1.3 Main technical parameters
Main technical data and circuit breaker technical parameters are presented in the tables below.
Table 1 - Main technical parameters
Type
VCB15_LD
VCB15_Shell
VCB25_LD
Rated voltage (Ur)
≤ 12 kV
≤ 17.5 kV
≤ 24 kV
Rated normal current (Ir)
≤ 800 A
≤ 1250 A
1)
≤ 2000 A
≤ 800 A
Rated power frequency withstand voltage (Ud)
28 (42)
2)
kV
38 (42) kV
2)
50 kV
Rated lightning impulse withstand voltage (peak) (Up)
75 kV
95 kV
3)
125 kV
Rated short-circuit breaking current (Isc)
≤ 20 kA
4)
≤ 31.5 kA
4)
≤ 16 kA
4)
Rated peak withstand current (Ip)
≤ 50 kA
≤ 82 kA
≤ 40 kA
Rated short-time withstand current (Ik)
≤ 20 kA
≤ 31.5 kA
≤ 16 kA
Rated duration of short circuit (tk)
4 s
Rated frequency (fr)
50/60 Hz
Rated operating sequence
O-0.3s-CO-10s-CO-10s-CO
5)
Standards
IEC 62271-100
GB 1984- 2003
IEC 62271-100
GB 1984- 2003
IEC 62271-100
Weight (depending on Pole centre distance) for three-phase ISM
34-36 kg
51-55 kg
36-38 kg
Weight for single phase ISM
13 kg
14 kg
CM supply voltage
Rated range of supply voltage of CM_16_1(60_x_x)
24V to 60V DC
Rated range of supply voltage of CM_16_1(220_x_x)
110V to 220V AC/DC
Power consumption of CM
Charging the close and trip capacitors of CM_16_1(60_x_x)
≤ 25 W
Charging the close and trip capacitors of CM_16_1(220_x_x)
≤ 42 W AC
6)
≤ 37 W DC
Permanent power consumption (standby) of CM_16_1(60_x_x)
≤ 5 W
Permanent power consumption (standby) of CM_16_1(220_x_x)
≤ 7 W AC
7)
≤ 5 W DC
Inrush current of of CM_16_1(60_x_x) with discharged capacitors
≤ 120 A
Inrush current of of CM_16_1(220_x_x) with discharged capacitors
≤ 18 A
Inrush time constant of CM_16_1(60_x_x) with discharged capacitors
≤ 0.5 ms
Inrush time constant of CM_16_1(220_x_x) with discharged capacitors
≤ 4 ms
Altitude above sea level
1000 m
8)
Relative humidity in 24 hours
≤ 95 %
Relative humidity over 1 month
≤ 90 %
Temperature range
-25 °C ... +55 °C
1) For VCB ISM15_Shell with Low upper terminal – up to 1250 A, with High upper terminal – up to 2000 A.
2) The information in brackets refers to the national Chinese standards GB1984-2003 and installation altitude of maximum 1000 m.
3) Parameter valid only when ISM is used with insulation masks. For details see dimensional drawings and accessory information.
4) At 40% d.c. component.
5) The number of sequential Close-Trip operations with interval 10 seconds should not exceed 10. The number of Close-Trip operations should not
exceed 60 per hour. Sequence of 10s Close-Trip operations can be repeated only after 260 s pause.
6) At Cos j >0.66.
7) At Cos j >0.33.
8) Up to an installation altitude of 1000 m above sea level. Above 1000m, the external insulation measurement of the ISM must be increased by
the atmospheric correction factor Ka according to IEC 62271-1 compared to the insulation measurement at sea level. The maximum allowed
altitude is 2000 m above sea level.
Содержание TAVRIDA ELECTRIC VCB15 LD
Страница 1: ...VCB Vacuum Circuit Breaker 17 5kV 31 5kA 2000A 24kV 16kA 800A User Guide...
Страница 3: ...1 Product description...
Страница 7: ...2 Nameplates and seals...
Страница 11: ...3 Product handling...
Страница 23: ...4 Installation...
Страница 50: ...5 Commissioning...
Страница 57: ...6 Operation...
Страница 61: ...7 Maintenance and troubleshooting...
Страница 66: ...8 Disposal...
Страница 68: ...Appendix 1 Product range...
Страница 71: ...Appendix 2 Overall drawings...
Страница 74: ...75 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Страница 81: ...82 ISM25_LD_2 1 PCD 150 mm Weight 35 kg ISM25_LD_2 2 PCD 150 mm Weight 37 kg...
Страница 85: ...Appendix 3 Secondary schemes...
Страница 86: ...87...
Страница 87: ...88...
Страница 88: ...89...
Страница 89: ...90...
Страница 90: ...91...
Страница 91: ...92...
Страница 92: ...93...