TD-1/07-008
63 / 83
Example
: To set Periodic Test Report Interval to 24 hours do 50 04
24
√
o
Central Monitorin Station(CMS) Periodic Report Time
Address = 50 05
< IP >
To see value
:
LED
50 05 (wait)
LCD
5-COMMUNICATOR
→
GENERAL SETTINGS
→
FIRST TEST AT (wait)
To change value
:
LED
50 05 R R √
LCD
5-COMMUNICATOR
→
GENERAL SETTINGS
→
FIRST TEST AT
TT TT HOUR(S) √
TT TT= Periodic test first time
Default Value
: 00:00
Example
: To set Periodic Test First Time to 16:00 do 50 05
1600
√
o
Redialing Pause
Address = 50 06
< IP >
To see value
:
LED
50 06 (wait)
LCD
5-COMMUNICATOR
→
GENERAL SETTINGS
→
REDIALING PAUSE(wait)
To change value
:
LED
50 06 R R √
LCD
5-COMMUNICATOR
→
GENERAL SETTINGS
→
REDIALING PAUSE
TT SECOND(S) √
TT = Redialing Pause Interval
Default Value
: 30 sec.
Example
: To set Redialing Pause Interval to 30 sec. do 50 06
30
√
o
Central Monitoring Station-1(CMS-1) Format
CMS-1 communication format is configured here. Meaning of data entered this address is in the following;
0 = Contact ID
1 = DTMF 4+2,4+1, 3+2, 3+1 50 07 address includes detailed settings)
Address: 50 07
< IP >
To see value
:
LED
50 07 (wait)
LCD
5-COMMUNICATOR
→
GENERAL SETTINGS
→
CMS 1 FORMAT (wait)
To change value
:
LED
50 07 F
√
LCD
5-COMMUNICATOR
→
GENERAL SETTINGS
→
CMS 1 FORMAT
[FORMAT] √
(Select using B(left) and C(right) buttons)
F = CMS format type, 0 ~ 1
Default Value
: 0, Contact ID
Example:
: To set CMS-1 contact as Contact ID do 50 07
0
√
o
Central Monitoring Station-2(CMS-2) Format
CMS-1 communication format is configured here. Meaning of data entered this address is in the following;
0 = Contact ID
1 = DTMF 4+2,4+1, 3+2, 3+1 (50 08 address includes detailed settings)
Address = 50 08 F< IP >