11
WIND sensor
1.1
4.1
Factory setting
ACTIVATED
The anemometer (
ANEM4
) detects wind speed, which the control unit compares with the threshold set through
DIPs 1-2-3
(see table).
The control unit is only compatible with anemometers generating 4 pulses per rev.
ALARM ACTIVATED when
What happens with ALARM ACTIVATED
ALARM NOT ACTIVE when
The detected speed is higher
than the set threshold (see table
at side).
The control unit tilts the pergola slats at
33%
of full
opening. The control unit executes
no command
.
The sensor has detected a lower
speed than the set threshold for 60
seconds.
L2
WIND
Alarm priority
HIGH
The temperature sensor (NTC 10K/3435K) activates whenever there is danger of ice forming.
TEMPERATURE sensor
1.1
4.2
Factory setting
DEACTIVATED
TEM
PERATURE
Alarm priority
MEDIUM
ALARM ACTIVATED when
What happens with ALARM ACTIVATED
ALARM NOT ACTIVE when
The measured temperature is below 2 °C.
The control unit tilts the pergola slats to
66%
of full opening. The
control unit only executes
hold-to-run commands
.
The measured temperature is above 3 °C.
Activation/
deactivation
of the
temperature
sensor with P1
*
The buzzer will make a beep each time the button is pressed.
P1
ACTIVATION
(only if the sensor is
connected)
*
7x
DEACTIVATION
*
7x
/
HOLD
(5 s)
continuous
sound
4 s
L2 flashes
once every 3 s
t
°
L2
DIP1 DIP2 DIP3 Km/h
OFF
OFF
OFF
40
OFF
OFF
ON
45
OFF
ON
OFF
50
OFF
ON
ON
55
ON
OFF
OFF
60
ON
OFF
ON
65
ON
ON
OFF
70
ON
ON
ON
75