24 of 40
Copyright © D 363 -06/99
Adjust Menus
•
D1
•
•
•
•
•
•
•
D1
D3
B2
B2
D3
•
•
•
D3
•
•
A
•
•
•
•
•
D1
•
•
A
363
Adjust
Menu (1 of 5)
Occ
D1
The desired room air temperature during an
Occupied period for mixing zone(s).
Note: There
is only a
±
3
°
F adjustment in the LTD access level.
DIP switch =
Characterized Heating Curve
No RTU connected
35 to 100˚F
(2 to 38˚C)
Default =
70
°
F (21
°
C)
35 to 100˚F
(2 to 38˚C)
Default =
65
°
F (18
°
C)
UnOcc
The desired room air temperature during an
UnOccupied period for mixing zone(s).
DIP switch =
Characterized Heating Curve
DIP switch =
Setback
No RTU connected
•
•
NONE, INDR
(Indoor),
MIX
(Mixing zone
control),
Boil
(Boiler
zone control),
SLAB
Default =
NONE
•
•
NONE, Boil
(Boiler
zone control)
Default =
NONE
The device that is to be connected to the 10K 1
input when an RTU is not connected.
DIP switch =
Characterized Heating Curve
No RTU connected
The device that is to be connected to the 10K 1
input when an RTU is connected.
DIP switch =
Characterized Heating Curve
RTU is connected
OFF, 35 to 120˚F
(OFF, 2 to 49˚C)
Default =
70
°
F (21
°
C)
40 to 150˚F
(4 to 66˚C)
Default =
90
°
F (32
°
C)
The minimum temperature at the slab sensor
DIP switch =
Characterized Heating Curve
No RTU connected
10K 1 = SLAB
OFF, 0:20 to 8:00 Hr.
Default =
OFF
The maximum temperature at the slab sensor.
DIP switch =
Characterized Heating Curve
No RTU connected
10K 1 = SLAB
The amount of morning boost.
DIP switch =
Characterized Heating Curve
DIP switch =
Setback
No RTU connected
10K 1
≠
MIX
The amount the mixing supply water temperature
will be reduced when the control is in the
UnOccupied mode.
DIP switch =
Reset Ratio
DIP switch =
Setback
0 to 50˚F
(0 to 28˚C)
Default =
9
°
F (5
°
C)
The type of terminal units that are being used for
the mixing side of the system.
DIP switch =
Characterized Heating Curve
HRF1
(Heavy),
HRF2
(Light), (Fan-)
COIL
,
CONV
(ector),
RAD
(iator),
BASE
(board)
Default =
HRF1
The minimum supply water temperature for the
mixing system.
DIP switch =
Characterized Heating Curve
OFF, 35 to 150˚F
(OFF, 2 to 66˚C)
Default =
OFF
Actual
Setting
Section
LT
D
INST
ADV
Range
Access
Level
Description
Item Field
USER