11
▻ The next DALI light starts to pulse. One after the other,
the lighting groups are assigned to all the lights.
•
In the case of group assignment (Unaddress) or (All):
When all DALI-ECGs have an assigned lighting group, the
detector automatically ends configuration and restarts
itself, see section „Switching behaviour“. Finally, the
-
Ronda DALI enters normal operation and configuration is
complete.
•
If necessary, the configuration process can be ended by
pressing „End Group Assignment“ (left function button).
In this case, the system is not ready for operation.
•
If „Change group assignment“ has been selected, use the
„Next“ button (button below) to switch to the next DALI
EB without changing the lighting group. Otherwise, the
sequence remains the same. When all desired changes
have been made, the configuration can be completed by
pressing „End“ (button below).
Configuration of the lighting groups by management remote
control „SendoPro 868-A“
On the management remote control „SendoPro 868-A“,
select type „theRonda P360-330 DALI“.
Select „Menu“ (right-hand function button) and then „Con-
trol commands“ (left-hand function button).
Open „DALI configuration“ with „Open“ (right-hand function
button).
For the DALI configuration, there are 3 options available:
y
„Group assignment (unaddressed)“: Only DALI ECGs without
a group address are processed.
y
„Group assignment (All)“: All connected DALI ECGs are
configured.
WARNING
: All existing group assignments with
group number 1, 2 or 3 will be deleted.
y
„Change group assignment“: The next available ECG will be
searched for and selected.
Select the desired group assignment using the off or on
button and start configuration by pressing „Send“ (right-
hand function button).
L
The remote control must be pointing at the detector! The
LED is switched off.
▻ A DALI lamp starts to pulse (random order).
Select the desired channel C1, C2 or C3 and assign to the
DALI ECG by pressing „Send“ (right-hand function button).
▻ The lamp confirms the assignment by dimming to 20
%.
▻ The next DALI lamp starts to pulse. In this way, all of the
lights are assigned to the lighting groups successively.
•
In the case of group assignment (Unadressed) or (All):
When all DALI-ECGs have an assigned lighting group, the
detector automatically ends configuration and restarts
itself, see section „Switching behaviour“. Finally, the
-
Ronda DALI enters normal operation and configuration is
complete.
•
If so required, the configuration can be completed by
pressing „End“ (left-hand function button). In this case,
the system will not be ready for use.
•
If „Change group assignment“ is selected, the right arrow
button „>“ can be used to switch to the next DALI ECG
without changing the lighting group. Otherwise, the
sequence remains the same. When all desired changes
have been made, the configuration can be completed by
pressing „End“ (left-hand function button).
Right-hand function button
Right button
Up button
Down button
Left-hand function button
Configuration of the lighting groups using buttons
For the configuration using buttons, the <Configuration
button/RC> parameter must be set to „enabled“. All connec
-
ted buttons can be used for configuration.
L
If button S3 is used, the <Terminal S3/P assignment>
parameter may not be set to „Parallel“.
•
DALI configuration is started by briefly pressing any
button 5 x (<0.4 s) followed by 1 x long press (> 15 s).
The LED is switched off.
▻ A DALI lamp starts to pulse (random order).
•
The lighting group is assigned by pressing the corres-
ponding button:
y
1 x short button push = Channel C1
y
2 x short button push = Channel C2
y
3 x short button push = Channel C3
▻ The lamp confirms the assignment by dimming to 20 %
(3 s after the last button push).
▻ The next DALI lamp starts to pulse. In this way, all of the
lights are assigned to the lighting groups successively.
•
When all DALI-ECGs have an assigned lighting group, the
detector automatically ends configuration and restarts
itself, see section „Switching behaviour“. Finally, the
-
Ronda DALI enters normal operation and configuration is
complete.
•
If so required the configuration can be ended by pressing
any button for longer than 15 s. The detector restarts
itself. In this case, the system will not be ready for use
and must be reconfigured.
L
Instead of the button, configuration can also be carried out
using the On/Off buttons on the „theSenda S“ user remote
control.
Checking the configuration
The lighting group assignment can be checked at any time
using the buttons or the „SendoPro, theSenda B/App“
management remote control, in that the individual lighting
groups are switched on or off (select the menu „control com-
mands“ on the „SendoPro, theSenda B/App“).
If the lighting group needs to be changed on individual DALI
ECGs, DALI configuration can be carried out using the „Sen
-
doPro, theSenda B/App“ via „Change group assignment“.
When using the button, the whole DALI configuration must be
carried out again.