4)
install BPA on
din rail
5)
close the case cover until it clicks
4
Connect the wires to the terminals in accordance with Table 1
5
Register BPA in the CONTROL PANEL accordance with p.7.3
10 TEST
1)
Press and release the opening button on the BPA, control in PKM
Astra Pro or on the CONTROL PANEL screen of Astra-812 Pro the
notifications "Opening" / "Restoring the opening".
2)
On the loop, initiate the state "Fire", "Alarm" or "Alarm" (depend-
ing on the type of loop). Control the corresponding indication on the
leds ZONE1-ZONE4 of the BPA (see table 6), in the CONTROL
PANEL "Astra-812 Pro", in the PKM Astra Pro the corresponding noti-
fication.
3)
Irradiate for 1-2 sec using the upper LP button the BPA led "IN-
TERFACE". Control in the CONTROL PANEL "Astra-812 Pro" the
message "TST", in the PKM Astra Pro - the notification "Test fire /
alarm" (the outputs are not activated in this case).
4)
Through PKM Astra Pro, CONTROL PANEL menu "Astra-812
Pro" in the settings of the BPA, enable line integrity control (if control
was disabled).
5)
Check the indication of the BPA (see Table 5) and the transmis-
sion of notifications to the CONTROL PANEL "Astra-812 Pro", PKM
Astra Pro, performing actions on the outputs OUT1, OUT2 (in turn) in
the following order:
- disconnect the line with actuators and terminal element from the
output;
- connect the line with actuators and terminal element to the output;
- close the output element with a piece of wire (jumper);
- clear the short.
6)
Upon completion of the test, restore the original connections and
BPA settings.
11 WARRANTY
The operation warranty period is 5 years from the date of operation
start-up, but no longer than 5 years 6 months from the date of manu-
facturing subject to the requirements of User guide.
Manufacturer:
ZAO NTC TEKO
420108, Russia, Kazan,
Gafuri str., 71
Tel.:+7(843) 528-03-69
Made in Russia