AMC-400 Series Digital Transmitter with Smart Sensor 2
50
Gas Number / Device Address; a 16bit
number made up of two 8 bit fields of Smart
Sensor 2 gas number and Transmitter
MODBUS address. Gas number is updated
from Smart Sensor 2 upon registration.
Gas Number [15:8]:
CO
=0
NO2
=1
CH4 =2
Pro(C3H8) =3
H2 =9
MODBUS Address [7:0]: 1-247
3
*1 Read
Slope; a reserved 32bit float number
representing the slope of the Smart Sensor 2
gas updated from Smart Sensor 2 at
registration. Slope is reserved for a monitor
based calibration procedure. *2 Not
Supported.
4-5
*1 Read
*3 Float
Offset; a reserved 32bit float number
representing the offset of the Smart Sensor 2
gas updated from Smart Sensor 2 at
registration. Offset is reserved for a monitor
based calibration procedure. *2 Not
Supported.
6-7
*1 Read
*3 Float
Calibration Data1; a reserved 32bit float
number for a monitor based procedure. *2
Not Supported.
8-9
*1 Read
*3 Float
Calibration Data2; a reserved 32bit float
number for a monitor based procedure. *2
Not Supported.
10-11
*1 Read
*3 Float
Calibration Data3; a reserved 32bit float
number for a monitor based procedure. *2
Not Supported.
12-13
*1 Read
*3 Float
Calibration Data4; a reserved 32bit float
number for a monitor based procedure. *2
Not Supported.
14-15
*1 Read
*3 Float
Output Trim Slope; a reserved 32bit float
number for calibrating output slope. *2 Not
Supported.
16-17
*1 Read
*3 Float
Output Trim Offset; a reserved 32bit float
number for calibrating output offset. *2 Not
Supported.
18-19
*1 Read
*3 Float