40
For personnel protection the metal housing of the ISM must be connected according to the applicable regulations,
such as IEC 62271-1, IEC 62271-100, IEC 62271-200 via the marked earth screw of the ISM to the earthing
arrangement of the particular panel. The earthing connection can be carried out with a cable or a flat copper bar.
The area around the earth screw shall be cleaned before providing the earth connection. After the occurrence of a
short circuit, the proper condition of the protective earthing must be checked.
4.1.8 Protective earthing
Fault current (1 s)
Maximum temperature
Cross section of earth connection
16 kA
300 °C
55-95 mm²
20 kA
300 °C
70-120 mm²
25 kA
300 °C
95-140 mm²
31.5 kA
300 °C
120-190 mm²
30Nm
Table 7 - Reference values for cross sections of earth connections (copper)
Figure 65
ISM protective earthing connection
Figure 62
Adjust the indicator for both closed and ope-
ned states of the switching module.
Figure 63
Position indicator shows
that main contacts are open
Figure 64
Position indicator shows
that main contacts are closed
Washer
Lock washer
Bolt M12x25
Содержание TAVRIDA ELECTRIC VCB15 LD
Страница 1: ...VCB Vacuum Circuit Breaker 17 5kV 31 5kA 2000A 24kV 16kA 800A User Guide...
Страница 3: ...1 Product description...
Страница 7: ...2 Nameplates and seals...
Страница 11: ...3 Product handling...
Страница 23: ...4 Installation...
Страница 50: ...5 Commissioning...
Страница 57: ...6 Operation...
Страница 61: ...7 Maintenance and troubleshooting...
Страница 66: ...8 Disposal...
Страница 68: ...Appendix 1 Product range...
Страница 71: ...Appendix 2 Overall drawings...
Страница 74: ...75 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Страница 81: ...82 ISM25_LD_2 1 PCD 150 mm Weight 35 kg ISM25_LD_2 2 PCD 150 mm Weight 37 kg...
Страница 85: ...Appendix 3 Secondary schemes...
Страница 86: ...87...
Страница 87: ...88...
Страница 88: ...89...
Страница 89: ...90...
Страница 90: ...91...
Страница 91: ...92...
Страница 92: ...93...