T-200 Series UPS User Manual
10
4.4.1 Push buttons
1- Sound on-off button :
When you push this button it will disable the audible alarm on the UPS. If you
want to enable the sound alarm again
you have to push the DISPLAY SELECT button for 2 sec.
2- Display select button :
Each time you push this button, you can see one of the parameters of the
FIRST (up) MESSAGE LINE.
4.4.2 First message (Up) line of the LCD
LOAD
The percentage of the load connected to the UPS output during this message
the sound button enables/disables sound alarm.
OUTPUT
UPS output Voltage during this message the sound button enables/disables
sound alarm.
BATTERY
UPS battery Voltage during this message the sound button enables/disables
sound alarm.
LINE
Line Voltage at the UPS input during this message the sound button
enables/disables sound alarm.
LANG. ENGLISH
Display language during this message the sound button enables/disables sound
alarm.
FREQ
UPS output frequency during this message the sound button enables/disables
sound alarm.
SOUND ON
SOUND OFF
Audible alarm is active.
Audible alarm is not active.( disabled by the user)
Each press to this button
will change the status.
BATT.USED
It shows battery operation time (the time passed after the last line failure alarm)
MOD: ONLINE
MOD : ECONO
This parameter determines the operation type of the UPS. Econo mode means
that if the mains is okay the load is fed from mains if the line failure alarm
occurs UPS feeds the load. (OFFLINE UPS)
SYNC:OK
COMM:OK
UPS and LINE synchronization status.
Communication active. (If PC sends data to UPS COMM:OK message will be
showed for 3 seconds)
LOG. EVENT
Your UPS records and keeps all its faults and alarms up to 64 events in its
memory for future monitoring. Events are recorded in the order of occurrence.
The upper line on LCD indicates the recorded event number, “000” being the
last event. The lover line shows the name of the event. While monitoring the
recorded events, you can return to event number ”000” by pressing the “sound
off” button for a relatively long time.
Display Select
Sound
On-Off Button
Figure 4.1
Control Panel
LCD
Status Indicators
Содержание T-200 Series
Страница 2: ......
Страница 18: ...T 200 Series UPS User Manual 15...
Страница 19: ...T 200 Series UPS User Manual 16 Connection Diagram Of The RMP COM1 T MON...
Страница 22: ...AGKK3802 09 2013...