background image

Product part no. 830049                                                                               Advantage

DC

 Dual Zone Fire Control Panel 

 Manual part no 650.830049                                                                                                                rev. June 13, 2022 

 

 

 

 

 

Product Operation and 

 

 

 

 

 

Advantage

DC

 Detection and Releasing 

 24 VDC Powered Fire Control Panel 

Maintenance Manual

 

Содержание AdvantageDC

Страница 1: ...art no 830049 AdvantageDC Dual Zone Fire Control Panel Manual part no 650 830049 rev June 13 2022 Product Operation and AdvantageDC Detection and Releasing 24 VDC Powered Fire Control Panel Maintenanc...

Страница 2: ...Product part no 830049 AdvantageDC Dual Zone Fire Control Panel Manual part no 650 830049 rev June 13 2022...

Страница 3: ...d Wiring and Control Panel Functions Power Input Circuits Initiating Detection Circuits Operation Actuation Circuits Operation Auxiliary Supervised Circuit Operation Abort Function Supervised Circuit...

Страница 4: ...no 650 830049 rev June 13 2022 8 0 Appendix and Notes 8 1 Miscellaneous Practical and Technical Notes 8 2 Installation and System Performance Document 8 3 High Temperature Operation 8 4 Spare and Rep...

Страница 5: ...zones of fire detection and suppression Two wire Class B supervision is provided for detection manual release and auxiliary zones The AdvantageDC control panel supports spot thermal linear thermal an...

Страница 6: ...o Manual Release on Cover 830049 01 01 Control Panel FireAway AdvantageDC Dual Detection Dual Release Plastic Wiring Hubs Manual Release Switch on Cover 830049 02 01 Control Panel FireAway AdvantageDC...

Страница 7: ...rovided for end user security purposes Two types of wiring hubs are available The AdvantageDC part no 830049 uses qty 3 die cast liquidtight metal flex conduit wiring hubs The AdvantageDC part no 8300...

Страница 8: ...ease circuit will override the Abort Switch operation Caution The AdvantageDC actuation circuits must be routed inside of approved protective conduit to prevent physical damage to the wiring Actuation...

Страница 9: ...Abort Battery Information This control panel is designed to use a single 9 VDC Nickel Metal Hydride NiMH battery as the secondary power source Use only AdvantageDC Battery part no 830053 as replacemen...

Страница 10: ...gth Max Linear Resistance ohms Wiring Cross Section Terminating Resistor ohms Pluggable Terminal Strip Screw Torque Wire Strip Length Detection 400 50 16 18 awg 470k 5 in lbs 0 5 0 6 nm 0 275 7mm Manu...

Страница 11: ...Product part no 830049 AdvantageDC Dual Zone Fire Control Panel Manual part no 650 830049 rev June 13 2022 3 3 Pluggable Terminal Strip Connections...

Страница 12: ...Product part no 830049 AdvantageDC Dual Zone Fire Control Panel Manual part no 650 830049 rev June 13 2022...

Страница 13: ...es supervision A 8 Actuation Zone 1 A 9 Actuation Zone 2 A 10 Actuation Zone 2 A 11 Auxiliary Input Normally Closed Fault when open A 12 Auxiliary Input A 13 Abort Switch Class B with 470K EOL A 14 Ab...

Страница 14: ...n and suppression while operating on the secondary battery for a minimum of 24 hours after the loss of 24 vdc primary power Initiating Detection Circuits Operation Default detection settings are progr...

Страница 15: ...a discharge time delay is programmed The Abort function contacts are supervised via a 470K end of line resistor If the Abort Switch closes the abort function will delay the system discharge if a disch...

Страница 16: ...ble alarm will turn On if the Fire or Fault condition has not been cleared AND after the audible has been silenced for six hours OR if a new Fault or Alarm condition is detected The alarm silence func...

Страница 17: ...cription is identified The Event Log is sequential with the most recent events listed at the top of the log The Event Log buffer can store 100 events Oldest events are replaced by the most recent even...

Страница 18: ...n occurs on any automatic detection zone The green System Normal LED will turn OFF The buzzer will begin to pulse The alarm zone will be indicated by the Alarm Zone red LED flashing ON Depending on de...

Страница 19: ...rm and Fault conditions are annunciated via an LED flash code sequence The flash code displayed by the Service System LED and corresponds to the indicated zone and condition I D The flash code list is...

Страница 20: ...e LED will turn OFF f A Fault condition will be displayed g Press the System Reset button and reset the simulated actuation devices h Fault will clear and the AdvantageDC will return to Normal operati...

Страница 21: ...or storing the AdvantageDC control panel for extended periods b The AdvantageDC control panel will not operate when the battery disconnect switch is in the System Power OFF position c No LED or audib...

Страница 22: ...ctuation zone and I O relay operation performed by programming the AdvantageDC via the user PC and interface module Momentary Transfer A relay option which allows for a one second transfer when the co...

Страница 23: ...rm Transfer on fault condition Follows function of local audible Silenceable Relay 3 0 0 Transfer on single detection alarm Transfer on cross zoning detection alarm Momentary transfer when Reset butto...

Страница 24: ...s o Relays 1 FACP Alarm relays transfer per mapping per fire detection o FACP Fault relay transfers as actuators are fired The system cannot be reset from an Alarm condition until the damaged detectio...

Страница 25: ...med as Transfer on Fault condition Relay 2 transfers o Relay 5 FACP Fault Fault relay transfers Detection zone 2 goes into alarm due to higher temperature linear heat detector fire detection o Both ac...

Страница 26: ...itial Inspection Verification of system performance must be performed upon completion of initial installation Use the installation verification checklist included as Appendix 8 1 to record verificatio...

Страница 27: ...rs from the Advantage panel Remove two 6 screws on either side of the battery bracket Unplug the 9 vdc battery and replace with a new battery Record the installation date on the battery replacement la...

Страница 28: ...res loose or broken connectors and pin socket connections Look for evidence of corrosion on connectors pins and sockets Check for connectors not completely engaged and pin sockets not completely inser...

Страница 29: ...fired Inspect wiring to look for breaks or chafing Take care not to apply voltage to the actuation circuit if using a multimeter or other device to check for continuity 6X Auxiliary Switch Check for c...

Страница 30: ...ure Other LED Indicators Description Troubleshooting Power Fault Power Fault Check to be sure both primary and secondary power connectors are plugged into the control panel Open the cover of the Advan...

Страница 31: ...rtcut to your PC desktop Figure 42 AdvantageDC PC Desktop Utility Shortcut The software default password for the Advantage PC utility is tfsinc As part of the PC Utility installation a PC USB to RS485...

Страница 32: ...pulse 2X and all LEDs will flash 2X indicating programming mode is enabled The AdvantageDC control panel will exit from programming mode and will return to normal operation if no operator action is ta...

Страница 33: ...own after opening To change the default settings select deselect or revise timing as needed then select Upload Configuration to Control Panel It is recommended to save a copy of the configuration on y...

Страница 34: ...o capture any non Normal conditions or other actions which occur while the AdvantageDC is operating Events such as Field Wiring off normal System Reset and Set Clock are recorded Events are time stamp...

Страница 35: ...re useful tools to help in periodic maintenance and troubleshooting The Monitor Mode function is accessed by selecting the Monitor tab on the start menu Figure 98 Monitor Mode screen 7 2 Bluetooth Sma...

Страница 36: ...C panel Press the Push to Enable button on the module A Blue LED will illuminate indicating the Bluetooth Comm module is ready to communicate Press and hold the System Reset and Alarm Silence buttons...

Страница 37: ...a default email address This allows you to easily send saved files such as Event Logs and Configurations to the email on record The Event log may be viewed and downloaded by pressing the Event Log bu...

Страница 38: ...Auxiliary Relays Settings include logical mapping and timing If a configuration is changed its good practice to save the configuration to your device and possibly email a copy to be kept as a permanen...

Страница 39: ...Event Log may be erased as needed but it s a good practice to save a copy of the log and store the Event Log files using a logical naming convention for easy retrieval and reference Year Month Day and...

Страница 40: ...nics and operating characteristics for the Advantage Lithium and the Advantage DC panels are the same The primary power source Lithium Thionyl Chloride batteries vs 24 VDC input and the secondary powe...

Страница 41: ...Code Date of Last Inspection Primary Battery Date Code Secondary Battery Date Code AdvantageDC Panel Programming Detection Zone Actuation Zone circle one in each detection zone Actuation Testing Verif...

Страница 42: ...Alarm conditions present 14 Actuation disable engaged 15 Ground fault 16 Abort Switch fault 17 High Temperature fault Comments B Control Panel Inspection Yes No N A 1 Is the control panel located outs...

Страница 43: ...sor Actuator and Field Wiring Yes No N A 1 Have there been any changes to the installation location which may affect system operation 2 Is the manual release switch located in the path of egress and u...

Страница 44: ...e control panel s life Refer to the chart below for guidance 8 4 Spare and Replacement Parts List The following is a list of spare and replacement parts as described in the Installation Operation and...

Страница 45: ...on Primary Secondary Power Circuits Qty 2 Alarm Silence Yellow LED steady on Abort Switch Input Qty 1 Local Audible Annunciator Qty 1 Front Panel Controls Batteries Push to Test button Chemistry Nicke...

Страница 46: ...ross section 16 18 AWG Gold terminal contacts only Gold terminal contacts only IP67 sealed connectors IP67 sealed connectors Auxiliary Contacts Pluggable Terminal Strips Maximum Voltage 30 vdc Conduct...

Страница 47: ...ays after discovery thereof to Seller prior to the expiration of one 1 year after shipment and or installation by Seller and further provided that if Seller so instructs such article or part thereof i...

Страница 48: ...art no 830049 xx xx AdvantageDC Dual Zone Fire Control Panel Manual part no 650 830049 rev June 13 2022 Total Fire Systems inc P O Box 1408 Wake Forest North Carolina 27588 U S A Tel 919 556 9161 www...

Отзывы: