14.8 Input/Output menu
Input/Output D06
Analog inputs
B11 = Condensation:
14.Obarg e 21.5°C
B12 = Evaporation:
14.Obarg e 21.5°C
Accessing to this menu it is possible to read a lot of values.
From the screen D01 to the screen D06 it is possible to read the
following sensors:
B1: it represents the SUBCOOLING in the heat pump operation
(heating). With an appropriate refrigerant charge the
indicative value of B1 probe should stay between 3.5 and 5*.
B2: internal ambient temperature.
B6: compressor head temperature
B8: External air temperature.
B9: flow temperature of the compressor.
B10: suction temperature of the compressor.
B11: condensate pressure and relevant temperature.
B12: evaporation pressure and relevant temperature.
*If the value is very different from these parameters please
contact your service centre
Mask D07:
speed management of the fan.
Mask D08:
view of the condition of the cooling circuit:
percentage of electronic expansion valve opening, B10, B12.
Mask D09:
view of working regime.
•
Capacity required.
•
Real capacity.
•
Compressor speed.
•
Waiting time ON: minimum time elapsing between a
shutdown and the other, or time necessary to equalize the
pressure of high and low to the right starting value.
Mask D10:
it is show the working zone in the envelope
and alarm count down “out of envelope”.
Mask D11:
it dispays information about pressures.
•
differece between pressure of high and low
•
relation between pressure of high and low
•
alarm count dow “delta P low“
Mask D14:
shown the temperature of compressor drain
and relevant condition and envelope zone.
Mask D15:
overheating of compressor drain and relevant
control type active.
•
SSH = Suction Super Heating
•
DSH = Discharge Super Heating
Mask D19:
Parameters Inverter/Engine
Mask D20:
Parameters Inverter/Engine
Mask D21:
Parameters Inverter/Engine
Masks D30, D31: masks relevant to the external battery fan. You
can find the rpm and instantaneous power absorbed.
Mask D33:
summary of the unit parameters
14.9 Alarms history menu
Alarm history E02
ALL02 16:02 28/10/13
Power plus off-line
Inlet Outlet
Plant : 18.2°C 17.8°C
Ext. T: 18.0°C
ACS : 20.5°C
Press : Hp 13.0 Lp 13.0
In this menu it is possible to display the alarms due to a possible
protection intervention. The alarm list is in the chapter 13.
14.10 Board change menu
The board change menu allows to display the other heat pump/s
when they are connected in pLAN and the settings of electronic
board/panel allow it.
14.11 Assistance menu
The Assistance menu presents a submenu structured as follows:
a. Language change
b. Information
c. Input / output assistance
d. Hours worked
e. Config. BMS
f. Param. Assistance
g. Manual management
A. LANGUAGE CHANGE
This menu allows the language change, if available.
Mask Ga01
Possible language: Italian, English, German e French.
B. INFORMATION
*
This menu contains masks where there are relevant information
to the software, to the control board, to the valves and the
inverter, reserved to the technical assistance.
C. INPUT / OUTPUT ASSISTANCE
This menu contains masks of input and outout reserved to the
technical assistance.
Gc16:
it displays in steps and percentage the injection
valve opening.
Gc17:
inverter status.
Gc18:
inverter status.
Gc22:
inverter status.
Gc23:
inverter status.
Gc24:
digital inputs
Gc25:
digital inputs
Gc26:
digital inputs
Gc27:
digital outputs
Gc29:
digital outputs
Gc32:
fan status
D. WORKED HOURS
This menu allows to monitor the working time
Mask Gd01: In this mask operation total hours of the heat
pump are displayed.