Chapter 7 Error Codes and Troubleshooting
This procedure requires access to the circuitry of a unit
under live power. Accidental contact with line voltage is
possible. Only qualified personnel should perform these proce-
dures. Potentially lethal voltages are present.
Troubleshooting procedures:
1. If an error message is displayed, refer to table 7.1 to see what
caused it and what action to take to correct the problem.
2. Check each point listed below. Experience has proven that
many control problems are caused by a defective instrument
and not the controller
•
Incorrect settings
• Line wires are improperly connected
• No voltage between line terminals
• Incorrect voltage between line terminals
• Connections to terminals are open, missing, or loose
• Thermocouple is open at tip
• Thermocouple lead is broken
• Shorted thermocouple leads
• Short across terminals
• Open or shorted heater circuit
• Open coil in external contactor
• Burned out line fuses
• Burned out relay inside control
• Defective solid-state relays
• Defective line switches
• Burned out contactor
• Defective circuit breakers
3. If the points listed on the above chart have been checked and
the controller still does not function properly, it is recom-
mended that the instrument be returned to the factory for
inspection. Do not attempt to make repairs without a qualified
engineer and proper technical information, as damage may
result. It is also recommended to use adequate packing mate-
rials to prevent damage during transportation.
4. Dismantle the controller according to figure 7.1. Refer to table
7.2 for some probable causes and actions.
Содержание TEC-9300
Страница 2: ...NOTES...
Страница 4: ...NOTES...
Страница 9: ...5 1 4 Keys and Displays continued...
Страница 10: ...6 1 5 Menu Overview...
Страница 12: ...8 1 7 Parameter Description NOTE For RS 232 Short J1 Open Cut J2 Using RS 232 will disable Event Input Function...
Страница 13: ...9 NOTE Parameter 1N1 continued on next page...
Страница 14: ...10 NOTE Parameter O1TY continued on next page...
Страница 15: ...11...
Страница 16: ...12...
Страница 17: ...13 Note Calibration menu is for supplier configuration use only...
Страница 18: ...14...
Страница 24: ...20 2 11 Output 1 Wiring...
Страница 25: ...21 2 12 Output 2 Wiring...
Страница 27: ...23 2 15 RS 485...
Страница 62: ...58...
Страница 63: ...59...
Страница 64: ...60 NOTES...
Страница 69: ...65 9 3 Parameter Table...
Страница 70: ...66...
Страница 71: ...67...
Страница 72: ...68...
Страница 73: ...69...
Страница 74: ...70...
Страница 75: ...71...
Страница 76: ...72...
Страница 77: ...73...
Страница 78: ...74...
Страница 79: ...75...
Страница 80: ...76 P 100 0 RC16 07 Lo 9 3 Communication Examples...
Страница 81: ...77 A 1 Menu Existence Conditions...
Страница 82: ...78...
Страница 83: ...79...
Страница 84: ...80 A 2 Factory Menu Description...
Страница 89: ...85 A 4 Memohe following table as a master copy for your settings...
Страница 90: ...86...