5.10.2.2 PLATFORM INSTALLATION ELECTRICAL WIRING (-P MODELS)
The electronics enclosure converts discrete input signals into serial communications for controlling the monitor. The
discrete input signals can be from a joystick, toggle switches, relay contacts or Canbus output module. The electronic
interface a12 volt signals, but can be field changed to accept ground signals.
The electronics enclosure is configured so that signals connected to the PRIMARY CONTROL cable will override any
other operator stations (see section 6.2.1).
See Figure 5.10.2.2 for wiring connections.
Figure 5.10.2.2
Electrical Components
(platform installations)
NOTE: To avoid excessive voltage drop at monitor operator station, cable
selection is critical.
Voltage supplied to ELECTRICS ENCLOSURE should not fall below 11 volts
when monitor is in operation.
Recommend Cable Gauge
Max Length
Gauge
4 0 ft . . . . . . 1 4 A W G
6 5 ft . . . . . . 1 2 A W G
80 ft......2-14AWG
105 ft......10AWG
130 ft.....2-12AWG
5.11 ELECTRIC NOZZLE ACTUATOR WIRING
The electric Monsoon RC monitor is designed to control and is factory wired for an electric actuated nozzle. A Task Force Tips, Inc.
Master Stream 2000 nozzle is available with the proper electric connection. After mounting the Master Stream 2000 nozzle onto the
monitor, plug the male cord from the nozzle into the female cord located on the outlet of the monitor. Make sure the two coupling nuts
are tightened securely to ensure a proper watertight seal.
If retrofitting an existing TFT nozzle, a male cord (TFT #Y5285) can be purchased and installed in place of the existing actuator cord.
Please consult factory for installation.
Monitor Mounted
Operator Station
25