Screen Gg05 set up CH/HP in manual “MAN” and set up the 

rps (60). Now turn on the heat pump (Mode ON) and wait for 

some minutes until the compressor icon appears in the lower 

left.

 

WARNINGS! 

      

 

During manual operation, probe B3 is ignored. If the functions 

setted in manual (MAN) during the running are not set back in 

automatic  (AUTO)  at  the  end,  the  heat  pump  will  continue  to 

work until it causes a high pressure alarm.

Verify the proper operation:

• 

Access to menu “D. inputs/outputs” to control the different 

temperatures from sensors

• 

Screen  D01:  B1  it  shows  il  valore  of  liquid  sub-cooling 

in  the  heat  pump,  it  has  to  stay  in  a  range  between  3 

and  4,  once  achieved  35°C  of  water  (see  B7).  If  the  hp  is 

started  up  during  the  hot  season,  for  the  check  of  sub-

cooling  set  up  the  fan  speeds  (Menu  G.  Assistance  --˃ 

g.  Manual  management  --˃  G.  Assistance  --˃  g.  Manual 

management  --˃  SERVICE  PASSWORD  --˃  Screen  Gg02:  set 

up “Speed Fan” in manual MAN and “Power required” at 5%. 

After checking the value of the B1 probe, reset the values as 

they were previously.

• 

Screen  D02  and  D04:  control  the  sensor  temperature  B7 

(water flow) and compare it with the sensor temperature B4 

to see se if the circulator works with a correct deltaT (less than 

8).

• 

Screen D06 and D04: control the B11 (condensation) with B7 

(water flow): the difference between them has to be included 

between 1 and 2 grades for a proper operation. If the deltaT is 

more verify the presence of possible narrowing in the circuit.

• 

Screen D08: verify that the value SH (overheating) is  included 

between 4 and 5

• 

Screen D15: verify, once set these conditions (B7 at 35°C and 

compressor at 60 rps and deltaT water <8 and SH between 4 

and 5 and sub-cooling between 3 and 4) the drain overheating 

has to be about 20. During the normal operation, with free 

compressor, this value can reach 45K.

• 

Screen D16 (just available in the versions Kita-L, L42 and L66): 

control the proper operation of the injection valve, considering 

that over 12°C external the valve is off.

• 

Menu G. Assistance --˃ g. Manual management --˃ SERVICE 

PASSWORD  --˃  Screen  Gg06:  activate  a  defrosting  forced 

cycle, setting up “Start the defrost cycle” in YES (once ended 

the cycle the function automatically come back to AUT).

• 

Menu G. Assistance --˃ g. Manual management --˃ SERVICE 

PASSWORD  --˃  Screen  Gg01:  “N09  Valv.3V  ACS”,  set  up  in 

manual  MAN,  if  the  3-way  valve  for  domestic  hot  water 

management is installed, to test the proper operation.

• 

Restore all settings from manual MAN to automatic AUT.

• 

Verify during the domestic production, that the HP performs 

with priority  respect to heating/cooling, that the difference 

of  temperature  between  the  sensors  B7(water  flow)  and 

B3(domestic sensor that has to be placed in the upper part of 

the tank) mustsn’t exceed 3 degrees.

• 

Verify that the working tensions and network frequencies  are 

in the following ranges:

230/1/50 -> valori ± 6%

400/3/50 -> valori ± 6%

 

NOTE!   

 

 

 

           

Some possible malfunctions can be intercepted at the start.

To extend the life of the heating pump it is a good habit to check 

the  value  of  the  sensor  B11  (condensation)  and  subtract  this 

value from B7 (water output). The delta T resulting, in case of 

proper operation, has to be between 1,5 e 2, depending on  the 

thermal  load of  the heating pump and the water flow system 

side.

If the delta T is more than 5 then it is really probable that there is 

one of the following problems:

• 

air in the cooling circuit;

• 

air in the hydraulic circuit;

• 

low flow water side;

• 

faulty electronic valve (it works to close wrongly increasing 

the condensation value).

A high delta T could be the responsible of possible high pressure 

alarms; in particular during the production of high temperature 

water.

 

NOTE!   

 

 

 

           

Other  problem  easily  detectable  is  the  steady  opening  of  the 

electronic valve at 100%

possible reasons and solutions:

• 

lack of refrigerant gas in the cooling system; for this reason 

the electronic valve, to compensate the lack of gas, is open 

over the normal values.

• 

heat  pump  used  in  incorrect  way.  Example:  installation 

of  a  heat  pump  undersized  respect  to  the  building  that 

requires  more  power  at  rating  levels.  In  this  case  for 

example the compressor works at 100% even with positive 

air temperatures; this fact requires an higher quantity   of 

refrigerant than the project data. The heat pump Kita has 

to be sized to work at full speed just at minimum external 

temperatures. The electronic valves are optimized to work 

in  the  medium  range  of  operation  and  for  this  reason 

oversized valves aren’t installed, they would work too close 

causing instability in the system. Possible solutions: 

control the proper operation of the valve

control that in the HP Kita there is the right quantity of gas

replace the heat pump if wrongly undersized resoect 

to the heating requirements of the building.

Содержание KITA L Cold

Страница 1: ...AIR WATER version Installation and maintenance manual T H E H E A T P U M P...

Страница 2: ...e of external device of the heat pump KITA S Si Templari 13 4 4 Components scheme of external device of the heat pump LINE KITA Mi Templari 14 4 5 Components scheme of external device of the heat pump...

Страница 3: ...pLAN net multi KITA 35 11 Electronic board 36 11 1 Digital outputs 36 11 2 Digital inputs 36 11 3 Analog outputs 36 11 4 Analog inputs 36 11 5 Wiring diagram KITA S S Plus mono phase 37 11 6 Wiring di...

Страница 4: ...5 3 Menu overview 51 15 4 Terminal buttons 52 15 5 Display of the terminal 52 15 6 Main menu 53 15 7 ON OFF menu 53 15 8 SETPOINT menu 53 15 9 Clock timetable menu 54 15 10 Input Output menu 55 15 11...

Страница 5: ......

Страница 6: ...lari you can find all the information in relation to current regulations of labeling in particular you can find Power to the machine in tension e frequency Thermal power in heating and cooling schemes...

Страница 7: ...ges or transformations to the device 2 3 Rules and law provided This heat pump is destined according to the article 1 chapter 2 k of Directive CE 2006 42 CE Machines Directive to the use in domestic a...

Страница 8: ...ase DN20 1698 28 3 Mi Cold Mi Cold 3Phase DN20 1698 28 3 Mi Plus Mi Plus 3Phase DN20 1698 28 3 Mi Plus Cold Mi Plus Cold 3Phase DN20 1698 28 3 L33 DN20 1698 28 3 L42 DN25 2520 42 L66 DN25 2520 42 L Co...

Страница 9: ...d to the manufacturer a heating resistor for the condensate drain una a three way valve for the combined system and domestic hot water management mesh filter switching rel operating with boiler integr...

Страница 10: ...5 125 180 Voltage supply frequency 1 x 230 V 50 Hz Energy efficiency index EEI 0 23 Maximum power 3 180 W Maximum current absorption 0 06 1 4 A Minimum pressure input 0 5 bar Producible water temperat...

Страница 11: ...agement module DHW domestic hot water composed by rel temperature sensors and 3 way valves Thanks to that the pump can manage the DHW both in summer and in winter as a priority Heating mode 1 Evaporat...

Страница 12: ...Hp 45 bar Lp 30 bar Kompressortyp Compressor type Tipo compressore Inj Hinweis die W rmeleistung wurde in Standardkonditionen gepr ft mit trockene nasse Testspitze 7 6 C Wassertemperatur in out 30 35...

Страница 13: ...of external device of the heat pump KITA S Si Templari 1 7 12 6 5 11 8 3 16 2 15 9 4 10 13 14 1 RELEASE VALVES 2 EVAPORATOR 3 COMPRESSOR 4 FILTER 5 FLOWMETER 6 LIQUID INDICATOR 7 INVERTER 8 LIQUID REC...

Страница 14: ...ALVES 2 EVAPORATOR 3 COMPRESSOR 4 FILTER 5 FLOWMETER 6 LIQUID INDICATOR 7 INVERTER 8 LIQUID RECEIVER 9 ELECTRIC BOARD 10 PLATE HEAT EXCHANGER 11 CIRCULATION PUMP 12 ECONOMIZER 13 CHECK VALVES 14 ELECT...

Страница 15: ...ALVES 2 EVAPORATOR 3 COMPRESSOR 4 FILTER 5 FLOWMETER 6 LIQUID INDICATOR 7 INVERTER 8 LIQUID RECEIVER 9 ELECTRIC BOARD 10 PLATE HEAT EXCHANGER 11 CIRCULATION PUMP 12 ECONOMIZER 13 CHECK VALVES 14 ELECT...

Страница 16: ...VES 2 EVAPORATOR 3 COMPRESSOR 4 FILTER 5 FLOWMETER 6 LIQUID INDICATOR 7 INVERTER 8 LIQUID RECEIVER 9 ELECTRIC BOARD 10 PLATE HEAT EXCHANGER 11 CIRCULATION PUMP 12 ECONOMIZER 13 CHECK VALVES 14 ELECTRO...

Страница 17: ...for example Consider the weight of the product shown in the technical data Inthetransportofheavyloads complywiththeinstructions and the provisions in force 6 Assembly and installation 6 1 Optional com...

Страница 18: ...257 325 1133 325 1791 641 88 289 292 1791 61 136 137 C A B D 1292 35 1257 678 13 C Bottom view A B C D WITH LEGS CON GAMBE WITH BRACKETS CON STAFFE 1513 256 1257 325 1133 325 1791 641 88 289 292 1791...

Страница 19: ...A S 400 KITA M 500 KITA L D 3000 E 1000 Respect the minimum distances mentioned above to ensure a sufficient air flow and facilitate maintenance works Verify there is asufficient space for the install...

Страница 20: ...ual and service manuals 2 Assembly the product on steel beams blocks of concrete or with the help of a wall holder accessory 3 Verify that under the product water doesn t accumulate non si accumuli 4...

Страница 21: ...e amortized feet increase the height of the product facilitating the flow of condensate and reducing vibrations 6 8 Probe installation All probe used for the operation of the plant must be installed p...

Страница 22: ...of a Y filter is necessary WARNINGS Install hydraulic system side a safety valve 7 3 Installation of hydraulic part Thorough washing of the system with clean water filling and emptying it many times...

Страница 23: ...valve B2 B3 B4 B7 Buffer tank temperature probe DHW temperature probe Outlet temperature probe Inlet temperature probe SIGNAL CABLES OUT IN DHW DW WARNINGS The buffer tank must comply with a minimum...

Страница 24: ...ta used KITA S 200 Litres KITA M 300 Litres KITA L 500 Litres KITA Li Plus 800 Litres GA MA RD 3W VE FY UE VB Anti vibration joint Manometer Drin tap 3 way valve Expansion vessel Y filter External uni...

Страница 25: ...pump Kita used KITA S 200 Litres KITA M 300 Litres KITA L 500 Litres KITA Li Plus 800 Litres GA MA RD 3W VE FY UE VB Anti vibration joint Manometer Drin tap 3 way valve Expansion vessel Y filter Exte...

Страница 26: ...A S 200 Litres KITA M 300 Litres KITA L 500 Litres KITA Li Plus 800 Litres GA MA RD 3W VE FY UE VB Anti vibration joint Manometer Drin tap 3 way valve Expansion vessel Y filter External unit Bypass va...

Страница 27: ...ate authorized service center 8 2 Cleaning of the condensate drain Make sure that the condensate drainpipe is in the correct position and no clogged to allow the correct drain of the condensate deposi...

Страница 28: ...Plus 11 00 1 59 6 90 18 20A 30mA 5x4 KITA Mi Plus Cold 16 70 1 89 8 84 18 20A 30mA 5x4 KITA L33 400V 3ph 23 10 2 37 9 75 18 20A 30mA 5x4 KITA L42 28 80 2 69 10 71 24 32A 30mA 5x6 KITA L66 18 30 1 46...

Страница 29: ...heater security DI8 Remote on off DI9 Switch modbus controller DI10 Flow switch Y1 Y2 Internal fan KITA Air Y3 PWM circulator Y4 External fan KITA Air NO1 Integration NO2 Defrost NO3 Air air or air w...

Страница 30: ...ower terminal 2 Auxiliary fuses 4 A 3 Power Phase Neutral and Ground for internal split 4 Sensor terminal block the symbol indicates GND L L L N L N 1 2 4 3 1 3 5 7 9 11 2 4 6 8 10 12 B3 Y3 B7 B2 B4 B...

Страница 31: ...rsion S L 12 K3 Rel K3 INTEGRATION MANAGEMENT A1 Relay coil to NO6 uPC contact A2 Relay coil to Neutral external unit 14 Normally open contact NO 12 Normally closed contact NC 11 Common contact C 3 wa...

Страница 32: ...11 2 4 6 8 10 12 B3 Y3 B7 B2 B4 B5 1 3 5 7 9 11 2 4 6 8 10 12 B2 Gnd B4 GND B5 VDC B3 GND Y3 GND B7 GND L L L N L N 1 2 4 3 1 3 5 7 9 11 2 4 6 8 10 12 B3 Y3 B7 B2 B4 B5 1 3 5 7 9 11 2 4 6 8 10 12 B2 G...

Страница 33: ...C Rel K3 INTEGRATION MANAGEMENT A1 Relay coil to NO6 uPC contact A2 Relay coil to Neutral external unit 14 Normally open contact NO 12 Normally closed contact NC 11 Common contact C Connection 3 way v...

Страница 34: ...ites and replaces the PA settings of the heat pump And therefore if the panel enables the PA function it won t be possible to disable it from the PGD1 The ID10 is the contact used to manage the PA fun...

Страница 35: ...o con gli altri disposi vi Corrisponde sempre alla COM3 Porta di comunicazione per il monitoraggio Nel caso del pannello 4 la COM1 Nel caso del pannello 7 la COM2 Nel caso del pannello 10 la COM2 3 Ca...

Страница 36: ...hooks Din 35 6 1 2 3 4 5 9 7 8 17 10 11 12 13 14 15 16 18 18 18 11 1 Digital outputs NO1 Integration NO2 Defrost NO3 Air air or air water indicator NO4 Circulation pump NO5 Condensate drain heating N...

Страница 37: ...ALLY CLOSED CONTACT NORMALLY OPEN CONTACT CIRCUIT BREAKER WITH THERMAL SAFETY SWITCH Flowmeter 4 20 mA CONTROL BOARD CIRCULATOR COMPRESSOR LOW PRESSURE TRANSDUCER Drain heater Auxiliary heater K3 rela...

Страница 38: ...ALLY OPEN CONTACT CIRCUIT BREAKER WITH THERMAL SAFETY SWITCH Flowmeter 4 20 mA CONTROL BOARD LOW PRESSURE TRANSDUCER REMOTE CONTROL PANEL Drain heater Auxiliary heater K3 relay 3 way valve K1 relay DH...

Страница 39: ...ATURE PROBE 2x BIPOLAR CABLE f p o set up by the customer installer REMOTE CONTROL PANEL Flowmeter 4 20 mA brown black LOW PRESSURE TRANSDUCER CONTROL BOARD LOW PRESSURE TRANSDUCER Drain heater Auxili...

Страница 40: ...POLAR CABLE f p o set up by the customer installer PROBES TERMINAL BOARD REMOTE CONTROL PANEL Flowmeter 4 20 mA LOW PRESSURE TRANSDUCER LOW PRESSURE TRANSDUCER CONTROL BOARD Drain heater Auxiliary hea...

Страница 41: ...eater K3 relay 3 way valve K1 relay DHW integra on 4 way valve Compressor heater Injec on valve Expansion valve CIRCULATOR REMOTE CONTROL PANEL brown black PROBES TERMINAL BOARD PUFFER TANK TEMPERATUR...

Страница 42: ...k Black Black Black Black Black B9 White B8 White White D13 D12 White B12 White White 16 15 17 18 8 7 2 1 4 3 5 6 11 10 3 4 way valve and carter resistance wiring PE Yellow Green N Blue NO4 3 2 1 N Lo...

Страница 43: ...rom the necessary time to bring to temperature the oil contained in the compressor then depending on the starting temperature 12 2 Testing and startup Access to men Assistance PRG G Assistance g Manua...

Страница 44: ...lv 3V ACS set up in manual MAN if the 3 way valve for domestic hot water management is installed to test the proper operation Restore all settings from manual MAN to automatic AUT Verify during the do...

Страница 45: ...t cable of the K Touch Panel to the shield of the Modbus data network Connect the ground terminal of the power supply to the shield of the Modbus data network The shiels of the various cable sections...

Страница 46: ...o the PC make sure you DO NOT have the terminal ID09 connected to GND as shown in Figure 5 With this configuration you can simultaneously use the PGD1 control panel and the K Touch Panel If the K touc...

Страница 47: ...20V Morse o Terra quadro macchina F N 24V G G0 A B G COM3 COM3 BMS G RX TX RX TX GND 3 2 4 6 7 5b 5a CONNESSIONE PLan CONNESSIONE BMS PLan o BMS BMS connection Heat pump terminal board ground connecti...

Страница 48: ...amic 2 Power supply 4 Green yellow shield ground connection 7 HCC touch panel connection 6 Shield compact lever connector 3 5a PC PLan connection 5b PC BMS connection Watch the video for the K Touch c...

Страница 49: ...D Vdc Vdc GND 5 Vref GND Y1 Y2 Y3 Y4 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DIC1 B8 B9 B10 B11 B12 GND DI8 DI9 DI10 DIC2 PC ENDWIDERSTAND 120 BMS G MODBUS TERMINATOR RESISTOR 120 MODBUS C4 NO8 NO9 NO10 NO11 NO12...

Страница 50: ...set the parameters of operation preference summer winter setpoint Some example figures to use the command and the machine will be reported below 15 1 Fixing of the panel The panel can be fixed direct...

Страница 51: ...ors D06 Analog sensors D07 Fan speed Circulator speed D08 Cooling circuit status D09 Work regime D10 Work pressures D11 Work pressures D14 Drain Gas Control D15 EED set up D19 Inverter Engine paramete...

Страница 52: ...ction for cold external temperatures and too low temperature of the system the compressor is active until reaching a system temperature of 40 C BOILER AUTOMATIC MANAGEMENT IF REQUIRED The start up of...

Страница 53: ...educed We underline that setting this function the efficiency of the machine too is progressively reduced Mask B06 Only in AIR version Automatic Mode Change to pass from cooling mode to heating mode d...

Страница 54: ...C04 It permits to enable a pre set operation for 6 different days maximum Press and to enable disable the special day s Confirm with to enter the choice of the starting day of the particular period U...

Страница 55: ...nformation about pressures differece between pressure of high and low relation between pressure of high and low alarm count dow delta P low Mask D14 shown the temperature of compressor drain and relev...

Страница 56: ...external temperature reaches a value equal to Setpoint Differential Turn off compressors it allows to turn off the heat pump under the defined temperature in Setpoint act the integrated system totall...

Страница 57: ...the function antifreeze winter Mask Gfc17 Setpoint on the system temperature for the activation of the antifreeze that activates the circulator Set antifreeze pump primary circuit temperature set that...

Страница 58: ...maximum speed allowed can increase Mask Gfc55 it enables the control of the circulator in If the previous parameter is active also the following parameters become editable Unit ON flow water temperat...

Страница 59: ...t enables the manual management Manual valve position if the manual management is active it shows the valve opening in steps Mask Gg05 manual or automatic management of the heat pump CH HP Request it...

Страница 60: ...ALA12 Ssensor B12 broken or disconnected Automatic 60 sec yes Stop the machine ALB01 Position ID3 high pressure Manual Immediate yes Stop the machine ALB02 High pressure compressor 1 from transducer...

Страница 61: ...Gfa01 Just reporting ALT08 Threshold reached worked hors internal battery fan Manual Immediate Settable Gfa01 Just reporting ALU01 Antifreeze geothermal exchanger Manual par Gfc28 Immediate Yes Stop...

Страница 62: ...be incoherent with the working field of the unit for example operation DHW with external temperature too high Please refer to the section operative zone allowed of this guide ALC04 The compressor can...

Страница 63: ...e between B7 and B3 probes in the case of DHW production is excessive Power limit temperature It is activated if the heat pump is producing water less than 6 or more than 58 The compressor is moves to...