background image

TUNING THE ER1200

Continued

Span Pot Rotation Effect

Figure 5: Span Adjustment

Typically, Gain and Stability adjustments are
not needed. However, the following general
guidelines can be followed to fine tune your
system:

Rotating the gain pot clockwise increases the
system gain and decreases the system
response time. Too little gain will result in slow
response and inaccurate signal tracking. Too
much gain will result in system instability, fast
vibration, or in the feedback signal
overshooting the setpoint signal when a large
step change in setpoint is initiated.

Rotating the stability pot clockwise will
decrease the reset time and quicken the
addition of gain into the system. This can
again result in setpoint overshoot. Rotating
the pot counter-clockwise will increase the
reset time and dampen the control response
to a step change in setpoint.

The stability adjustment does not interact with
any of the other adjustments, however, if the
gain or deadband pots are turned at this point,
the zero and span will need to be readjusted
per the procedure outlined above.

Reaction To Step Change In Setpoint

Figure 6: System Response

If the system is experiencing a slow oscillation,
decrease the gain by rotating the pot counter-
clockwise until the oscillation stops. If the
oscillation is rapid, increase the reset action by
rotating the stability pot clockwise until the
oscillation stops. These settings will be the
maximum gain and minimum reset time that
can be used with the system as it is configured.
If the feedback signal severely overshoots the
setpoint signal when a change in setpoint is
made, turn the stability pot counter-clockwise
alternately with the gain pot (also counter-
clockwise), until the overshoot is eliminated.

For very precise tuning of the control, a dual
channel storage oscilloscope is recommended
so that the user can see the effect of gain and
integral adjustment on the response of the
system. One channel of the scope is used to
monitor the setpoint voltage and the other
channel to monitor the feedback voltage. The
gain and integral adjustments have the
greatest effect on the system response to a
step change in setpoint signal. The control
can be tuned in this fashion for millisecond
response to step changes in setpoint from 0 to
100%. Remember, after adjusting the gain
pot, the control will need to have its zero and
span readjusted.

7

Form # 1925     Rev. 4/06     TESCOM

Signal (mA)

Output

0

Time

Feedback Response

Over Damped

Under Damped

Critically 
Damped

Содержание ER1200 Series

Страница 1: ...Feedback Mode 1 External Feedback Mode 2 SPECIFICATIONS 3 ELECTRICAL INSTALLATION 3 4 ER1200 CONFIGURATION Configure Setpoint Signal 5 Configure Analog Output Signal 5 Configure Feedback Signal 5 TUN...

Страница 2: ...inlet valve and increases output pressure If the feedback is above setpoint the ER1200 opens its exhaust valve to decrease the output pressure Every 25 milliseconds the feedback is compared to the se...

Страница 3: ...either a pressure reducing or back pressure regulator shown with a ratio actuated pressure reducing regulator Figure 2 If the feedback signal is below setpoint the ER1200 opens its inlet valve and inc...

Страница 4: ...PSIG Minimum 10 PSIG above desired output pressure Media Clean dry inert gas Environment Temperature 10 F to 150 F Flow Stream Materials 300 Series SST Buna N 6000 Series Aluminum Brass Nickel Silico...

Страница 5: ...Form 1925 Rev 4 06 TESCOM 4 Current Setpoint Active Source Voltage Setpoint Current Setpoint Passive Source...

Страница 6: ...L MODE JP1 Current Setpoint Mode Install Jumper Voltage Setpoint Mode Remove Jumper RANGE JP2 4 20 mAmp 1 5 Volts Install Jumper on pins 1 2 0 10 Volts Install Jumper on pins 2 3 CONFIGURE ANALOG OUTP...

Страница 7: ...sed deadband voltage This can result in drifting of the feedback signal or no response to a small change in setpoint signal Apply a setpoint signal of about 2 5 4 4 mAmps 1 1 VDC if 1 5 VDC or 0 25 VD...

Страница 8: ...ystem is experiencing a slow oscillation decrease the gain by rotating the pot counter clockwise until the oscillation stops If the oscillation is rapid increase the reset action by rotating the stabi...

Страница 9: ...ressure line The system design has components that can cause a delay in down stream transducer response while the up stream pressure is allowed to build up pressure differential between measurement po...