7 of 40
Copyright © D 363 -06/99
BOILER DESIGN (
Boil DSGN
) (
RESET
RATIO
&
CHARACTERIZED
HEATING
CURVE
)
The
Boil DSGN
temperature is the supply water temperature required to heat the boiler zones when the outdoor air is as cold as the
Outdoor Design temperature.
BOILER MINIMUM
(
Boil MIN
)
(
RESET
RATIO
&
CHARACTERIZED
HEATING
CURVE
)
The
Boil MIN
is the lowest water temperature that the control is allowed
to use as a
boiler target (Boil TRG)
temperature. During mild conditions,
if the 363 calculates a
Boil TRG
temperature that is below the
Boil MIN
setting, the
Boil TRG
temperature is adjusted to be at least the
Boil MIN
setting. During this condition, if the boiler is operating, the
Minimum
pointer turns on in the LCD while the
Boil TRG
or the
Boil SUP
temperature is viewed. If the installed boiler is designed for condensing
operation, set the
Boil MIN
adjustment to
OFF
.
BOILER MAXIMUM
(
Boil MAX
)
(
RESET
RATIO
&
CHARACTERIZED
HEATING
CURVE
)
The
Boil MAX
is the highest water temperature that the control is allowed
to use as a
Boil TRG
temperature. If the control does target
Boil MAX
,
and the
Boil SUP
temperature is near the Boil MAX temperature, the
Maximum pointer turns on in the LCD while the
Boil TRG
or the
Boil SUP
temperature is viewed. At no time does the control operate the boiler
above 248˚F (120˚C).
WARM WEATHER SHUT DOWN (
WWSD
) OCC & UNOCC
(
RESET
RATIO
&
CHARACTERIZED
HEATING
CURVE
)
When the outdoor air temperature rises above the
WWSD
setting, the 363 turns on the
WWSD
pointer in the display. When the control
is in Warm Weather Shut Down, the
Boiler Demand pointer is displayed if there is a demand. However, the control does not operate
the heating system to satisfy this demand. The control does respond to either a
DHW Demand or a Setpoint Demand and operates as
described in Section C.
BOILER SETBACK (
Boil SETB
) (
RESET
RATIO
)
The
Boil SETB
is the amount that the boiler supply water temperature is reduced when the 363 is placed into an
UnOccupied mode,
using an internal or an external setback as described in Section A. This setting is only available if the
Reset Ratio DIP switch is selected
and
Setback / None DIP switch is set to Setback.
BOILER INDOOR (
Boil INDR
)
(
CHARACTERIZED
HEATING
CURVE
)
The
Boil INDR
is the room temperature used in the original heat loss
calculations for the building. This setting establishes the beginning of the
Characterized Heating Curve for the boiler zones. This single setting
replaces the
Boil STRT
water temperature and
OUT STRT
air tempera-
ture settings used by the
Reset Ratio.
BOILER ROOM OCC & UNOCC (
Boil ROOM
)
(
CHARACTERIZED
HEATING
CURVE
)
The
Boil ROOM
is the desired room temperature for the boiler zones and
it provides a parallel shift of the
Characterized Heating Curve. The room
temperature desired by the occupants is often different from the de-
signed indoor temperature (Boil INDR). If the room temperature is not
correct, adjusting the
Boil ROOM
setting increases or decreases the
amount of heat available to the building. If the
Setback / None DIP switch
is set to
Setback, a
Boil ROOM
setting must be made for both the
Occupied and UnOccupied modes.
BOILER TARGET TEMPERATURE (
Boil TRG
)
(
RESET
RATIO
&
CHARACTERIZED
HEATING
CURVE
)
The
Boil TRG
temperature is determined from either the
Characterized
Heating Curve or the Reset Ratio settings and the outdoor air tempera-
ture. The control displays the temperature that it is currently trying to
maintain as the boiler supply temperature. If the control does not
presently have a requirement for heat, it displays “- - -” in the LCD.
Sequence, Section B
Boil Max + 1/2 Boiler Differential
Boil Max - 1/2 Boiler Differential
B
o
il
W
a
t
e
r Te
m
pe
rat
ure
Pointer On
Pointer On
Boil MAX
70
(21)
90
(32)
110
(43)
130
(54)
150
(66)
170
(77)
190
(88)
Outdoor Air Temperature
Supply W
ater
T
emperature
210
(99)
-20
(-29)
0
(-18)
20
(-7)
40
(5)
60
(16)
80
(27)
Boil DSGN
Boil MAX
Boil MIN
WWSD
Unocc
Boil IND
OUT DSGN
Boiler Characterized
Heating Curve
WWSD
Occ
50
(10)
Boil ROOM
Occ
Boil ROOM Un
Occ
Pointer On
Boil MIN
Boil Wat
er Te
mpe
ratu
re
Boil Min + 1/2 Boiler Differential
Boil Min - 1/2 Boiler Differential