background image

TROUBLESHOOTING

ER1200 Symptom

Cause

Remedy

8

Form # 1925     Rev. 4/06     TESCOM

Unable to maintain outlet
pressure

Positive output pressure
with zero setpoint

Outlet pressure is equal
to inlet pressure 

Outlet pressure does not
follow setpoint changes

Outlet pressure becomes
uncontrollable (unstable
or unable to establish
setpoint)

ER1200 exhaust valve
leaking

ER1200 supply pressure is
not high enough

ER1200 inlet solenoid valve
leaking

ER1200 supply pressure
exceeds the maximum

ER1200 not getting a
feedback signal

ER1200 jumpers not
configured correctly

ER1200 GAIN, INTEGRAL,
or DEADBAND are out of
adjustment

The feedback signal reacts to
a process change at a slower
bandwidth than the ER1200
(25 milliseconds)

There are leaks in the
downstream pressure line

The system design has
components that can cause a
delay in down stream
transducer response while
the up stream pressure is
allowed to build up (pressure
differential between
measurement point and
source)

Return unit to factory for
replacement of valve

Check the incoming pressure
to the ER1200 and ensure that
it is between 10 to 20 PSIG
above the maximum desired
output pressure

Return unit to factory for
replacement of valve

Lower supply pressure to less
than 115 PSIG

Check transducer wiring and
feedback jumper settings 

Reconfigure jumper settings
according to page

Read TUNING THE ER1200

(page 6)

in this manual and

readjust the gain and pots per
that section

Replace the transducer with
one that has a full range
response time at least as fast
as that of the ER1200

Locate and eliminate all leaks

Eliminate the flow restriction, or
slow down the ER1200
response time by restricting the
flow of supply pressure into the
ER1200

Содержание ER1200 Series

Страница 1: ...Feedback Mode 1 External Feedback Mode 2 SPECIFICATIONS 3 ELECTRICAL INSTALLATION 3 4 ER1200 CONFIGURATION Configure Setpoint Signal 5 Configure Analog Output Signal 5 Configure Feedback Signal 5 TUN...

Страница 2: ...inlet valve and increases output pressure If the feedback is above setpoint the ER1200 opens its exhaust valve to decrease the output pressure Every 25 milliseconds the feedback is compared to the se...

Страница 3: ...either a pressure reducing or back pressure regulator shown with a ratio actuated pressure reducing regulator Figure 2 If the feedback signal is below setpoint the ER1200 opens its inlet valve and inc...

Страница 4: ...PSIG Minimum 10 PSIG above desired output pressure Media Clean dry inert gas Environment Temperature 10 F to 150 F Flow Stream Materials 300 Series SST Buna N 6000 Series Aluminum Brass Nickel Silico...

Страница 5: ...Form 1925 Rev 4 06 TESCOM 4 Current Setpoint Active Source Voltage Setpoint Current Setpoint Passive Source...

Страница 6: ...L MODE JP1 Current Setpoint Mode Install Jumper Voltage Setpoint Mode Remove Jumper RANGE JP2 4 20 mAmp 1 5 Volts Install Jumper on pins 1 2 0 10 Volts Install Jumper on pins 2 3 CONFIGURE ANALOG OUTP...

Страница 7: ...sed deadband voltage This can result in drifting of the feedback signal or no response to a small change in setpoint signal Apply a setpoint signal of about 2 5 4 4 mAmps 1 1 VDC if 1 5 VDC or 0 25 VD...

Страница 8: ...ystem is experiencing a slow oscillation decrease the gain by rotating the pot counter clockwise until the oscillation stops If the oscillation is rapid increase the reset action by rotating the stabi...

Страница 9: ...ressure line The system design has components that can cause a delay in down stream transducer response while the up stream pressure is allowed to build up pressure differential between measurement po...

Страница 10: ...ev 4 06 TESCOM Tescom Industrial Controls Systems Group 12616 Industrial Boulevard Elk River Minnesota 55330 2491 Toll Free 800 447 1250 Tel 763 241 3238 Fax 763 241 3224 e mail systems tescom com www...

Отзывы: