TSA-200 / TSA-200XT / TSA-240 / TSA-240XT
© 2010 –
2014 Telefire Fire & Gas Detectors Ltd
Revision 1.06 July 2014
– Page 14 of 53 –
ITEM
RATING
REMARKS
COMMUNICATION
PARAMETERS
Battery Charge Current, CP in
Alarm
No current
Charging is disabled in Alarm
Battery Fuse
PTC, 3A
Self Resettable
Current consumption from battery
60mA Quiescent condition, buzzer ON
Control Panel (CP) Only
Current consumption (TSA-200XT /
TSA-240 / TSA-240XT)
110mA, two zones in alarm
CP Only, extinguisher OFF
Current consumption(TSA-200XT /
TSA-240 / TSA-240XT)
160mA, two zones in alarm,
CP Only, extinguisher ON
Max Current from Batteries
3A
Limited by PTC
Battery voltage range
20.4V DC min to 27.8V DC max
Max (single) battery size
to 9.5 (W) by 7 (D) by 12.5 (H) cm each
MB INTERFACES
Fire Alarm Relay (1) contacts rating 48V DC, 1.5A, not monitored
Dry contact SPDT
Fault Relay (2) contacts rating
48V DC, 1.5A, not monitored
Dry contact SPDT
NC when unpowered
OUTPUTS
MB outputs are monitored
Outputs EOL
3.9 K ±5%
Only required for MB outputs