background image

ISU-689:2016/GB 

 

 

 
3.4. Connection to the gas installation 

 

All connections should be made by an appropriately  
qualified person, in accordance with applicable standards 
and regulations, in particular those relating to safety.  

 

Connect a gas supply pipe directly to the connector of the boiler gas 
unit by means of standard connector subassembly. It is necessary to 
install a gas filter on the gas supply pipe. This filter is not included in 
the standard boiler equipment. The gas filter is necessary for a 
proper operation of a gas unit and a burner. Install a cut-off valve on 
the gas pipe in an accessible place. 

 

 

 

 

 
 
A - (

G5/4”

)

 

 Power supply of the CH 

installation 

 

(G5/4”)

 

 return from the CH 

installation 

 

(G1”)

 

 Gas connection 

 

(G3/4”)

 - Drain from the safety 

valve / emptying the boiler 

 (

Ø

 25)

 - Condensate drain

 

Fig. 3.4.1 

 Description of the connectors

 

 

3.5. Connection of the boiler to a water system  

 

Power connector and connector of return of the central heating 
boiler should be screwed to the installation. Install a water filter on a 
water return from central heating system (in front of the connection 
with the pump). The filter is not included in standard boiler 
equipment. The central heating system should be thoroughly rinsed 
out before the boiler is connected. In the central heating system it is 
permitted to use as a heat carrier any antifreeze fluids which can be 
used in central heating systems.  
The cut-off valves needs to be installed between the boiler and 
central heating system so that the boiler could be dismounted 
without draining the system. 

 

Before installing the boiler thoroughly flush the central 
heating system to free it from any solid impurities.    
It is recommended that after first start-up of the boiler 

                and heating up of the installation drain the water from 
                the system to remove residues of pastes metallurgical 
                and precautionary measures of heaters. These activities 
                would benefit for the operation of the device, its 
                parameters and components life. 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 3.5.1 

 Installation requirements 

KW

 

 Exhaust ventilation, 

KN

 

 Air inlet, 

3W

 

 three-way valve, 

TS

 

 Tank temp. 

sensor, 

KS

 

 Floor drain, 

FW

 

 Water filter, 

FS

 

 gas filter. 

 

After the boiler installation it is necessary to: 

 

Fill the heating system with water. Filling the system should be 
done slowly to allow the air outflow through the air vent valve 
mounted in the boiler; also check the complete air outlet from all 
components of the system.

 

The pressure in the cold installation 

should be 1.2 ÷ 1.5 bar.

 

 

Check whether connections of the boiler and in the central heating 
system are tight. 

 

Ensure that pipes of water and heating installation are not used as 
grounding the electrical installation.  

 

Connect the outlet of safety valves to the floor drain to avoid 
flooding the room (where the boiler is installed) as a result of 
protection devices. Such outlets should be carried out so as to 
avoid damage in the case of opening of the valve and outflowing of 
the hot fluid. 

 

3.5.2. Cleaning the installation and water treatment for 
filling the CH installation 

 

In all elements of the CH installation there are processes of scaling, 
corrosion and similar phenomena. The boiler is the most expensive 
part of the installation and it is important to ensure that the heat 
exchanger and other components are protected against these 
processes. Correct preparation of the CH system for the operation 
shall be carried out by two operation: cleaning the installation and 
water treatment for the operation of the installation.  

 

Cleaning the installation  

In new installation there may be remnants of the installation such as 
solder residues, welding residues, flux residues, oil residues, grease 
residues, or corrosion products - especially in old installation. In the 
first place, both new and old installations should be cleaned with 
clean water to remove solid waste. his operation must be carried out 
without the boiler installed. The next step is to chemical cleaning the 
installation. For cleaning new and old installations, use a suitable 
cleaning agent, like Fernox Cleaner F3 (for old and heavily 
contaminated installations use Cleaner F5). After this cleaning the 
system should be rinsed with mains water. 

 

Water treatment for filling the installation  

Use the water with following parameters to fill the installation: pH 
from 6,5 to 8,5 units, general hardness not more than 

10 °n (~ 18°F). 

For filling do not use demineralized water or distilled water. For 
proper protection against scale and corrosion of the installation, use 
a suitable inhibitor (passivator) e.g. Fernox Protector F1. In addition, 
there can also be used a liquid heat carrier such as HP-5 or antifreeze 
such as Fernox Alphi 11. In situations where water is very hard, the 
use of the HP-5 liquid heat carrier effectively reduces the risk of 
scaling of the heat exchanger.  

 

Low-temperature circuits 

In low-temperature zones it is recommended to treat the water by 
using HP-5 liquid heat carrier or alternatively Fernox biocide AF10.  

 

Filtering technology 

In addition, modern filters with magnetic and cyclone effects are 
recommended for the high quality of the current heating system.  
 
The method and amount of use of the particular products for 
cleaning the installation and for water treatment should be used 
according to the instructions of the product given by the 
manufacturer.  
Cleaning the installation and water treatment should be made by 
authorized installers or service personnel. 

 

 
 
 

Содержание ECOCONDENS CRYSTAL 100

Страница 1: ...INSTRUCTION MANUAL INSTALLATION OPERATION AND MAINTENANCE Gas fired condensing central heating boilers SYSTEM BOILERS ECOCONDENS CRYSTAL 80 ECOCONDENS CRYSTAL 100...

Страница 2: ...lters are not included in a basic boiler equipment An example of connecting a boiler to these systems is presented on fig 3 5 1 All defects caused by lack of filters on central heating or gas supply w...

Страница 3: ...nnecting the boilers in the cascade system 10 4 BOILER ADJUSTMENT AND PRELIMINARY SETTING 10 4 1 INTRODUCTORY REMARKS 10 4 2 ADJUSTING THE BOILER TO COMBUST ANOTHER TYPE OF GAS 11 BOILER CAN BE ADJUST...

Страница 4: ...esign and technical specifications of the boiler 2 2 1 Main units of the boiler 2 1 Flue gas water heat exchanger 2 2 Temperature limiter of flue gas 2 3 Temperature limiter of air collector 2 4 Ignit...

Страница 5: ...parameter P06 If the heating water temperature exceeds 97 C an additional temperature limiter is activated the burner is turned off until the hot water temperature drops below 81 C The system of conti...

Страница 6: ...he boiler from the SUMMER function CH only to the WINTER function CH and DHW A 3sec The entrance to the TEST mode B The reset the displayed error B 3sec Preview of the parameters C Turns on or off the...

Страница 7: ...This prepared cables connect according to Fig 3 1 3 1 Fig 3 1 3 1 Wire colors L brown N blue PE yellow green If you need to replace the supply wire use a minimum cord of 3 x 0 75 mm2 The boiler supply...

Страница 8: ...ing the back and bottom of the boiler Due to the heavy weight 2 people are required Fig 3 3 1 Mounting dimensions Mounting method on hooks Mounting method with hanger Fig 3 3 2 Mounting method Fig 3 3...

Страница 9: ...n are not used as grounding the electrical installation Connect the outlet of safety valves to the floor drain to avoid flooding the room where the boiler is installed as a result of protection device...

Страница 10: ...a blowing fan 3 The boiler is designed for cooperation with the flue gas air system with a diameter of 100 flue gas and air and in a collective cascade system where the flue gas exhaust from a single...

Страница 11: ...he sum of the lengths of the flue gas air system when the elbow is mounted on the flue gas system or the air supply system to the boiler Table 3 8 3 1 Reduce the length of the installation elbows Exam...

Страница 12: ...iler connection with PC MASTER and SLAVE communication connectors are not located in the control console casing Connectors appropriately described are located in bulk inside the boiler Fig 3 9 1 1 Des...

Страница 13: ...r in tank EP External cascade pump ES Outdoor temperature sensor CS Temperature sensor in supply collector 3W three way valve Boilers cooperating in the cascade system are connected in series by a cab...

Страница 14: ...ctrical installation was made in accordance with applicable regulations the correctness of connections between the boiler and the chimney was checked and confirmed by a qualified chimney service 4 3 B...

Страница 15: ...mming mode is switched off 4 5 1 Preview of parameters value You can review the parameter values without the need of change To do this use the B 3sec button After starting LOCAL INSTALLATION mode the...

Страница 16: ...ow pressure fill the installation with a filling valve mounted on the installation Start the boiler in the TEST service mode the boiler will start the circulation pump and start the ignition Due to la...

Страница 17: ...de The symbol W11 shown on the picture will appear on the screen Press B button to activate the boiler 5 4 Diagnosis When the operation of the boiler will be incorrect the display shows the symbol E a...

Страница 18: ...ctrical connections Error 96 description When the P14 parameter is set on a value other than zero the controller does not detect the presence of the sensor closed open Please check the sensor ES conne...

Страница 19: ...ont cover 1 Loosen the screws K1 2 Pull the cover behind its lower edge to release from the latches 3 Move the cover up Dismantling the side cover 4 Unscrew the screws K2 5 Move the cover up Fig 6 1 1...

Страница 20: ...gas 6 1 3 Thermal protection of the heat exchanger The heat exchanger is equipped with thermal protection BW1 and BW2 protecting against improper assembly of the exchanger If the exchanger is mounted...

Страница 21: ...ceeding the limits of temperature protection against exceeding the pressure limits check whether vents are present with correct dimensions and operating according to the installed device In this regar...

Страница 22: ...ELV Contact Thermal fuse item 2 2 Supply voltage from the controller SELV Activation temperature 115 C Return NTC sensor item 2 14 Supply item 2 15 Supply voltage from the controller SELV 12K 25 C 363...

Страница 23: ...e the power level with D and E buttons by 1 use F button to set the min power or G button to set the max power The PWM signal for the cascade pump is selected according to the operation algorithm of b...

Страница 24: ...g 7 2 3 2 1 Diagram of connecting boilers for DHW needs in divided configuration with one three way valve Diagram of connecting 4 boilers two of which are intended for heating DHW Each boiler is equip...

Страница 25: ...E n v i r o n m e n t a l p r o t e c t i o n Emission of NOx natural gas Class Class NOx 6 Emissions of nitrogen oxides mg KWh 50 The pH of the condensate natural gas 5 Max amount of condensate natu...

Страница 26: ...ly H Flue gas temperature limiter RELAY Relay of the pump 5A ALARM Error information connector PWM PWM pump control G1 Protection against heat exchanger overheating 2xF2 5A Fuses in control panel RT T...

Страница 27: ......

Страница 28: ......

Отзывы: