4  DESIGN 

 

4.1 

 

The  BPA  is  made  in  the  form  of  a  module,  consisting  of  a  base 

and  a  removable  cover.  The  PCB  with  radio  elements  is  mounted  in-
side the device (Pic. 2). 

 

Picture 2  

4.2 

The PCB has 9 LEDs: 

  
-  

POWER 

– power supply status led 

FAILURE

 

– failures led 

INTERFACE

 

– SLC status led 

OUTPUT1,  OUTPUT2

 

–  to  display  respectively  the  status  of  control 

outputs OUT1, OUT2 

ZONE1 - ZONE4

 

– state display  

4.3 

There  is  a  tamper  switch  on  the  PCB  to  control  opening  of  the 

cover 

4.4 

The  PCB  has  screw  terminal  blocks,  the  function  of  terminal  de-

scribed in Table 1. 

 

Table 1 

Name 

Terminal function 

U1, GND 

Main external power supply connection 

U2, GND 

Connecting a backup 
external power supply 

+OUT1-  
+OUT2- 

Load connection 

Zone1 

– 

Zone4  

(AL1-AL4)

 

Connection  of  addressable  detectors  (devices)  for 
fire, security (including those powered by AL) 

А, В 

Connection to SLC information line from RPA 

+,  

– 

Connection to SLC power line from RPA 

4.5 

The  design  of  the  BPA  provides  the  posibility  to  install  and  use 

the BPA inside control cabinets. 

 

5  AL OPERATING MODES

 

 

BPA distinguishes the following AL states: 
- double-event smoke (Fire) 
- double event heat (Fire) 
- fire single event (Fire) 
- alarm 
- emergency 
- emergency with short circuit control (Open circuit). 

The AL state is determined by the parameters according to table 2. 

 

Table 2 

 

AL Type 

Alarm Loop resistance, kOhm 

0

–1.5 

from 1.5 

to 3.0

 

from 

3.0 to 

5.0

 

from  

5.0 

to 12.0

 

more 

12.0 

Fire smoke 
double-
event 

Fire 

Fire danger  Norm 

Fire 

Open 
circuit 

Fire heat 
double event

 

Short 
Cicuit

 

Norm 

Fire dan-
ger 

Fire 

Open 
circuit 

Fire single 
event 

Short 
Cicuit 

Fire 

Norm 

Fire 

Open 
circuit 

Alarm 

Alarm 

Alarm 

Norm 

Alarm 

Alarm 

Emergency 

Alarm 

Alarm 

Norm  

Alarm 

Alarm 

AL Type 

Alarm Loop resistance, kOhm 

0

–1.5 

from 1.5 

to 3.0

 

from 

3.0 to 

5.0

 

from  

5.0 

to 12.0

 

more 

12.0 

Emergency 
short circuit 
(Open circuit) 
control 

Short 
Cicuit 

Alarm 

Norm 

Alarm 

Open 

circuit 

 

6  INDICATION 

 

TEST

 led is generated when the power supply is turned on via any of 

the inputs U1 or U2, or by the CONTROL PANEL command, once the 
indication is turned on for 1 sec in turn on all leds of the BPA: POWER 
-  green,  FAILURE  -  yellow,  OUT1  -  red/yellow,  OUT2  -  red/  yellow, 
AL1 - AL4 - red/yellow, INTERFACE - green/red/yellow. 

 

Table 3

 - 

POWER

 

LED

 notifications and CONTROL PANEL  

Notification

 

LED POWER

 

CONTROL 

PANEL 

External power normal 

Green 

Failure  of  the  main  (or  back-
up) power supply (lower or no 
voltage at the inputs U1 or U2, 
GND)

 

x1 green flashes every 

sec.

 

 

Recovery  of  the  main  (or 
backup)  power  supply  (volt-
age  recovery  at  inputs  U1  or 
U2, GND)

 

Green 

Generic Failure (lack of power 
at  both  inputs  U1  and  U2, 
GND)

 

Off 

Recovery  from  a  general  Fail-
ure  (both  inputs  U1  and  U2, 
GND energized)

 

Steady on or flashing 
green x1/sec (accord-
ing to current power 
status)

 

«+» - notification is transmitted to Control Panel

  

«-» - notification is not transmitted to Control Panel

  

Table  4 

- Notifications to the 

FAILURE

 

LED

 and Control Panel 

Notification

 

LED FAILURE

 

CONTROL 

PANEL 

No Failures 

Off 

Failure (any) 

Yellow 

«+» - notification is transmitted to CONTROL PANEL

  

«-» - notification is not transmitted to CONTROL PANEL

 

Table  5

  -  Notifications  to 

LEDs  OUTPUT1,  OUTPUT2

  and  Control 

Panel 

Notification

 

LED  

OUTPUT 1, OUTPUT2 

CONTROL PANEL 

Output  on  (Integrity  contol) 
(straight polarity applied) 

Red 

Output  on  (no  integrity  con-
trol) (straight polarity voltage 
applied) 

Output  off  (Integrity  control) 
(reverse  polarity  voltage  ap-
plied) 

Off 

Output  off  (no  integrity  con-
trol)  (straight  polarity  de-
energized) 

Output 

interruption 

(with 

output  integrity  control  ena-
bled)  

x1 yellow flashes 

every 2 sec. 

Output  short  circuit  (with 
output  integrity  control  ena-
bled) 

x2 yellow flashes 

every 2 sec. 

Output  short  circuit  recov-
ered 

Solid  red  or  off. 
(

depending on the 

current  state  of 
the 

output 

whether  the  out-
put  is  enabled  or 
disabled

)  

Output open circuit recovery 

«+» - notification is transmitted to CONTROL PANEL, 

«-» - notification is not transmitted to CONTROL PANEL 

 

 