26
in the 3
rd
pos.
for SIM 2
ErХ
communication error with base station.
0 … 9
is error code (see interpretation in the table on
Page
27
)
For LAN
in the 2
nd
and
3
rd
pos.
CAB:CON
cable connected
CAB:DISC
cable disconnected
For HE
in the 2
nd
and
3
rd
pos.
(8 possible
Values)
«_»
AL not assigned in ES
R
Status «
Normal
» and
ready
to be armed for all types of
AL (except
«fire heat double-event»
).
AL resistance within
3,0 to 5,0 kOhm
.
For AL of «fire heat double-event» type means that
only
one detector
is in fire status
f
Status «
Failure»
.
Resistance ranges for ALs of different types are various.
For details see manual integrated into
Setup Module
of
MSS Astra Pro software
D
AL resistance within
1,5 to 3,0 kOhm
.
For AL of «fire combined double-event» type means that
only one detector
is in fire status.
For AL of «fire heat double-event» type indicates
«
Normal
» status and
readiness
to be armed
F
Status «
Fire
»:
- AL resistance within
5,0 to 12 kOhm
for all AL of
«fire…» types;
- AL resistance within
0 to 1,5 kOhm
for «fire combined
double-
event» type;
- AL resistance within
1,5 to 3,0 kOhm
for «fire
combined single-
event» type
A
or
E
Status «
Alarm
» or «
Violation
» for “intrusion” and
“technological” AL correspondingly.
Resistance of AL
between 0 and 3,0 кOhm
or
from 5,0
кOhm till open-circuit status
.
For HKP
in the 2
nd
pos.
PNC
Key «
» pressed (Panic)
NOR
Status «Normal»
in the 3
rd
pos.
ALM
Status «Violation» for AL2 («Zone2»)
NOR
Status «Normal» for AL2 («Zone2»)