![Templari KITA AIR Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/templari/kita-air/kita-air_installation-instruction_1085666010.webp)
10
www.templari.com
Frost proof
depth
min 200mm
Frost
proof
depth
•
Example 2 condensate drain
•
Example 3 condensate drain with condensate drain element
The condensation water accumulated during the operation must
be carried away without it can freeze. To ensure the correct
outflow the heat pump must be in a horizontal position. The
condensation water pipe must have a minimum diametre of
18mm and must flow in the drain channel without it can freeze.
Don’t discharge the condensate directly into purification basins
and moats. The aggressive fumes and the condensation pipe, if
it isn’t protected against frost, can cause irreparable damages to
the evaporator.
In places where there are snowfalls, install the heat pump at least 25
cm from the floor to avoid clogging in the suction and condensate
drain area.
6.7 Correct alignment
Put horizontally the heat pump
KITA AIR Templari® so that
the condensate can flow. The product must be installed with
amortized feet, purchased separately. The amortized feet
increase the height of the product, facilitating the flow of
condensate and reducing vibrations.
6.8 Probe installation
All probe used for the operation of the plant must be installed
properly in the appropriate wells using a suitable thermal paste.
WARNINGS!
Installing the probes not in a proper way will voids the warranty.
7 Montaggio e installazione
dell’unità interna
7.1 Internal unit sizes and components
Содержание KITA AIR