61
To open the ISM15_Shell manually, the torque shall be applied to the interlocking shaft - see Figure 85. The
torque shall be applied counterclockwise of shaft rotation (90 degrees angle). The torque shall not be applied at
the end of shaft rotation. ISM15_Shell_2 has a built in electrical interlock that interrupts the ISM coil circuit after
the interlocking shaft is rotated counterclockwise. After manual trip, the shaft should be rotated clockwise to
unlock the ISM.
Figure 85
ISM15_Shell manual trip execution