15 Alarms
Alarm
code
Visualized message
Reset
Delay
Relay
Action
ALA01
Probe B1 broken or disconnected
Automatic
60 sec
Yes
Stop the machine
ALA02
Probe B2 broken or disconnected
Automatic
60 sec
Yes
If there is a geothermal modulating pump it
is set at the maximum speed
ALA03
Probe B3 broken or diconnected
Automatic
60 sec
Yes
Stop the regulation of the domestic circuit
ALA04
Probe B4 broken or disconnected
Automatic
60 sec
Yes
Stop the machine
ALA05
Probe B5 broken or disconnected
Automatic
60 sec
Yes
Stop the pump of the solar collector
ALA06
Probe B6 broken or disconnected
Automatic
60 sec
Yes
Stop the functions enabled by the outside
probe
ALA07
Probe B7 broken or disconnected
Automatic
60 sec
Yes
Stop the machine
ALA08
Probe B8 broken or disconnected
Automatic
60 sec
Yes
Stop the pump of the solar collector
ALA09
Probe B9 broken or disconnected
Automatic
60 sec
Yes
If Siam compressor stops the compr.
ALA10
Probe B10 broken or disconnected
Automatic
60 sec
Yes
If there is the electronic expansion valve it
stops the machine
ALA11
Probe B11 broken or disconnected
Automatic
60 sec
Yes
Stop the machine
ALA12
Probe B12 broken or disconnected
Automatic
60 sec
Yes
Stop the machine
ALB01
Position: ID3 High pressure
Manual
Immediate
Yes
Stop the machine
ALB02
High pressure of the compressor 1 from
transducer
Manual
Immediate
Yes
Stop the machine
ALB03
Low pressure of the compressor/s from
transducer
Automatic (par.
Hc05)
At the start: 40s (par.
Hc03) at regime: 10s
(par. Hc04)
Yes
Stop the machine
ALC01
Position: ID2 Thermal compressor 1 or
allarm inverter
Manual
Immediate
Yes
If 1 comp. enabled: stop the machine
If 2 comp. enabled: stop comp.1 (if comp. 2
is available)
ALC02
Position: ID9 Thermal compressor 2
Manual
Immediate
Yes
Stop comp.2 (if comp. 1 is available)
ALC03
Alarm envelope:
0: Max.rel.compr.
1: Max.press.drain
2: Power limit
3: Max.press.suc.
4: Min.rel.compr.
5: Min.diff.pressure.
6: Min.press.drain
7: Min. press.suc.
Compressor off for working out of
envelope (only with compressor Siam)
Manual
60 sec (par. H1b14)
Yes
Stop the compressor
ALC04
Alarms missing start of the compressor
(only with compressor Siam)
After 5 times per
hour it becomes
manual
60 sec (par. H1b11)
Yes
Stop the compressor
ALC05
Max.drain time (only with compressor
Siam)
After 3 times per
hour it becomes
manual
Immediate
Yes
Stop the compressor
ALC06
Delta pressure < minimum request for
the return of the compr. oil (only with
compressor Siam)
Automatic
120 sec (par. H1b12)
Yes
Stop the compressor