ISU-689:2016/GB 

14 

 

 

 

Protection against possibility of blocking the pump and the three-
way valve (pump and valve are switched on for about 20 seconds, 
at least once a daily). 

CH mode

 

 mode in which the boiler heats the CH system. Detailed 

described in section 2.4.1.

 

DHW mode

 

 mode in which the boiler heats the DWH tank. Detailed 

described in section 2.4.3.  

WINTER mode

 

 the boiler performs the heat demand for both CH 

system and heating of domestic water. Priority is always DHW. In the 
boiler we can turn off the heating of domestic water function by 
pressing 

[C]

 button. In this mode, the boiler will ignore the heat 

demand from the DHW tank. 

SUMMER mode

 

 the boilers performs only heating of domestic 

water, and ignores the heat demand for heating in CH system.  
 
The boiler is factory adapted for operation in CH system only, after 
installing to boiler the domestic hot water tank, the boiler can 
operate in heating the domestic water mode. 

 

 

5.3. Settings  
5.3.1. Change the setting of heating water 

 

Use 

[D]

 or 

[E]

 buttons to 

change the heating water 
temperature of the CH 
system on the outlet from 
boiler. The display will flash 
the set temperature in 
degrees Celsius. The 

selection must be accepted with 

[B] 

button. If the user does not 

accept, after about 10 sec you will leave the function without  saving 
new value.  

 

 

5.3.2. Change the setting of domestic water  

 

Use 

[G]

 or 

[F]

 buttons to 

change the heating water 
temperature of the DHW 
system on the outlet from 
boiler. The display will 
flash the set temperature 
in degrees Celsius. The 

selection must be accepted with 

[B] 

button. If the user does not 

accept, after about 10 sec you will leave the function without  
saving new value.  

 

 

5.3.3. Switching the SUMMER / WINTER mode  

 

Use 

[A]

 button to change 

WINTER mode to 
SUMMER mode. The 
symbol (W2) shown on 
the picture will appear 
on the screen. To revert 
to WINTER mode, use 

[A]

 button again.

 

 

5.3.4. Turn off the heating of domestic water 

 

By using 

[C]

 button, you 

can turn on or turn off 
the heating function. 
Turning off the function 
is signaled by the 
symbol (W5) shown on 
the picture. 

 

 
 
 

5.3.5. Stand-by mode 

 

Use [

A+C]

3sec

 buttons to 

activate this mode The 
symbol (W11) shown on 
the picture will appear 
on the screen. Press 

[B]

 

button to activate the 
boiler.  

5.4. Diagnosis  

 

When the operation of the boiler will be incorrect the display shows 
the symbol "E" and the error number. When user intervention is 
required to remove the blockade of, there will be RESET displayed.  
If the boiler will continue to go into a blockade state an AUTHORISED 
SERVICE COMPANY needs to be called. 
 

Error 
code 

Error description 

Reset 

required 

01 

No flame 

02 

Fake flame 

 signaling of disturbances in the flame 

control circuit 

03 

Activation of temperature limiter on boiler water 
system or activation of heat exchanger temperature 
limiters 

04 

05 

No record of fan speed 

06 

07 

Protection on exhaust outlet (2.2) 

08 

Flame control circuit error 

09 

Error of circuit of gas valve control 

13 

Remote reset error 

15 

Test of NTC sensors failed 

16 

Error of supply water NTC sensor (2.15) 

17 

Error of return water NTC sensor (2.14) 

18 

Damage of supply water NTC sensor (2.15) or return 
water NTC sensor (2.16) 

21 

ADC transducer error 

25 

Matching error 

30 

Closed SUPPLY CH NTC sensor (2.15) 

31 

Open SUPPLY CH NTC sensor (2.15) 

32 

Closed DHW NTC sensor  

33 

Open DHW NTC sensor 

34 

Low supply voltage 

37 

Low pressure of boiler water  

41 

Pressure transducer (2.8) 

 no communication 

43 

Closed RETURN CH NTC sensor (2.14) 

44 

Open RETURN CH NTC sensor (2.14) 

45 

46 

47 

Pressure transducer (2.8) 

 damaged or not connected 

74 

Temperature sensor of solar collector - closed 

75 

Temperature sensor of solar collector - open 

76 

77 

78 

79 

80 

Swapped NTC sensors of supply and return  

81 

NTC sensors error 

see 
description 

90 

Internal error 

 

94 

Internal error 

see descr. 

95 

Error of cascade NTC sensor 

see descr. 

96 

Error of ES outdoor temp. sensor 

see descr. 

97 

Cascade system error 

see descr. 

98 

Error of communication between boilers  

see descr. 

99 

No communication CONSOLE / CONTROLLER

 

see descr. 

Table 5.4.1 

 Error codes

 

 
During displaying of each error code the pump is startup.  
The only exception is an error E37. 

 

Error 01 description 

 

Number of ignition attempts has been 

exhausted and no flame is detected during the safety time in any of 
the attempt. 
The error may also indicate that the boiler water flow is too low - less 
than 20 dm

3

/min - or the water flow sensor is damaged (2.17).  

 

Содержание ECOCONDENS CRYSTAL 100

Страница 1: ...INSTRUCTION MANUAL INSTALLATION OPERATION AND MAINTENANCE Gas fired condensing central heating boilers SYSTEM BOILERS ECOCONDENS CRYSTAL 80 ECOCONDENS CRYSTAL 100...

Страница 2: ...lters are not included in a basic boiler equipment An example of connecting a boiler to these systems is presented on fig 3 5 1 All defects caused by lack of filters on central heating or gas supply w...

Страница 3: ...nnecting the boilers in the cascade system 10 4 BOILER ADJUSTMENT AND PRELIMINARY SETTING 10 4 1 INTRODUCTORY REMARKS 10 4 2 ADJUSTING THE BOILER TO COMBUST ANOTHER TYPE OF GAS 11 BOILER CAN BE ADJUST...

Страница 4: ...esign and technical specifications of the boiler 2 2 1 Main units of the boiler 2 1 Flue gas water heat exchanger 2 2 Temperature limiter of flue gas 2 3 Temperature limiter of air collector 2 4 Ignit...

Страница 5: ...parameter P06 If the heating water temperature exceeds 97 C an additional temperature limiter is activated the burner is turned off until the hot water temperature drops below 81 C The system of conti...

Страница 6: ...he boiler from the SUMMER function CH only to the WINTER function CH and DHW A 3sec The entrance to the TEST mode B The reset the displayed error B 3sec Preview of the parameters C Turns on or off the...

Страница 7: ...This prepared cables connect according to Fig 3 1 3 1 Fig 3 1 3 1 Wire colors L brown N blue PE yellow green If you need to replace the supply wire use a minimum cord of 3 x 0 75 mm2 The boiler supply...

Страница 8: ...ing the back and bottom of the boiler Due to the heavy weight 2 people are required Fig 3 3 1 Mounting dimensions Mounting method on hooks Mounting method with hanger Fig 3 3 2 Mounting method Fig 3 3...

Страница 9: ...n are not used as grounding the electrical installation Connect the outlet of safety valves to the floor drain to avoid flooding the room where the boiler is installed as a result of protection device...

Страница 10: ...a blowing fan 3 The boiler is designed for cooperation with the flue gas air system with a diameter of 100 flue gas and air and in a collective cascade system where the flue gas exhaust from a single...

Страница 11: ...he sum of the lengths of the flue gas air system when the elbow is mounted on the flue gas system or the air supply system to the boiler Table 3 8 3 1 Reduce the length of the installation elbows Exam...

Страница 12: ...iler connection with PC MASTER and SLAVE communication connectors are not located in the control console casing Connectors appropriately described are located in bulk inside the boiler Fig 3 9 1 1 Des...

Страница 13: ...r in tank EP External cascade pump ES Outdoor temperature sensor CS Temperature sensor in supply collector 3W three way valve Boilers cooperating in the cascade system are connected in series by a cab...

Страница 14: ...ctrical installation was made in accordance with applicable regulations the correctness of connections between the boiler and the chimney was checked and confirmed by a qualified chimney service 4 3 B...

Страница 15: ...mming mode is switched off 4 5 1 Preview of parameters value You can review the parameter values without the need of change To do this use the B 3sec button After starting LOCAL INSTALLATION mode the...

Страница 16: ...ow pressure fill the installation with a filling valve mounted on the installation Start the boiler in the TEST service mode the boiler will start the circulation pump and start the ignition Due to la...

Страница 17: ...de The symbol W11 shown on the picture will appear on the screen Press B button to activate the boiler 5 4 Diagnosis When the operation of the boiler will be incorrect the display shows the symbol E a...

Страница 18: ...ctrical connections Error 96 description When the P14 parameter is set on a value other than zero the controller does not detect the presence of the sensor closed open Please check the sensor ES conne...

Страница 19: ...ont cover 1 Loosen the screws K1 2 Pull the cover behind its lower edge to release from the latches 3 Move the cover up Dismantling the side cover 4 Unscrew the screws K2 5 Move the cover up Fig 6 1 1...

Страница 20: ...gas 6 1 3 Thermal protection of the heat exchanger The heat exchanger is equipped with thermal protection BW1 and BW2 protecting against improper assembly of the exchanger If the exchanger is mounted...

Страница 21: ...ceeding the limits of temperature protection against exceeding the pressure limits check whether vents are present with correct dimensions and operating according to the installed device In this regar...

Страница 22: ...ELV Contact Thermal fuse item 2 2 Supply voltage from the controller SELV Activation temperature 115 C Return NTC sensor item 2 14 Supply item 2 15 Supply voltage from the controller SELV 12K 25 C 363...

Страница 23: ...e the power level with D and E buttons by 1 use F button to set the min power or G button to set the max power The PWM signal for the cascade pump is selected according to the operation algorithm of b...

Страница 24: ...g 7 2 3 2 1 Diagram of connecting boilers for DHW needs in divided configuration with one three way valve Diagram of connecting 4 boilers two of which are intended for heating DHW Each boiler is equip...

Страница 25: ...E n v i r o n m e n t a l p r o t e c t i o n Emission of NOx natural gas Class Class NOx 6 Emissions of nitrogen oxides mg KWh 50 The pH of the condensate natural gas 5 Max amount of condensate natu...

Страница 26: ...ly H Flue gas temperature limiter RELAY Relay of the pump 5A ALARM Error information connector PWM PWM pump control G1 Protection against heat exchanger overheating 2xF2 5A Fuses in control panel RT T...

Страница 27: ......

Страница 28: ......

Отзывы: