Troubleshooting
Error Displayed
Description of Error
363
Error
Messages (3 of 4)
The control is no longer able to read the Boiler Supply sensor due to an open circuit. If the Boiler
Minimum setting is higher than 100˚F (38˚C) the control will close the boiler contact when there is a
call for heat in the system and the boiler temperature will be controlled by the boiler’s operating aquastat.
If the Boiler Minimum setting is lower than 100˚F (38˚C) the control will not operate the boiler contact.
Locate and repair the problem as described in the Data Brochure D070. To clear the error message
from the control after the sensor has been repaired, press either the Menu or Item button.
The control is no longer able to read the 10K 1 input because of a short circuit. The control will continue
to operate as if there was nothing connected to the 10K 1 input. To clear the error message from the
control after the sensor has been repaired, press either the Menu or Item button.
The control is no longer able to read the 10K 1 input because of an open circuit. The control will
continue to operate as if there was nothing connected to the 10K1 input. Locate and repair the problem
as described in the Data Brochure D070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button.
10K 1
≠
NONE
The control is no longer able to read the 10K 2 input because of a short circuit. If a DHW sensor was
being used, the control will no longer operate the DHW system. If a Storage sensor was being used,
the control will continue to operate as described in Section E3. Locate and repair the problem as
described in the Data Brochure D070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button.
The control is no longer able to read the 10K 2 input because of an open circuit. If a DHW sensor was
being used, the control will no longer operate the DHW system. If a Storage sensor was being used,
the control will continue to operate as described in Section E3. Locate and repair the problem as
described in the Data Brochure D070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button.
10K 2
≠
NONE
The air sensor in the RTU is being read as a short circuit. The RTU will continue operation using all
remaining sensors. If all of the sensors are unavailable, the control will continue to operate as if the
RTU was not connected to the control. This error message can be cleared once the sensor has been
repaired. To clear the error message from the control, press either the Menu or Item button.
The air sensor in the RTU is being read as an open circuit. The RTU will continue operation using all
remaining sensors. If all of the sensors are unavailable, the control will continue to operate as if the
RTU was not connected to the control. This error message can be cleared once the sensor has been
repaired. To clear the error message from the control, press either the Menu or Item button.
The Remote Sensor 1 attached to the RTU is being read as a short circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D 070.
To clear the error message from the control, press either the Menu or Item button.
REM 1
≠
NONE
The Remote Sensor 1 attached to the RTU is being read as an open circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D 070.
To clear the error message from the control, press either the Menu or Item button.
REM 1
≠
NONE
The Remote Sensor 2 attached to the RTU is being read as a short circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D 070.
To clear the error message from the control, press either the Menu or Item button.
REM 2
≠
NONE
The Remote Sensor 2 attached to the RTU is being read as an open circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D 070.
To clear the error message from the control, press either the Menu or Item button.
REM 2
≠
NONE
The Remote Sensor 3 attached to the RTU is being read as a short circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D 070.
To clear the error message from the control, press either the Menu or Item button.
REM 3
≠
NONE
Содержание Universal Reset Control 363
Страница 39: ...39 of 40 Copyright D 363 06 99 Notes...