T-200 Series UPS User Manual 

9

 

 

IV. OPERATING PROCEDURE

 

 
 
 

 

4.1 Turn On procedure 

 

1.

  Turn on the Main Switch and battery fuse on the rear panel to "

1

" position.  

 

(There is line voltage at the output.)

  

 
2.

  Turn on the On-Off Switch PK1 on the rear panel to the "

1

" position. Turn on the power switches on  

your critical load after the "Inverter" indicator (green light) is turned on. 

(There is inverter voltage at the 

output.)

 

 
 
 

4.2 Turn Off procedure 

 
1.

  Turn off all the power switches on your critical equipments that are connected to the UPS. 

 
2.

 Turn off the On-Off switch PK1 and the Main Switch to "

0

" position. 

 

 
CAUTION 

 

A-

  For daily TURN ON / TURN OFF operation, it is recommended to keep the Main switch and  

 

battery fuse at "

1

" position to ensure proper battery operation. 

 
B-

  If the Main switch is in "

1

" position the line power will be supplied to output receptacles  

 directly. DO NOT insert objects other than equipment power cords into outlets. 
 

 
 

 

4.3 When Utility Power Is Interrupted 

 
In  case  the  utility  power  is  interrupted,  the  UPS  converts  the  built-in  battery  source  to  output  terminals 
immediately to protect your critical loads from loss of data or damage. 
Battery back-up time is more than 10 minutes for full load and can be extended by removing non-critical 
loads. 
After an utility power blackout, the audible alarm and "

LINE FAILURE

 " indicator on LCD panel will start 

operating.1 minute after the power is interrupted, and you will see the message "

BAT.USED :001min

"on 

the LCD panel. This will show you for how long the batteries were used since the power was interrupted. 
When the "

Battery Low

" alarm appears, you have to shut down all your loads immediately, and turn the 

main switch 

PK1

 to position "

0

". 

 
 
 
4.4 Operator Control Panel  

 
The panel can be divided into two functional sections; ”LED indications” and “control and display”. As can 
be seen the upper section consists of leds which indicate the operation mode.  
 
This panel shows the systems operation such as input and output Voltages, Frequency, % Load  
Status etc. by LCD. 
 
 
 
 
 

Содержание T-200 Series

Страница 1: ...USER MANUAL T 206 6 kVA T 207 7 5 kVA T 210 10 kVA T 200 SERIES UNINTERRUPTIBLE POWER SUPPLIES 3 Phase Input 1 Phase Output...

Страница 2: ......

Страница 3: ...rupted 9 4 4 Operator Control Panel 9 4 4 1 Push Buttons 10 4 4 2 First Message Line Of The LCD 10 4 4 3 Second M L ALARMS Of The LCD 11 4 5 Automatic Battery Test System optional 11 V OPTIONAL EQUIPM...

Страница 4: ...ed service personnel The output may be energized when the unit is not connected to a mains supply Risk of electric shock hazardous live parts inside this unit are energized from the battery supply eve...

Страница 5: ...wave output PWM and IGBT technology Microprocessor controlled main controller board Static STS and maintenance by pass LCD Liquid Crystal Display display Alarm history Memory for max 64 alarms Automa...

Страница 6: ...of power transistor IGBT and pulse width modulation PWM Inverter converts dc bus voltage into an alternative voltage like line voltage And provides this voltage and frequency being fixed Static Trans...

Страница 7: ...Voltage 220 230 240 VAC Output Voltage Tolerance 1 Output Frequency 50 Hz Output Frequency Tolerance Line Synchronized 1 Free Running 0 2 Efficiency 100 Load 85 87 Crest Factor 3 1 Overload capacity 1...

Страница 8: ...Figure 2 2 1 6 7 5 10 kVA Rear view 6 7 5 10 kVA Model S Rear view Battery Fuse AC Output Terminals DB9 Port PK1 On Off Switch AC Output 6 7 5 10 kVA Model A Rear view Battery Fuse DB9 Port PK1 On Off...

Страница 9: ...Optional 3 2 Location Selection The UPS is designed to be installed in a protected environment The following conditions should be prohibited 1 Blocking the airflow intake and outlet It is recommended...

Страница 10: ...tected by a circuit breaker 1 Before connecting AC and DC power to the UPS make sure that the On Off Switch PK1 Main Switch and battery fuse on the rear panel are in the 0 position OFF 2 Connect the A...

Страница 11: ...audible alarm will sound intermittently Now the output receptacles are supplied from the battery source 4 Connect the power again and see that LINE FAILURE alarm is off 5 Now your UPS is ready to oper...

Страница 12: ...cords into outlets 4 3 When Utility Power Is Interrupted In case the utility power is interrupted the UPS converts the built in battery source to output terminals immediately to protect your critical...

Страница 13: ...s message the sound button enables disables sound alarm SOUND ON SOUND OFF Audible alarm is active Audible alarm is not active disabled by the user Each press to this button will change the status BAT...

Страница 14: ...out of tolerance ONLINE MODE UPS operating mode is ONLINE mode ECONO MODE optional This message shown the alternate operating mode is active OFFLINE 4 5 Automatic battery test system optional There ar...

Страница 15: ...unicate so that the computer system is warned of impending UPS shutdown Software T MON RUPS RUPSII UPSILON 2000 and SNMP devices is available for most operating systems and is supplied with a signalin...

Страница 16: ...ftware supplied with the module or it is possible to monitor the UPS through an Internet Browser It is possible to shutdown the servers or users with Client mate Software that communicates with SNMP m...

Страница 17: ...system from several different locations at the same time 5 5 UPS Port Sharer Multiple server shut down unit Using one of this units you can automatic shut down of 4 8 servers or PC where without LAN...

Страница 18: ...T 200 Series UPS User Manual 15...

Страница 19: ...T 200 Series UPS User Manual 16 Connection Diagram Of The RMP COM1 T MON...

Страница 20: ...iced only by authorized people In case of a persistent failure or problem properly turn off the unit first Then review the following check list Be prepared to answer the questions before calling the s...

Страница 21: ...not apply if the product has been subjected to physical abuse improper installation unauthorized service or modification 2 The sole responsibility of corporation under this warranty shall be limited t...

Страница 22: ...AGKK3802 09 2013...

Отзывы: