Templari KITA L Cold Скачать руководство пользователя страница 56

56

www.templari.com

generated by PID of the reached water that 

activate the integration. 

• 

ON-Propor.:  it  represents  the  distance  from 

the  set,  in  percentage,  over  that  activate 

auxiliary integration.

For example: the percentage of the proportional band 

Hc06  as  per  factory  default  is  set  at  10.  The  60%  of 

10 is 6°C . It represents the proportional enabling the 

integration  of  auxliary  heating.  Higher  this  value  is  it 

means the machine is far from set. If this value was low 

and the previous higher, the boiler could start even if it 

isn’t necessary, for example if the machine stayed near 

the set (low proportional) for long time (high integral 

pushing),  no  reaching  it.  In  qthis  case  the  machine 

would be  a little subsized but it could heat the water 

in  any  case,  without  a  necessary  intervention  of  the 

boiler.

The combination of the two previous parameters, then, 

identifies when the machine is really in crisis and needs 

integration. Happening both conditions the integration 

is active.

• 

OFF-Propor.:  it’s  the  percentage  of  the 

proportional band Hc06, that as defaut is set 

at 10, under that the integration shut down.

• 

OFF-Diff.:  Degrees  the  integration  has  to 

produce  more  on  Setpoint  set  on  the  heat 

pump.

Mask Gfc03: 

integration activation in case of need 

(heat pump in “crisis”).

• 

Setpoint act.:   external temperature value 

under that the boiler is enabled to start if the 

machine is considered in crisis ( parameters in 

Gfc02)

• 

Differential: 

deltaT  positive,  that  is 

the  integration  is  enabled  until  the  external 

temperature reaches a temperature equal to 

SDifferential.

• 

Boiler  activation  delay:  verify  previous 

conditions, the boiler is activated if they stay 

for the time set.

Mask Gfc04: 

integration  activated  according  to 

the outside temperature.

In this case the integration started when the outside air 

temperature falls below the set value. Once activated 

the auxiliary source, it works in conjunction with a heat 

pump, unless it is not been set her to turn off.

Integration remains active until it reaches the set water 

setpoint, although the air temperature rises above the 

value set.

• 

Setpoint act.:  external  temperature  value 

that  enable  the  heating  control,  heating 

independent from other factors

• 

Differential:  deltaT  positive,  that  is  the 

integration  is  enabled  until  the  external 

temperature  reaches  a  value  equal  to 

SDifferential.

• 

Turn off compressors: it allows to turn off the 

heat pump under the defined temperature in 

Setpoint  act.  :  the  integrated  system  totally 

replaces the heat pump.

Mask Gfc05: 

integration  to  HDW  based  on  the 

external temperature.

• 

Diff.on HWD: value of external temperature 

over that the integration HWD system turns 

on,  it  stays  on  until  the  reaching  of  the  set 

value in Diff.off HWD.

 

Gc18: 

inverter status.

 

Gc22: 

inverter status.

 

Gc23: 

inverter status.

 

Gc24: 

digital inputs

 

Gc25: 

digital inputs

 

Gc26: 

digital inputs

 

Gc27: 

digital outputs

 

Gc29: 

digital outputs

 

Gc32: 

fan status

D. WORKED HOURS

This menu allows to monitor the working time

 

Mask Gd01: In this mask operation total hours of the heat 

pump are displayed.

 

Mask Gd02: In  this  mask  it  is  displayed  the  number  of 

defrost made by the machine during the operation in heat 

pump.

E . CONFIGURATION BMS

This menu allows to set the communication protocol of the port 

“BMS“  of  the  electronic  control.  This  menu  is  protected  by  a 

password. Only the authorized staff can enter it.

F . ASSISTANCE PARAMETER

This menu is protected by a password. Only the athorized staff 

can enter it.

a. Counter settings

b. Sensors calibration

c. Thermoregulation

d. default user / change password

 

a. COUNTER SETTINGS

 

Reserved to the authorized staff

 

b. SENSORS CALIBRATION

Gfb01:  sensor calibration B1 and B2

Gfb02:  sensor calibration B3 and B4

Gfb03:  sensor calibration B5 and B6

Gfb04:  sensor calibration B7 and B8

The  position  of  B8  sensor  may  affect  the  operation 

of your heat pump, therefore only for sensor B8 it is 

possible to choose:

• 

on board: the sensor on board is set

• 

remote: remote sensor is set

Gfb05:  sensor calibration B9 and B10

Gfb06:  sensor calibration B11 and B12

Gfb07:  offset S1, S2

Gfb08:  offset S3, S4

Gfb09:  enable and set sensor calibration B2 and B3

 

c. THERMOREGULATION

Mask Gfc01: 

it sets the presence of a puffer and 

the auxiliary integration.

• 

puffer presence: (yes - no)

• 

system integration: (none - boiler)

• 

domestic integration: (none - boiler)

 

Mask Gfc02: 

Configuration  request  integration 

parameters.

It allows to define the thresholds of auxiliary integration 

intervention  (boiler  /  electric  heater)  to  the  heating 

based on the request (the ability to reach the set point 

in a given time interval) and on its proportional part.

It is defined the working condition to which the heat 

pump requires help from the integration, namely the 

condition of “crisis”.

• 

ON-Request:  it  represents  the  request 

Содержание KITA L Cold

Страница 1: ...AIR WATER version Installation and maintenance manual T H E H E A T P U M P...

Страница 2: ...e of external device of the heat pump KITA S Si Templari 13 4 4 Components scheme of external device of the heat pump LINE KITA Mi Templari 14 4 5 Components scheme of external device of the heat pump...

Страница 3: ...pLAN net multi KITA 35 11 Electronic board 36 11 1 Digital outputs 36 11 2 Digital inputs 36 11 3 Analog outputs 36 11 4 Analog inputs 36 11 5 Wiring diagram KITA S S Plus mono phase 37 11 6 Wiring di...

Страница 4: ...5 3 Menu overview 51 15 4 Terminal buttons 52 15 5 Display of the terminal 52 15 6 Main menu 53 15 7 ON OFF menu 53 15 8 SETPOINT menu 53 15 9 Clock timetable menu 54 15 10 Input Output menu 55 15 11...

Страница 5: ......

Страница 6: ...lari you can find all the information in relation to current regulations of labeling in particular you can find Power to the machine in tension e frequency Thermal power in heating and cooling schemes...

Страница 7: ...ges or transformations to the device 2 3 Rules and law provided This heat pump is destined according to the article 1 chapter 2 k of Directive CE 2006 42 CE Machines Directive to the use in domestic a...

Страница 8: ...ase DN20 1698 28 3 Mi Cold Mi Cold 3Phase DN20 1698 28 3 Mi Plus Mi Plus 3Phase DN20 1698 28 3 Mi Plus Cold Mi Plus Cold 3Phase DN20 1698 28 3 L33 DN20 1698 28 3 L42 DN25 2520 42 L66 DN25 2520 42 L Co...

Страница 9: ...d to the manufacturer a heating resistor for the condensate drain una a three way valve for the combined system and domestic hot water management mesh filter switching rel operating with boiler integr...

Страница 10: ...5 125 180 Voltage supply frequency 1 x 230 V 50 Hz Energy efficiency index EEI 0 23 Maximum power 3 180 W Maximum current absorption 0 06 1 4 A Minimum pressure input 0 5 bar Producible water temperat...

Страница 11: ...agement module DHW domestic hot water composed by rel temperature sensors and 3 way valves Thanks to that the pump can manage the DHW both in summer and in winter as a priority Heating mode 1 Evaporat...

Страница 12: ...Hp 45 bar Lp 30 bar Kompressortyp Compressor type Tipo compressore Inj Hinweis die W rmeleistung wurde in Standardkonditionen gepr ft mit trockene nasse Testspitze 7 6 C Wassertemperatur in out 30 35...

Страница 13: ...of external device of the heat pump KITA S Si Templari 1 7 12 6 5 11 8 3 16 2 15 9 4 10 13 14 1 RELEASE VALVES 2 EVAPORATOR 3 COMPRESSOR 4 FILTER 5 FLOWMETER 6 LIQUID INDICATOR 7 INVERTER 8 LIQUID REC...

Страница 14: ...ALVES 2 EVAPORATOR 3 COMPRESSOR 4 FILTER 5 FLOWMETER 6 LIQUID INDICATOR 7 INVERTER 8 LIQUID RECEIVER 9 ELECTRIC BOARD 10 PLATE HEAT EXCHANGER 11 CIRCULATION PUMP 12 ECONOMIZER 13 CHECK VALVES 14 ELECT...

Страница 15: ...ALVES 2 EVAPORATOR 3 COMPRESSOR 4 FILTER 5 FLOWMETER 6 LIQUID INDICATOR 7 INVERTER 8 LIQUID RECEIVER 9 ELECTRIC BOARD 10 PLATE HEAT EXCHANGER 11 CIRCULATION PUMP 12 ECONOMIZER 13 CHECK VALVES 14 ELECT...

Страница 16: ...VES 2 EVAPORATOR 3 COMPRESSOR 4 FILTER 5 FLOWMETER 6 LIQUID INDICATOR 7 INVERTER 8 LIQUID RECEIVER 9 ELECTRIC BOARD 10 PLATE HEAT EXCHANGER 11 CIRCULATION PUMP 12 ECONOMIZER 13 CHECK VALVES 14 ELECTRO...

Страница 17: ...for example Consider the weight of the product shown in the technical data Inthetransportofheavyloads complywiththeinstructions and the provisions in force 6 Assembly and installation 6 1 Optional com...

Страница 18: ...257 325 1133 325 1791 641 88 289 292 1791 61 136 137 C A B D 1292 35 1257 678 13 C Bottom view A B C D WITH LEGS CON GAMBE WITH BRACKETS CON STAFFE 1513 256 1257 325 1133 325 1791 641 88 289 292 1791...

Страница 19: ...A S 400 KITA M 500 KITA L D 3000 E 1000 Respect the minimum distances mentioned above to ensure a sufficient air flow and facilitate maintenance works Verify there is asufficient space for the install...

Страница 20: ...ual and service manuals 2 Assembly the product on steel beams blocks of concrete or with the help of a wall holder accessory 3 Verify that under the product water doesn t accumulate non si accumuli 4...

Страница 21: ...e amortized feet increase the height of the product facilitating the flow of condensate and reducing vibrations 6 8 Probe installation All probe used for the operation of the plant must be installed p...

Страница 22: ...of a Y filter is necessary WARNINGS Install hydraulic system side a safety valve 7 3 Installation of hydraulic part Thorough washing of the system with clean water filling and emptying it many times...

Страница 23: ...valve B2 B3 B4 B7 Buffer tank temperature probe DHW temperature probe Outlet temperature probe Inlet temperature probe SIGNAL CABLES OUT IN DHW DW WARNINGS The buffer tank must comply with a minimum...

Страница 24: ...ta used KITA S 200 Litres KITA M 300 Litres KITA L 500 Litres KITA Li Plus 800 Litres GA MA RD 3W VE FY UE VB Anti vibration joint Manometer Drin tap 3 way valve Expansion vessel Y filter External uni...

Страница 25: ...pump Kita used KITA S 200 Litres KITA M 300 Litres KITA L 500 Litres KITA Li Plus 800 Litres GA MA RD 3W VE FY UE VB Anti vibration joint Manometer Drin tap 3 way valve Expansion vessel Y filter Exte...

Страница 26: ...A S 200 Litres KITA M 300 Litres KITA L 500 Litres KITA Li Plus 800 Litres GA MA RD 3W VE FY UE VB Anti vibration joint Manometer Drin tap 3 way valve Expansion vessel Y filter External unit Bypass va...

Страница 27: ...ate authorized service center 8 2 Cleaning of the condensate drain Make sure that the condensate drainpipe is in the correct position and no clogged to allow the correct drain of the condensate deposi...

Страница 28: ...Plus 11 00 1 59 6 90 18 20A 30mA 5x4 KITA Mi Plus Cold 16 70 1 89 8 84 18 20A 30mA 5x4 KITA L33 400V 3ph 23 10 2 37 9 75 18 20A 30mA 5x4 KITA L42 28 80 2 69 10 71 24 32A 30mA 5x6 KITA L66 18 30 1 46...

Страница 29: ...heater security DI8 Remote on off DI9 Switch modbus controller DI10 Flow switch Y1 Y2 Internal fan KITA Air Y3 PWM circulator Y4 External fan KITA Air NO1 Integration NO2 Defrost NO3 Air air or air w...

Страница 30: ...ower terminal 2 Auxiliary fuses 4 A 3 Power Phase Neutral and Ground for internal split 4 Sensor terminal block the symbol indicates GND L L L N L N 1 2 4 3 1 3 5 7 9 11 2 4 6 8 10 12 B3 Y3 B7 B2 B4 B...

Страница 31: ...rsion S L 12 K3 Rel K3 INTEGRATION MANAGEMENT A1 Relay coil to NO6 uPC contact A2 Relay coil to Neutral external unit 14 Normally open contact NO 12 Normally closed contact NC 11 Common contact C 3 wa...

Страница 32: ...11 2 4 6 8 10 12 B3 Y3 B7 B2 B4 B5 1 3 5 7 9 11 2 4 6 8 10 12 B2 Gnd B4 GND B5 VDC B3 GND Y3 GND B7 GND L L L N L N 1 2 4 3 1 3 5 7 9 11 2 4 6 8 10 12 B3 Y3 B7 B2 B4 B5 1 3 5 7 9 11 2 4 6 8 10 12 B2 G...

Страница 33: ...C Rel K3 INTEGRATION MANAGEMENT A1 Relay coil to NO6 uPC contact A2 Relay coil to Neutral external unit 14 Normally open contact NO 12 Normally closed contact NC 11 Common contact C Connection 3 way v...

Страница 34: ...ites and replaces the PA settings of the heat pump And therefore if the panel enables the PA function it won t be possible to disable it from the PGD1 The ID10 is the contact used to manage the PA fun...

Страница 35: ...o con gli altri disposi vi Corrisponde sempre alla COM3 Porta di comunicazione per il monitoraggio Nel caso del pannello 4 la COM1 Nel caso del pannello 7 la COM2 Nel caso del pannello 10 la COM2 3 Ca...

Страница 36: ...hooks Din 35 6 1 2 3 4 5 9 7 8 17 10 11 12 13 14 15 16 18 18 18 11 1 Digital outputs NO1 Integration NO2 Defrost NO3 Air air or air water indicator NO4 Circulation pump NO5 Condensate drain heating N...

Страница 37: ...ALLY CLOSED CONTACT NORMALLY OPEN CONTACT CIRCUIT BREAKER WITH THERMAL SAFETY SWITCH Flowmeter 4 20 mA CONTROL BOARD CIRCULATOR COMPRESSOR LOW PRESSURE TRANSDUCER Drain heater Auxiliary heater K3 rela...

Страница 38: ...ALLY OPEN CONTACT CIRCUIT BREAKER WITH THERMAL SAFETY SWITCH Flowmeter 4 20 mA CONTROL BOARD LOW PRESSURE TRANSDUCER REMOTE CONTROL PANEL Drain heater Auxiliary heater K3 relay 3 way valve K1 relay DH...

Страница 39: ...ATURE PROBE 2x BIPOLAR CABLE f p o set up by the customer installer REMOTE CONTROL PANEL Flowmeter 4 20 mA brown black LOW PRESSURE TRANSDUCER CONTROL BOARD LOW PRESSURE TRANSDUCER Drain heater Auxili...

Страница 40: ...POLAR CABLE f p o set up by the customer installer PROBES TERMINAL BOARD REMOTE CONTROL PANEL Flowmeter 4 20 mA LOW PRESSURE TRANSDUCER LOW PRESSURE TRANSDUCER CONTROL BOARD Drain heater Auxiliary hea...

Страница 41: ...eater K3 relay 3 way valve K1 relay DHW integra on 4 way valve Compressor heater Injec on valve Expansion valve CIRCULATOR REMOTE CONTROL PANEL brown black PROBES TERMINAL BOARD PUFFER TANK TEMPERATUR...

Страница 42: ...k Black Black Black Black Black B9 White B8 White White D13 D12 White B12 White White 16 15 17 18 8 7 2 1 4 3 5 6 11 10 3 4 way valve and carter resistance wiring PE Yellow Green N Blue NO4 3 2 1 N Lo...

Страница 43: ...rom the necessary time to bring to temperature the oil contained in the compressor then depending on the starting temperature 12 2 Testing and startup Access to men Assistance PRG G Assistance g Manua...

Страница 44: ...lv 3V ACS set up in manual MAN if the 3 way valve for domestic hot water management is installed to test the proper operation Restore all settings from manual MAN to automatic AUT Verify during the do...

Страница 45: ...t cable of the K Touch Panel to the shield of the Modbus data network Connect the ground terminal of the power supply to the shield of the Modbus data network The shiels of the various cable sections...

Страница 46: ...o the PC make sure you DO NOT have the terminal ID09 connected to GND as shown in Figure 5 With this configuration you can simultaneously use the PGD1 control panel and the K Touch Panel If the K touc...

Страница 47: ...20V Morse o Terra quadro macchina F N 24V G G0 A B G COM3 COM3 BMS G RX TX RX TX GND 3 2 4 6 7 5b 5a CONNESSIONE PLan CONNESSIONE BMS PLan o BMS BMS connection Heat pump terminal board ground connecti...

Страница 48: ...amic 2 Power supply 4 Green yellow shield ground connection 7 HCC touch panel connection 6 Shield compact lever connector 3 5a PC PLan connection 5b PC BMS connection Watch the video for the K Touch c...

Страница 49: ...D Vdc Vdc GND 5 Vref GND Y1 Y2 Y3 Y4 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DIC1 B8 B9 B10 B11 B12 GND DI8 DI9 DI10 DIC2 PC ENDWIDERSTAND 120 BMS G MODBUS TERMINATOR RESISTOR 120 MODBUS C4 NO8 NO9 NO10 NO11 NO12...

Страница 50: ...set the parameters of operation preference summer winter setpoint Some example figures to use the command and the machine will be reported below 15 1 Fixing of the panel The panel can be fixed direct...

Страница 51: ...ors D06 Analog sensors D07 Fan speed Circulator speed D08 Cooling circuit status D09 Work regime D10 Work pressures D11 Work pressures D14 Drain Gas Control D15 EED set up D19 Inverter Engine paramete...

Страница 52: ...ction for cold external temperatures and too low temperature of the system the compressor is active until reaching a system temperature of 40 C BOILER AUTOMATIC MANAGEMENT IF REQUIRED The start up of...

Страница 53: ...educed We underline that setting this function the efficiency of the machine too is progressively reduced Mask B06 Only in AIR version Automatic Mode Change to pass from cooling mode to heating mode d...

Страница 54: ...C04 It permits to enable a pre set operation for 6 different days maximum Press and to enable disable the special day s Confirm with to enter the choice of the starting day of the particular period U...

Страница 55: ...nformation about pressures differece between pressure of high and low relation between pressure of high and low alarm count dow delta P low Mask D14 shown the temperature of compressor drain and relev...

Страница 56: ...external temperature reaches a value equal to Setpoint Differential Turn off compressors it allows to turn off the heat pump under the defined temperature in Setpoint act the integrated system totall...

Страница 57: ...the function antifreeze winter Mask Gfc17 Setpoint on the system temperature for the activation of the antifreeze that activates the circulator Set antifreeze pump primary circuit temperature set that...

Страница 58: ...maximum speed allowed can increase Mask Gfc55 it enables the control of the circulator in If the previous parameter is active also the following parameters become editable Unit ON flow water temperat...

Страница 59: ...t enables the manual management Manual valve position if the manual management is active it shows the valve opening in steps Mask Gg05 manual or automatic management of the heat pump CH HP Request it...

Страница 60: ...ALA12 Ssensor B12 broken or disconnected Automatic 60 sec yes Stop the machine ALB01 Position ID3 high pressure Manual Immediate yes Stop the machine ALB02 High pressure compressor 1 from transducer...

Страница 61: ...Gfa01 Just reporting ALT08 Threshold reached worked hors internal battery fan Manual Immediate Settable Gfa01 Just reporting ALU01 Antifreeze geothermal exchanger Manual par Gfc28 Immediate Yes Stop...

Страница 62: ...be incoherent with the working field of the unit for example operation DHW with external temperature too high Please refer to the section operative zone allowed of this guide ALC04 The compressor can...

Страница 63: ...e between B7 and B3 probes in the case of DHW production is excessive Power limit temperature It is activated if the heat pump is producing water less than 6 or more than 58 The compressor is moves to...

Страница 64: ...r Cold 3Phase Air Cold Booster 3Phase Air Plus 3Phase Designa on Heat Pump Type Produkt W rmepumpe Typ Dire ve EC Direc ves EC Anforderungen Dire va 2004 108 EC e 2009 142 EC Direc ve 2004 108 EC e 20...

Страница 65: ...65 www templari com...

Страница 66: ...66 www templari com...

Страница 67: ...67 www templari com...

Страница 68: ...AIR WATER version T H E H E A T P U M P vers 11 06 2021 I via Pitagora 20A 35030 Rubano PD Italia Tel 39 049 8597400 info templari com www templari com...

Отзывы: