T-200 Series UPS User Manual 

11

 

 
 
4.4.3 Second message line of the LCD 

 

VERSION XXXX 

Micro controller software version of the UPS. 

BYPASS FAILURE 

This message shown that there is a problem of the static bypass system, 
please call for service. 

FAULT 2 

“INVERTER FAILURE” Inverter can not generate AC output. Turn-off the 
UPS and then turn it on again. If it doesn't start, please call for service. 

FAULT 3 

The temperature on the heatsink inside the UPS cabinet has exceeded 90 
°C three times in the last 30 minutes. In such a case, the UPS should be 
turned-off and on again to resume normal operation. 

FAULT 4 

"Output Failure" alarm has occurred 4 times in the last 30minutes. Please 
call for service.   

BAT.AUTONOMY END 

Battery autonomy has finished during line failure. 

BATTERY FAILURE 

Battery test aborted. Battery test performed whilst battery not perfectly  
charged or battery cells damaged. Please call service 

FAULT 7 

Rectifier fault. Please call service for checking the UPS. 

FAULT 8 

Line voltage out of tolerance.  

ONLINE MODE 

UPS operating mode is ONLINE mode. 

ECONO MODE 

(optional)

 

This message shown the alternate, operating mode is active OFFLINE. 

 
 

 

 
 
 

4.5

 

Automatic battery test system (optional) :  

 

There are some conditions to make this test ( e. g availability of by-pass supply, line synchronization,. a 
min.  time  requirement  since  the  last  line  failure  etc.).  The  first  test  is  performed  automatically,  8  hours 
later following the first turning on of the UPS. There is a 65 hours interval between two successive tests 
an each test lasts about 36 seconds. 
 
During  the  battery  test  operation,  the  inverter  power  will  be  supplied  from  batteries.  At  the  end  of  this 
test,if the battery voltage is below a predetermined value, " BATTERY FAILURE / BATTERY LOW

 

Fault 

messages appear on the LCD panel and the UPS starts operating in By-Pass mode. 
 
In this case you have to call your service. 
 
If the batteries are in normal conditions the system will start operating in normal mode after 36 sec. 
 
This test protects  your operation  against  unexpected  battery failures, and indicates  you  if there are any 
damaged  batteries.  It  also  discharges  the  batteries  periodically,  which  is  a  good  thing  for  extending 
battery life. 
  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание T-200 Series

Страница 1: ...USER MANUAL T 206 6 kVA T 207 7 5 kVA T 210 10 kVA T 200 SERIES UNINTERRUPTIBLE POWER SUPPLIES 3 Phase Input 1 Phase Output...

Страница 2: ......

Страница 3: ...rupted 9 4 4 Operator Control Panel 9 4 4 1 Push Buttons 10 4 4 2 First Message Line Of The LCD 10 4 4 3 Second M L ALARMS Of The LCD 11 4 5 Automatic Battery Test System optional 11 V OPTIONAL EQUIPM...

Страница 4: ...ed service personnel The output may be energized when the unit is not connected to a mains supply Risk of electric shock hazardous live parts inside this unit are energized from the battery supply eve...

Страница 5: ...wave output PWM and IGBT technology Microprocessor controlled main controller board Static STS and maintenance by pass LCD Liquid Crystal Display display Alarm history Memory for max 64 alarms Automa...

Страница 6: ...of power transistor IGBT and pulse width modulation PWM Inverter converts dc bus voltage into an alternative voltage like line voltage And provides this voltage and frequency being fixed Static Trans...

Страница 7: ...Voltage 220 230 240 VAC Output Voltage Tolerance 1 Output Frequency 50 Hz Output Frequency Tolerance Line Synchronized 1 Free Running 0 2 Efficiency 100 Load 85 87 Crest Factor 3 1 Overload capacity 1...

Страница 8: ...Figure 2 2 1 6 7 5 10 kVA Rear view 6 7 5 10 kVA Model S Rear view Battery Fuse AC Output Terminals DB9 Port PK1 On Off Switch AC Output 6 7 5 10 kVA Model A Rear view Battery Fuse DB9 Port PK1 On Off...

Страница 9: ...Optional 3 2 Location Selection The UPS is designed to be installed in a protected environment The following conditions should be prohibited 1 Blocking the airflow intake and outlet It is recommended...

Страница 10: ...tected by a circuit breaker 1 Before connecting AC and DC power to the UPS make sure that the On Off Switch PK1 Main Switch and battery fuse on the rear panel are in the 0 position OFF 2 Connect the A...

Страница 11: ...audible alarm will sound intermittently Now the output receptacles are supplied from the battery source 4 Connect the power again and see that LINE FAILURE alarm is off 5 Now your UPS is ready to oper...

Страница 12: ...cords into outlets 4 3 When Utility Power Is Interrupted In case the utility power is interrupted the UPS converts the built in battery source to output terminals immediately to protect your critical...

Страница 13: ...s message the sound button enables disables sound alarm SOUND ON SOUND OFF Audible alarm is active Audible alarm is not active disabled by the user Each press to this button will change the status BAT...

Страница 14: ...out of tolerance ONLINE MODE UPS operating mode is ONLINE mode ECONO MODE optional This message shown the alternate operating mode is active OFFLINE 4 5 Automatic battery test system optional There ar...

Страница 15: ...unicate so that the computer system is warned of impending UPS shutdown Software T MON RUPS RUPSII UPSILON 2000 and SNMP devices is available for most operating systems and is supplied with a signalin...

Страница 16: ...ftware supplied with the module or it is possible to monitor the UPS through an Internet Browser It is possible to shutdown the servers or users with Client mate Software that communicates with SNMP m...

Страница 17: ...system from several different locations at the same time 5 5 UPS Port Sharer Multiple server shut down unit Using one of this units you can automatic shut down of 4 8 servers or PC where without LAN...

Страница 18: ...T 200 Series UPS User Manual 15...

Страница 19: ...T 200 Series UPS User Manual 16 Connection Diagram Of The RMP COM1 T MON...

Страница 20: ...iced only by authorized people In case of a persistent failure or problem properly turn off the unit first Then review the following check list Be prepared to answer the questions before calling the s...

Страница 21: ...not apply if the product has been subjected to physical abuse improper installation unauthorized service or modification 2 The sole responsibility of corporation under this warranty shall be limited t...

Страница 22: ...AGKK3802 09 2013...

Отзывы: