MERIDIAN
UNIVERSAL GAS DETECTOR
CONFIGURATION & SETUP
5-12
USE AND DISCLOSURE OF DATA
Information contained herein is classified as EAR99 under the U.S. Export Administration Regulations. Export, reexport or diversion contrary to U.S. law is
prohibited.
Current Loop,
cont.
Inhibit (ALL)
Takes the 4-20mA signal and adjusts it during Inhibit for either indi
-
vidual sensor or the entire device.
Default= 3.8mA
Range 3.8 to 24mA in .1mA steps
†
Over Range
Used to select the current when the gas concentration is over range.
Default =21.6mA
Options: 3.6mA or 21.6mA
†
Fault
Used to select the current when the transmitter reports a general
fault.
Default= 3.6mA
Options: 1.0mA or 3.6mA
General
Time/Date
Allows editing the time and date settings. Time in military format and
date is mm/dd/yy format.
N/A
Editor
Name – An editable 16 ASCII charter text string. Typically used to
identify the monitored point by your tag # or other familiar terminol
-
ogy.
Lat – Allows entry of degrees and fraction of degrees.
Long – Allows entry of degrees and fraction of degrees.
†
General,
cont.
Regional
Daylight Savings – Select
YES
or
NO
.
Date Format – Select
MDY
,
DMY
or
YMD
.
Languages – Select from list provided.
†
Restart
Meridian
Allows the reboot of the device. Select
ESC
or
ENTER
.
†
† Indicates the minimum user access level required to access this particular parameter.
Table 5-2: Transmitter Setup Menu Parameters (Continued)
Item
Sub-Item
Description*
OA SMA