8.9 Gas charging
Procedure:
1. Connect the charge hose to the charging cylinder.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.
2. Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the
liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
If the system cannot be charge with the specified amount of refrigerant, if can be charged with a little at a time (approximately
150g each time0 while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately
1 minute and then repeat the procedure.(pumping down-pin).
4. Immediately disconnect the charge hose from the 3-way valve’s service port.
Stopping partway will allow the refrigerant to be discharged.
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before
disconnecting the hose.
5. Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
Содержание MWVT09S
Страница 1: ......
Страница 17: ...Service manual 16 5 Refrigerant cycle diagram Cooling only mode Heat pump mode ...
Страница 19: ...Service manual 18 MRVT09AS MRVT12AS Outdoor unit ...
Страница 20: ...Service manual 19 MRHVT09AS MRHVT12AS Outdoor unit ...
Страница 21: ...Service manual 20 MRVT18AS MRHVT18AS Outdoor unit ...
Страница 22: ...Service manual 21 MWVT24S MWHVT24S Indoor unit ...
Страница 23: ...Service manual 22 MRVT24AS Outdoor unit ...
Страница 24: ...Service manual 23 MRHVT24AS Outdoor unit ...