SPECIFICATIONS
Enclosure
NEMA 4 housing
Mounting
2 10-32 UNF mounting holes
Power Requirement
24 Volts DC +/- 2 volts
150 milliAmp typical current draw
Input Signals
All signals are field configurable using
onboard jumpers:
Setpoint:
4-20 mAmp, 1-5 VDC or
0-10 VDC
Feedback: Internal (0-100 PSIG) or
external
External
Feedback: 4-20 mAmp, 1-5 VDC or
0-10 VDC
Inlet Pressure
Maximum: 120 PSIG
Typical:
110 PSIG
Minimum: 10 PSIG above desired
output pressure
Media
Clean, dry, inert gas
Environment
Temperature: -10°F to +150°F
Flow Stream Materials
300 Series SST, Buna-N, 6000 Series
Aluminum, Brass, Nickel, Silicon, Gold,
Glass, RTV
Performance
Total Accuracy: +/- 0.25%
Linearity:
+/- 0.1%
Repeatability:
+/- 0.12%
Flow Capacity: Cv = 0.03
3
Form # 1925 Rev. 4/06 TESCOM
1
White
+ Setpoint
2
Brown
- Setpoint
3
Green
+ Feedback
4
Yellow
+ Analog Output
5
Black
Power Ground
6
Red
+ TTL Output
7
Orange
+ 24 VDC Power
8
Violet
*
Secondary Ground
Wire Number
Wire Color
Function
ELECTRICAL INSTALLATION
*
Not available for ER1200-2 and ER1200-2-1