6. COMMUNICATOR PARAMETERS
Before configuring the communicator call your Monitoring company and specify
the necessary parameters - phone numbers, the subscriber account number,
communication report and event codes.
Before starting to configure the parameters erase the non-transmitted codes
from the event buffer in address 93 by pressing the 0 key once.
ADDRESS 60
PRIMARY PHONE NUMBER (PHONE 1)
Tel No 1
In this address the primary phone number for communication with the monitoring
station is set. Hexadecimal indication. The maximum lenght of the phone number
is 16 symbols, including the pause symbols (ON and 2) and the symbols for
entering a DTMF dialing (ON and 1).
DEFAULT
:
No phone number entered
ADDRESS 61
SUBSCRIBER ACCOUNT NUMBER 1
PANEL ID 1
This is the panel ID number for the primary monitoring station. The lenght of
the number is 3 or 4 digits (depending on the report format - 3x or 4x). The 0
symbol is replaced by an A (See the hexadecimal programming table in Appendix
A).
DEFAULT
:
9999
ADDRESS 62
COMMUNICATION REPORT 1
COMMUNICATION
The communication report types to the monitoring station are listed in the table
REPORT 1
below. The symbols from 0 to B could be used.
[0]
User report - dialer
[1]
SP=10 pps; HS=KO=1400Hz; Data=1900Hz; 3x1, 3x2, 4x1, 4x2;
[2]
SP=10 pps; HS=KO=1400Hz; Data=1900Hz; EXT; 3x1, 4x1;
[3]
SP=20 pps; HS=KO=1400Hz; Data=1900Hz; 3x1, 3x2, 4x1, 4x2;
[4]
SP=20 pps; HS=KO=1400Hz; Data=1900Hz; EXT; 3x1, 4x1;
[5]
SP=20 pps; HS=KO=2300Hz; Data=1800Hz; 3x1, 3x2, 4x1, 4x2;
[6]
SP=20 pps; HS=KO=2300Hz; Data=1800Hz; EXT; 3x1, 4x1;
[7]
SP=40 pps; HS=KO=2300Hz; Data=1800Hz; 3x1, 4x2;
[8]
SP=40 pps; HS=KO=2300Hz; Data=1800Hz; EXT; 3x1;
[9]
SP=40 pps; HS=KO=2300Hz; Data=1800Hz; 3x1, 4x2; Checksum;
[A]
SP=40 pps; HS=KO=2300Hz; Data=1800Hz; EXT; 3x1; Checksum;
[B]
ADEMCO CONTACT ID
[C]…[F] - reserved for future use
DEFAULT
:
1
ADDRESS 63
REPORT FORMAT 1
x 1
Choosing the format of the set report 3x1, 4x1. The LEDs from 1 to 6 light.
x 2
Choosing the format of the set report 3x2, 4x2. The LEDs from 1 to 6 do not
light.
DEFAULT
:
x2
ADDRESS 64
SECONDARY PHONE NUMBER (PHONE 2)
Tel No 2
In this address the secondary phone number for communication with the
monitoring station is set. Hexadecimal indication. The maximum lenght of the
phone number is 16 symbols, including the pause symbols (ON and 2) and the
symbols for entering a DTMF dialing (ON and 1).
DEFAULT
:
No entered phone number