General Safety Information
(Continued)

Install a good grounding bond
between disconnect box, control
box, and piping system. Tape cable
closely to discharge pipe at intervals
of ten feet or less. 

13. NEVER leave control box, fused

disconnect switch, or pressure
control switch covers open (either
partially or completely) when not
being worked on by a competent
electrician or repairman. 

14. Always use caution when operating

electrical controls in damp areas. If
possible, avoid all contact with
electrical equipment during thunder
storms or extreme damp conditions.

15. Install all electrical equipment in

protected area to prevent
mechanical damage which could
produce serious electrical shock
and/or equipment failure.

16. Pump is designed  to pump water

only.

Fire or explosion
hazard! Do not

pump flammable liquids such as gasoline,
fuel oil, kerosene, etc., with this pump.
Pump water only with this pump.

17.

DO NOT

handle pump with wet

hands or when standing in water as
fatal electrical shock could occur.
Disconnect main power supply
before handling pump for any
reason.

Preinstallation

Risk of electrical
shock. Connect

motor ground wire to grounded metal
raceway system or power system ground.
Bond (ground) pump and all metal
components to building ground system in
accordance with National Electrical Code
(NEC) requirements.

Most submersible pump problems are
electrical. To reduce problems, have all
electrical hook-up work or service work
done by a qualified electrician or
serviceman only.

To save added expense and extra trips,
complete as many as possible of the
following procedures before going to
the installation site.

1. Examine pump for damage. 

Make

sure

check valve works properly. For

3-wire units, motor and control box
horsepower and voltage must match

exactly

.

NOTE: 

All units are supplied with extra

label for above ground pump
identification. Place label in
conspicuous location (on control box,
etc.) for future reference.

2. Check electrical supply for correct

fusing, wire size, transformer size,
and adequate grounding.

3. Follow wiring directions in the

control box and make momentary
tests to see that motor runs. If test is
satisfactory, proceed to Step 4 (cable
splice).

4. First check cable size against

Submersible Wire Size Charts
(below). 

Use extreme care

; this is a

very important step. If required
length falls between two wire sizes,
use the larger wire size (smaller
number) of the two. 

IMPORTANT: 

Use of wire sizes smaller

than those specified in charts will cause
low starting voltage, may cause early
pump failure and will void warranty.
Larger wire sizes may be used for better
economy of operation. Be sure voltage
at pressure switch or fuse box is
between the following limits:

• 115 Volts Rated – Between 105

and 125 Volts

• 230 Volts Rated – Between 210

and 250 Volts

5. Use butt connectors and plastic

sleeves included in the splice kit to
make underwater cable splices. 

IMPORTANT: 

Do not handle motor or

pump by power cable or motor leads!
Damage to cable will result! 

IMPORTANT: 

Follow instructions

carefully to make a watertight splice! A
leak in the splice can result in:

a. Damage to motor winding.

b. Electrolytic deterioration of the

joint, resulting in an open circuit.

4

Teel Operating Instructions and Parts Manual

Teel Deep Well Submersible Pumps

®

E

N
G

L

I

S

H

Wire Size Chart

1/3

115

130

210

340

540

840

1300

1/3

230

550

880

1390

2190

3400

5250

1/2

115

100

160

250

390

620

960

1/2

230

400

650

1020

1610

2510

3880

3/4

230

300

480

760

1200

1870

2890

1

230

250

480

630

990

1540

2380

1

1

2

230

190

310

480

770

1200

1870

Single Phase Submersible Pump Wire Size Chart

Pump to Power Source AWG Wire Size – Maximum Distance in Feet

HP

Volts

#14

#12

#10

#8

#6

#4

4P847A thru 4P851A, 4P852 thru 4P865, 4RH01 thru 4RH06, 

4RG76 thru 4RG84, 4RG94 thru 4RG97 and 4RG99

Содержание 4P847A

Страница 1: ...94 thru 4RG97 and 4RG99 are thermoplastic discharge Pumps 4P847A thru 4P851A and 4P852 thru 4P856 are cast iron discharge E N G L I S H Printed in U S A 09319 0798 116 E3 4P847A 1 3 10 3 4P840 5 115 6...

Страница 2: ...RK69 4P854 40 9 5 7 5 4 3 50 7 2 3 8 60 3 7 4P855 20 15 6 14 8 14 0 13 0 11 8 10 2 8 2 2 1 4P837 4P856 30 14 6 13 7 12 8 11 6 10 3 8 3 6 0 4RK69 4P857 40 13 6 12 6 11 5 10 1 8 6 6 1 2 8 4P858 50 12 5...

Страница 3: ...on 230 volt installations to prevent motor damage 7 Be sure to provide adequate ventilation for pressure switch and control box to prevent moisture damage to components 8 Periodically check well seal...

Страница 4: ...its are supplied with extra label for above ground pump identification Place label in conspicuous location on control box etc for future reference 2 Check electrical supply for correct fusing wire siz...

Страница 5: ...time selector switch is changed 2 Clip one ohmmeter lead to bare cable end 3 Clip the other lead to edge of steel tank in which pump and cable are submerged If pump is already in the well clip lead t...

Страница 6: ...2 If replacing a jet pump expect to set the submersible deeper in the well because the submersible will pump more water than the jet pump Be sure the new submersible is set at least ten feet above the...

Страница 7: ...astic pipe adapter in the pump discharge tapping using pipe joint compound or teflon tape Models 4P847A thru 4P851A 4P852 thru 4P865 4RH01 thru 4RH06 4RG76 thru 4RG84 4RG94 thru 4RG97 and 4RG99 7 Teel...

Страница 8: ...he pipe f If you have not already done so splice the electrical cable to the motor wire leads according to the directions under Sections 5 6 and 7 in Preinstallation g Unroll electrical cable alongsid...

Страница 9: ...the pipe to eliminate rubbing against well casing Leave four to five feet of slack at the upper end to allow for plastic pipe stretch 5 Tie safety rope to top of pump in holes provided Tape end of ro...

Страница 10: ...Use ONLY submersible cable to pump 7 Two wire pump hookup Wire the fused electrical disconnect box to water system pressure switch and from pressure switch to motor See Figures 15 and 16A Power cable...

Страница 11: ...230 1 3 6 0 7 4 26 1 32 32 1 39 4 4 6 4 6 0 15 5 4P853 4P849A 4RG99 230 1 2 4 2 5 2 16 7 20 5 20 9 25 7 6 0 6 0 0 15 7 4P856 4RG76 4P851A 4RH01 230 3 4 3 0 3 6 11 0 13 4 14 0 17 0 8 0 8 0 0 20 9 4P85...

Страница 12: ...itively identified proceed as follows 1 Disconnect all three drop cables from the control box For temporary identification tie a numbered tag to each cable 1 2 3 2 Using an ohmmeter check the resistan...

Страница 13: ...l rights which vary from jurisdiction to jurisdiction LIMITATION OF LIABILITY To the extent allowable under applicable law Dayton s liability for consequential and incidental damages is expressly disc...

Страница 14: ...L10P4DS WG 4P860 1D125 L10P4DS WG 4P861 1D133 4P845 L10P4ES WG 4P862 1D134 4P846 L10P4FS WG 4P863 1D133 4P845 L20P4ES WG 4P864 1D126 L20P4ES WG 4P865 1D134 4P846 L20P4FS WG 4RG99 1D131 4P843 L5P4CJL W...

Страница 15: ...one minute intervals no water 2 Gas or air in well water 2 Connect hose to service valve Run water thru hose submerged in water in clear jar Observe for air bubbles from hose outlet If tank is standar...

Страница 16: ...t circuit breakers may trip or fuses blow Ventilate or shade box Move away from heat source 5 If problem has not been found check motor and control box Use test procedures that follow Ground Insulatio...

Отзывы: