3–16 Failure Transfer
The controller will enter failure mode if one of the following conditions occurs:
1.
SB1E
occurs (due to input 1 sensor break or input 1 current below 1mA if 4–
20mA is selected or input 1 voltage below 0.25V if 1–5V is selected) if PV1, P1-
2, or P2-1 is selected for PVMD or PV1 is selected for SPMD.
2.
SB2E
occurs (due to input 2 sensor break or input 2 current below 1mA if 4–
20mA is selected or input 2 voltage below 0.25V if 1–5V is selected) if PV2, P1-
2, or P2-1 is selected for PVMD or PV2 is selected for SPMD.
3.
ADER
occurs if the A-D converter of the controller fails.
Output 1 and output 2 will perform the failure transfer function as one of the fol-
lowing conditions occurs:
1. During power starts (within 2.5 seconds).
2. The controller enters failure mode.
3. The controller enters manual mode.
4. The controller enters calibration mode.
Output 1 failure transfer, if activated, will perform:
1. If output 1 is configured as proportional control (PB1≠0), and BPLS is selected
for O1FT, then output 1 will perform bumpless transfer. Thereafter, the previous
averaging value of MV1 will be used for controlling output 1.
2. If output 1 is configured as proportional control (PB1≠0), and a value of 0 to
100.0% is set for O1FT, then output 1 will perform failure transfer. Thereafter,
the value of O1FT will be used for controlling output 1.
3. If output 1 is configured as ON-OFF control (PB1≠0), then output 1 will be driv-
en OFF if O1FN selects REVR and be driven ON if O1FN selects DIRT.
Output 2 failure transfer, if activated,
will perform:
1. If OUT2 selects COOL, and BPLS is selected for O1FT, then output 2 will per-
form bumpless transfer. Thereafter, the previous averaging value of MV2 will be
used for controlling output 2.
2. If OUT2 selects COOL, and a value of 0 to 100.0% is set for O2FT, then output
2 will perform failure transfer. Thereafter, the value of O1FT will be used for
controlling output 2.
Alarm 1 failure transfer
is activated as the controller enters failure mode.
Thereafter, alarm 1 will transfer to the ON or OFF state preset by A1FT.
Exception:
If A1FN is configured for loop break (LB) alarm or sensor break
(SENB) alarm, alarm 1 will be switched to ON state independent of the setting of
A1FT. If A1FN is configured for dwell timer (TIMR), alarm 1 will not perform
failure transfer.
Alarm 2 failure transfer
is activated as the controller enters failure mode.
Thereafter, alarm 2 will transfer to the ON or OFF state preset by A2FT.
Exception:
If A2FN is configured for loop break (LB) alarm or sensor break
(SENB) alarm, alarm 2 will be switched to ON state independent of the setting of
A2FT. If A2FN is configured for dwell timer (TIMR), alarm 2 will not perform
failure transfer.
Failure mode occurs as:
1. SB1E
2. SB2E
3. ADER
Failure Transfer of output
1 and output 2 occurs as:
1. Power start (within 2.5 seconds)
2. Failure mode is activated
3. Manual mode is activated
4. Calibration mode is activated
Failure Transfer of alarm 1
and alarm 2 occurs as:
Failure mode is activated
Failure Transfer Setup:
1. O1FT
2. O2FT
3. A1FT
4. A2FT
Содержание TEC-9300
Страница 2: ...NOTES...
Страница 4: ...NOTES...
Страница 9: ...5 1 4 Keys and Displays continued...
Страница 10: ...6 1 5 Menu Overview...
Страница 12: ...8 1 7 Parameter Description NOTE For RS 232 Short J1 Open Cut J2 Using RS 232 will disable Event Input Function...
Страница 13: ...9 NOTE Parameter 1N1 continued on next page...
Страница 14: ...10 NOTE Parameter O1TY continued on next page...
Страница 15: ...11...
Страница 16: ...12...
Страница 17: ...13 Note Calibration menu is for supplier configuration use only...
Страница 18: ...14...
Страница 24: ...20 2 11 Output 1 Wiring...
Страница 25: ...21 2 12 Output 2 Wiring...
Страница 27: ...23 2 15 RS 485...
Страница 62: ...58...
Страница 63: ...59...
Страница 64: ...60 NOTES...
Страница 69: ...65 9 3 Parameter Table...
Страница 70: ...66...
Страница 71: ...67...
Страница 72: ...68...
Страница 73: ...69...
Страница 74: ...70...
Страница 75: ...71...
Страница 76: ...72...
Страница 77: ...73...
Страница 78: ...74...
Страница 79: ...75...
Страница 80: ...76 P 100 0 RC16 07 Lo 9 3 Communication Examples...
Страница 81: ...77 A 1 Menu Existence Conditions...
Страница 82: ...78...
Страница 83: ...79...
Страница 84: ...80 A 2 Factory Menu Description...
Страница 89: ...85 A 4 Memohe following table as a master copy for your settings...
Страница 90: ...86...