14.4  Main menu

To enter the menu press the button 

 .

Press the buttons   and   to navigate manus. At the end of 

operations, press 

 to come back to the main screen.

Here below the 8 menus:

A.

On-Off unit

B.

Setpoint

C.

Watch/Time table

D.

Inputs/Outputs

E.

Alarm history

F.

Board change

G.

Assistance

H.

Manufacturer

14.5  ON-OFF menu

On/Off       Unit         A01
Unit  Heat-pump

OFF

SUMMER

Mask A01: 

it  permits  to  set  the  condition  and  the 

operation  mode.  The  state  OFF  set  in  this  menu  is  always 

conditioned (ex. antifreeze operation).

MasK A02: 

It  turns  off  without  conditions  the  pump  for 

a certain period of time. Expired the time the function A01 is 

rehabilitate.

14.6  SETPOINT menu

Thermoregulation  Unit  B01
Temp.HP
Setpoint nominal

(ON)

Cooling:

12.0°C

Heating:

35.0°C

 

Mask B01: 

Variations of nominal setpoint.

Mask B02: 

Variations  of  Energy  saving  setpoint.  We 

suggest the use of the Energy saving during the night or during 

long  absences  from  home.  To  reduce  the  consumption  of  the 

unit we suggest to use the climatic curve instead of setting the 

Setpoint, because it permits a continuous flow.

MasK B05:  

it permits the choice of fan operation mode.

It is possible to chose between the following conditions:

• 

POWERFULL:  it  is  the  most  efficient  condition,  that  also 

involves the noisiness of the greater fan.

• 

NORMAL:  it  is  the  condition  of  operation  set  by  the 

manufacturer, it permits a very good compromise between 

efficiency and noisiness.

• 

QUIET1 - QUIET2 - SILENT: in these conditions of operation 

the  fan  is  slowed  down    respectively  of  10,  15,  20 

percentage points. Those conditions permit to work with 

a  noisiness  more  and  more  reduced.  We  underline  that 

setting this function the efficiency of the machine too is 

progressively reduced.

Mask B06: 

Only in AIR version. Automatic Mode Change 

to pass from cooling mode to heating mode defining a confort 

zone in which neither mode is active. To activate the function 

the  difference  between  the  cooling  and  heating  setpoint  has 

to be equal to Delta Confort. It also allows to set the operation 

mode  of the internal fan. The internal fan can follow the 

request (compressor speed) low medium or high or control the 

condensation.

Mask B07: 

it  manages  the  Automatic  End  Season.  You 

have to set the daily medium external temperature over which 

you  want  the  heating  function  is  turned  off;  if  present  the 

domestic function stay active in any case.

Mask B08: 

Optimizer management.  The  optimizer    is 

an algorithm that allows to store energy using the thermal inertia 

of the building when the conditions are more favorable.

• 

Active  optimizer:  it  activates  or  deactivates  the 

function.

• 

Final Setpoint : it shows the reference value of the heat 

pump including the Delta Optimizer.

• 

Delta  Optimizer:  it  shows  the  delta  (positive  or 

negative) due to optimization algorithm.

• 

Influence: it sets the minimum value (delta negative) 

and maximum (delta positive). This function is needed 

to limit the influence of optimizer if necessary.

Mask B09:  

it allows to set a hysteresis in shutdown. Once 

reached the Setpoint the machine, instead of turn off, continue 

operating at minimum until reaching this target on setpoint set 

up. If in the meanwhile the request increases again (ex. request 

from the domestic) the compressor come back to the operating 

regime required.

Содержание KITA AIR

Страница 1: ...INSTALLATION INSTRUCTION AIR TO AIR T H E H E A T P U M P...

Страница 2: ...ts 8 6 3 Free spaces for the assembly 8 6 4 Choice of installation place 9 6 5 External unit mounting 9 6 6 Condensate discharge preparation 9 6 7 Correct alignment 10 6 8 Probe installation 10 7 Mont...

Страница 3: ...8 12 5 Electric diagram KITA AIR 19 12 6 Internal wiring connection diagram 20 13 Commissioning 21 13 1 Preliminary controls 21 13 2 Commissioning 21 14 Control unit 22 14 1 Control panel measurement...

Страница 4: ...sary please request for original parts You can find all informations on the KITA Templari label in accordance with the regulation on labeling in particular you can find Voltage and frequency of Power...

Страница 5: ...supply For design and realization of the heat pump all the CE directives and all the DIN and VDE have been observed The electric connection of the heat pump must be made in accordance with the VDE EN...

Страница 6: ...e indicated on the plate 1 Figure 1 and 2 figure 1 1 3 3 Operation mode The heat pump can operate in two modes actionable trough the switching of the 4 way valve as shown below this modes are heating...

Страница 7: ...mension 1 Deflector 2 Fan 3 Case 4 Battery exchanger 5 Electric box 6 Side cover remove to access to electric box 7 Probe cable B2 prewired to unroll The image is intended only to indicate the main in...

Страница 8: ...he provisions in force It is recommended to pay attention do not to overexertion when lifting the internal unit It is advisable to be at least in two persons 6 Mounting and installation 6 1 Equipment...

Страница 9: ...are snowfalls install the heat pump at least 25 cm from the ground to avoid clogging at the inlet and drain zone 6 5 External unit mounting 1 Before installing the device please see the safety warnin...

Страница 10: ...e irreparable damages to the evaporator In places where there are snowfalls install the heat pump at least 25 cm from the floor to avoid clogging in the suction and condensate drain area 6 7 Correct a...

Страница 11: ...the circuit Nominal lenght Maximum lenght of the piping m of equivalent length Maximum height difference m of equivalent length Additional refrigerant charge recommended g m of equivalent length All...

Страница 12: ...connect the pump charging vacuum connection procedure 1 4 inside the external unit Perform the vacuum until reaching 0 4mbr pressure duration of procedure for about 1 h for 15m total length connection...

Страница 13: ...or incrustations of various kinds also provoking a malfunctioning of the heat pump It is possible then clean the battery with a under pressure jet of air in a parallel direction of the fins you should...

Страница 14: ...cable The cable carries low voltage control signals find a route far from sources of interference do not joints along the way possibly using a 3 core cable shield section 1 50 sq mm shield connected...

Страница 15: ...ower supply cables indication KITA AIR External unit Supply 400 Vac 50 Hz Cable 5x6 mmq Secondary line protection 230 PC protection 24 Vdc 3 fuses 5x20 4A 1 fuse 5x20 4A Internal unit Supply 230 Vac 5...

Страница 16: ...E 1 3 5 7 9 11 2 4 6 8 10 12 B2 1 3 5 7 9 11 2 4 6 8 10 12 B2 Gnd B4 GND B5 VDC B3 GND Y3 GND B7 GND C 230V auxiliary power supply internal fan A Auxiliary fuses 4 A B Power Phase Neutal and Ground fo...

Страница 17: ...switch high DI6 solar boost SGR bit0 DI8 remote on off DI9 P Lan protocol DI10 flow switch present on old models F4 Elektrische Sicherung 5x20 250 mA Y2 Y3 PWM Circulator GND 5VR C4 NO8 NO9 NO10 NO11...

Страница 18: ...alve 14 Block outputs C1 NO1 NO3 15 Block outputs C2 NO4 NO6 16 Block outputs C3 No7 Nc7 17 Block outputs C4 NO8 NO12 18 Bar hooks Din 35 6 1 2 3 4 5 9 7 8 17 10 11 12 13 14 15 16 18 18 18 12 1 Digita...

Страница 19: ...IDC2 J8 J10 J12 J13 J14 J15 J1 5 J 4 J 3 J 2 J J18 J16 R S T N R S T N N EVV EVV M OUT 5vrf M OUT 5vrf R S T Heater condensate drain Injection valve 4 4 CH 3 RS485 M 3 M 3 RS485 Bridge to the terminal...

Страница 20: ...2 1 N Lok 6 Yellow Green N Blue T Brown N Blue N Blue NO11 6 5 4 3 2 1 N Lok 9 Brown PE Yellow Green No10 Brown 8 7 9 20 19 B6 B1 14 13 12 11 10 9 Molex Mini Fit Jr 20 White 5V Red Gnd Black B11 B10 W...

Страница 21: ...y the proper operation Access to menu D inputs outputs to control the different temperatures from sensors Screen D01 B1 it shows the value of liquid sub cooling in the heat pump it has to stay in a ra...

Страница 22: ...ivation It activates when the solar panels are installed and active It activates when the defrosting procedure is active 4 Unit status The unit can be in one of the following states OFF ON ENERGY S AU...

Страница 23: ...20 percentage points Those conditions permit to work with a noisiness more and more reduced We underline that setting this function the efficiency of the machine too is progressively reduced Mask B06...

Страница 24: ...the other days press and proceed as explained above Contrary it is possible to copy the setting in different days once entered in mask C02 press the button to have access to the choice of the day you...

Страница 25: ...ating DSH Discharge Super Heating Mask D19 Parameters Inverter Engine Mask D20 Parameters Inverter Engine Mask D21 Parameters Inverter Engine Masks D30 D31 masks relevant to the external battery fan Y...

Страница 26: ...ion is active OFF Propor it s the percentage of the proportional band Hc06 that as defaut is set at 10 under that the integration shut down OFF Diff Degrees the integration has to produce more on Setp...

Страница 27: ...the defrosting is finished because the maximum time is exceeded Mask Gfc50 It allows to enable the condensate drain in fix or intermittent mode in base on the external temperature Res drain cond it e...

Страница 28: ...bles speed manual management of compressor for the heat pump in heating and cooling speed if the manual management is active it shows the compressor speed for the heat pump Mask Gg06 it enables the de...

Страница 29: ...ors D06 Analog sensors D07 Fan speed Circulator speed D08 Cooling circuit status D09 Work regime D10 Work pressures D11 Work pressures D14 Drain Gas Control D15 EED set up D19 Inverter Engine paramete...

Страница 30: ...A12 Probe B12 broken or disconnected Automatic 60 sec Yes Stop the machine ALB01 Position ID3 High pressure Manual Immediate Yes Stop the machine ALB02 High pressure of the compressor 1 from transduce...

Страница 31: ...e Immediate Settable Gfa01 Only signal ALT08 Threshold reached worked hours outside battery fan Manual Immediate Settable Gfa01 Only signal ALU01 Geothermal frosting protection exchanger Manual par Gf...

Страница 32: ...of time the cause can be the inertia of the system and the nearness between the temperatures of air and water If it occurs occasionally it s just a no serious signal permitting to the unit to keep on...

Страница 33: ...umer 1 Nominal diameter mm 910 Maximum input power kW 0 625 Maximum current A 1 1 Max speed rps 610 Max air flow m3 h 15000 Internal fan Model EBMPAPST Type Inverter BLDC Numer 1 Nominal diameter mm 8...

Страница 34: ...ate Applied standard Standard Armonizzati EN 55014 1 2006 A1 2009 EN 55014 2 1997 A 2001 A2 2008 EN 61000 3 2 2006 A1 A2 2009 EN 61000 4 2 2008 61000 4 4 2008 EN 61000 4 5 2008 EN 61000 4 6 2008 Angew...

Страница 35: ...Note...

Страница 36: ...vers 26 07 2019 C via Pitagora 20A 35030 Rubano PD Italia Tel 39 049 8597400 39 049 5225929 www templari com info templari com T H E H E A T P U M P...

Отзывы: