. Operation
•
The red LED is off.
The constant light control or switching
mode are started.
•
The detector is ready for operation.
10. Technical data
Operating voltage
110 – 230 V AC, +10% / -15%
Frequency
50 – 60 Hz
Upstream protection device:
16 A
Power consumption (without DALI-ECG)
< 0.4 W
Type of installation
Ceiling installation; flush/surface
mounted or ceiling installation
Recommended installation height
2.0 – 3.5 m/max. 15 m
Minimum height
> 1.7 m
Detection area
horizontal 360°
Maximum range
Ø 7 m (Mh. 3.5 m) / 38 m
2
seated
Ø 25 m (Mh. 10 m) / 491 m
2
walking
Setting range brightness setpoint value
10 – 3000 lux
Lighting time delay
10 s – 60 min
Presence switch-on delay
0 s – 30 min
Presence time delay
10 s – 120 min
Lighting standby time
0 s – 60 min / permanently on
Standby dimming value
1 – 25 %
Control output lighting
100 mA guaranteed, max. 250 mA,
max. 64 DALI operating devices,
basic insulation
Connection type
Screw terminals
Max. cable cross-section
Max. 2 x 2.5 mm²
Size of flush-mounted box
Size 1, Ø 55 mm (NIS, PMI)
Protection rating
IP 20 (IP 54 installed)
Ambient temperature
-15 °C ... 50 °C
CE Declaration of Conformity
This device conforms to the
safety regulations of the EMC
directive 2014/30/EU and of
directive 2014/35/EU.
Dali conformity
IEC 62386-101, IEC 62386-103
Product overview
Type of
installation
Channel Operating
voltage
Colour
Type
Item
number
Ceiling
installation
Light
230 V AC
White
theRonda P360-
330 DALI WH
2080045
Troubleshooting
Fault
Cause
Light does not switch
on and/or off if pre-
sence is detected and
in darkness
Brightness setpoint value is set too low; detector
set on semi-automatic; light was switched off
manually via button or “theSenda S”; person not
within detection area; obstruction(s) interrupting
detection; time delay set too short
Light stays on with
detection of presence
despite sufficient
brightness
Brightness setpoint value is set too high; light was
briefly switched on manually via button or with
“theSenda S” (wait 30 min in switching operation);
detector is in test mode
Light does not switch
off and/or light swit-
ches on spontaneously
when no one is present
Wait for time delay (self-learning);
thermal sources of interference in the detection
area: fan heaters, incandescent lamps/halogen
spotlights, moving objects (e.g. curtains hanging in
open windows)
Push button does not
work
Device still in the start-up phase; illuminated
button was used without neutral conductor;
Push button not fed to the master. <Terminal S3/P
assignment> parameter set to "Parallel".
Light cannot be swit-
ched off with the push
button
Push button not fed to the detector. Check wiring
to the push button. <Terminal S3/P assignment>
parameter set to "Parallel".
Lighting does not react
Short circuit or interruption in the DALI bus. Electri
-
cal surge in the DALI bus: Disconnect the detector
from the supply network for 1 minute (thermal
fuse).
Error flashing
(4 x per second)
Error in self-test;
device not properly functional!
LED is on and flashes
off briefly 2 x every 3 s
Detector does not recognise DALI ECGs. Check DALI
connections. At least 1 DALI ECG must be connec
-
ted to the detector. Short circuit in DALI bus.
Master/Slave, Master/
Master parallel swit-
ching is not working
Detectors and buttons are not connected to the
same external conductor. <Terminal S3/P assign
-
ment> parameter is not set to "Parallel".
11. Dimensions diagrams