Alarm
code
Visualized message
Reset
Delay
Relay
Action
ALP01
Position: ID1 Flow switch geothermal circ.
water
After 5 times per
hour it becomes
manual
At the start: 15s (par.
Hc15) at regime: 5s
(par. Hc16)
Yes
Stop the machine at maximum time reached
ALP02
Position: ID4 Thermal pumps
Manual
Immediate
Yes
Stop the machine
ALP03
Positions: ID10 Fllow switch primary
circuit water
After 5 times per
hour it becomes
manual
At the start: 15s (par.
Hc12) at regime: 5s
(par. Hc13)
Yes
Stop the machine at maximum time reached
ALP04
Position: ID5 Thermal pump solar circuit
Manual
Immediate
Habilitable
(Gfc01)
Stop the pump of solar collector
ALR01
Position: ID7 Alarm boiler/ resistance
integr. system
Automatic
Immediate
Habilitable
(Gfc02)
Stop boiler/ resistance operation primary
circuit integration
ALR02
Position: ID6 Thermic boiler/resistance
DHW from digital input
Manual
Immediate
Settable
(Gfc03)
Stop operation boiler/resistance integration
DHW
ALF01
Position: ID1 Thermic fan
Manual
Immediate
Stop the machine
ALT01
Threshold reached worked hours by the
compressor 1
Manual
Immediate
Settable
(Gfa01)
Only signal
ALT02
Threshold reached worked hours by the
compressor 2
Manual
Immediate
Settable
(Gfa01)
Only signal
ALT03
Threshold reached worked hours by the
geothermal pump
Manual
Immediate
Settable
(Gfa01)
Only signal
ALT04
Threshold reached worked hours by
primary circ. pump
Manual
Immediate
Settable
(Gfa01)
Only signal
ALT05
Reached threshold worked hours pump
DHW
Manual
Immediate
Settable
(Gfa01)
Only signal
ALT07
Threshold reached worked hours solar
pump
Manuale
Immediate
Settable
(Gfa01)
Only signal
ALT08
Threshold reached worked hours
outside battery fan
Manual
Immediate
Settable
(Gfa01)
Only signal
ALU01
Geothermal frosting protection exchanger Manual (par. Gfc28) Immediate
Yes
Stop the machine
ALU02
Frosting protection primary exchanger
Manual (par. Gfc32) Immediate
Yes
Stop the machine
ALU03
Overheating exchanger
Manual
Immediate
Yes
Stop the machine
ALW01
Threshold reached high domestic water
Automatic
60 sec
Habilitable
(Gfc01)
Only signal
ALW02
Threshold reached maximum domestic
temperature at solar collector
Automatic
60 sec
Yes
Only signal
ALW03
Exceeded max. time to defrosting end
Automatic
Immediate
Yes
Only signal
ALD01
Alarm EEPROM
Manual
Immediate
Yes
Stop the machine
ALD02
Probe EVD EVO broken or disconnected
Automatic
Immediate
Yes
Stop the machine
ALD03
Engine error EEV
Manual
Immediate
Yes
Stop the machine
ALD04
Low overheating (LowSH)
Manual
Immediate
Yes
Stop the machine
ALD05
Low suction temperature
Manual
Immediate
Yes
Stop the machine
ALD06
Evaporation low temperature (LOP)
Manual
Immediate
Yes
Stop the macbine
ALD07
High evaporation pressure (MOP)
Manual
Immediate
Yes
Stop the machine
ALD08
High condensation temperature (HiTcond) Manual
Immediate
Yes
Stop the machine
ALD09
Driver offline
Automatic
Immediate
Yes
Stop the machine
ALL01
Device Power+ n. 1 Offline
Automatic
30 sec
Yes
Stop the machine
ALL02
Alarms Power+ n.1
0: No error
1: Overpower
2: Overp. engine
3: Overvoltage
4: Undervoltage
5: Overtemperature
6: Undertemperature
7: Overpower HW
8: Overtemp. engine
9: Reserved
10: Error Cpu
11: Param. default
12: Undulation DC bus
13: timeout com.ser.
14: Error thermistor
15: Error Autotuning
16: Drive disabled
17: Engine phase missing
18: Broken fan
19: Engine stalling
Manual
Immediate
Yes
Stop the machine