teel 4P847A Скачать руководство пользователя страница 12

Installation (Continued)

(drawdown) than the same size
standard tank, a physically smaller
tank can do the same job. The
drawdown (water delivered
between pump cycles) is the
common factor when comparing
precharged to standard tanks; total
volume of each tank is not
comparable. 

10.

A Waterlogged Tank: 

The purpose

of the pressure tank is to allow a
certain amount of water to be
drawn before the pressure drops
enough to cause the pump to start.
Without a pressure tank, the pump
is controlled only by the pressure
switch. Just one use of the water tap
would cause the pump to rapidly
start and stop numerous times,
resulting in premature failure of the
pump motor. The same condition
occurs when a tank is waterlogged.
The air supply in the tank is
gradually absorbed by the water,
leaving little or no water available
for drawdown. The pump must cycle
with increasing frequency to deliver

the same amount of water.
Waterlogging can be caused by
either failure of the air volume
control on a standard tank system or
rupture of the bladder in a
precharged tank system.

NOTE: 

Should you be replacing your

pump, be sure that the tank system is in
good operating condition, as a
waterlogged tank may have caused
your pump failure.

Maintenance

SERVICING SUBMERSIBLE MOTOR
AND CONTROLS

The following is included to assist in
motor installation and servicing. These
procedures are limited to the motor
and control system; they do not include
pump requirements.

CABLE IDENTIFICATION WHEN
COLOR CODE IS LOST (3-WIRE ONLY)

If the colors on the individual drop
cables cannot be determined and the
leads cannot be positively identified,
proceed as follows:

1. Disconnect all three drop cables

from the control box. For temporary

identification, tie a numbered tag to
each cable (1, 2, 3).

2. Using an ohmmeter, check the

resistance between cables as follows:

Unknown Value:

Cable 1 to Cable 2

Cable 1 to Cable 3

Cable 2 to Cable 3

Known Value:

Lowest - Black to Yellow

Intermediate - Red to Yellow

Highest - Black to Red

NOTE: 

The “yellow” cable is that giving

lowest and intermediate readings and
the “red” cable gives highest and
intermediate readings. 

Example:

1 to 2 gives 7 Ohms (highest reading)

1 to 3 gives 5 Ohms (intermediate
reading)

2 to 3 gives 2 Ohms (lowest reading)

Cable 3 gave both intermediate and
lowest reading.

12

Teel Operating Instructions and Parts Manual

Teel Deep Well Submersible Pumps

®

E

N
G

L

I

S

H

Insulation Resistance

New Motor (without drop cable)

20.0

20,000,000 or more

Used Motor which can be reinstalled in a well

10.0

10,000,000 or more

Motor in Well (Readings Are for Drop Cable Plus Motor)

New motor in the well

2.0

2,000,000 or more

Motor in reasonably good condition

0.5-2.0

500,000 to 2,000,000

Motor may have damaged leads or have been damaged by lightning.
Does not need to be pulled

0.02-0.5

20,000 to 500,000

Motor definitely damaged or with damaged cable.
Should pull pump and repair or replace motor or cable.
Motor will probably not continue to operate for long.

0.01-0.02

10,000 to 20,000

Motor has failed or cable insulation has been completely destroyed.
Pull pump and repair or replace motor and/or cable.
Motor will not run in this condition.

0-0.1

< 10,000

Insulation Resistance in Ohms and Megohms for all motors

values between leads and ground

Condition of Motor and Leads

Megohms

Ohms

4P847A thru 4P851A, 4P852 thru 4P865, 4RH01 thru 4RH06, 

4RG76 thru 4RG84, 4RG94 thru 4RG97 and 4RG99

Содержание 4P847A

Страница 1: ...94 thru 4RG97 and 4RG99 are thermoplastic discharge Pumps 4P847A thru 4P851A and 4P852 thru 4P856 are cast iron discharge E N G L I S H Printed in U S A 09319 0798 116 E3 4P847A 1 3 10 3 4P840 5 115 6...

Страница 2: ...RK69 4P854 40 9 5 7 5 4 3 50 7 2 3 8 60 3 7 4P855 20 15 6 14 8 14 0 13 0 11 8 10 2 8 2 2 1 4P837 4P856 30 14 6 13 7 12 8 11 6 10 3 8 3 6 0 4RK69 4P857 40 13 6 12 6 11 5 10 1 8 6 6 1 2 8 4P858 50 12 5...

Страница 3: ...on 230 volt installations to prevent motor damage 7 Be sure to provide adequate ventilation for pressure switch and control box to prevent moisture damage to components 8 Periodically check well seal...

Страница 4: ...its are supplied with extra label for above ground pump identification Place label in conspicuous location on control box etc for future reference 2 Check electrical supply for correct fusing wire siz...

Страница 5: ...time selector switch is changed 2 Clip one ohmmeter lead to bare cable end 3 Clip the other lead to edge of steel tank in which pump and cable are submerged If pump is already in the well clip lead t...

Страница 6: ...2 If replacing a jet pump expect to set the submersible deeper in the well because the submersible will pump more water than the jet pump Be sure the new submersible is set at least ten feet above the...

Страница 7: ...astic pipe adapter in the pump discharge tapping using pipe joint compound or teflon tape Models 4P847A thru 4P851A 4P852 thru 4P865 4RH01 thru 4RH06 4RG76 thru 4RG84 4RG94 thru 4RG97 and 4RG99 7 Teel...

Страница 8: ...he pipe f If you have not already done so splice the electrical cable to the motor wire leads according to the directions under Sections 5 6 and 7 in Preinstallation g Unroll electrical cable alongsid...

Страница 9: ...the pipe to eliminate rubbing against well casing Leave four to five feet of slack at the upper end to allow for plastic pipe stretch 5 Tie safety rope to top of pump in holes provided Tape end of ro...

Страница 10: ...Use ONLY submersible cable to pump 7 Two wire pump hookup Wire the fused electrical disconnect box to water system pressure switch and from pressure switch to motor See Figures 15 and 16A Power cable...

Страница 11: ...230 1 3 6 0 7 4 26 1 32 32 1 39 4 4 6 4 6 0 15 5 4P853 4P849A 4RG99 230 1 2 4 2 5 2 16 7 20 5 20 9 25 7 6 0 6 0 0 15 7 4P856 4RG76 4P851A 4RH01 230 3 4 3 0 3 6 11 0 13 4 14 0 17 0 8 0 8 0 0 20 9 4P85...

Страница 12: ...itively identified proceed as follows 1 Disconnect all three drop cables from the control box For temporary identification tie a numbered tag to each cable 1 2 3 2 Using an ohmmeter check the resistan...

Страница 13: ...l rights which vary from jurisdiction to jurisdiction LIMITATION OF LIABILITY To the extent allowable under applicable law Dayton s liability for consequential and incidental damages is expressly disc...

Страница 14: ...L10P4DS WG 4P860 1D125 L10P4DS WG 4P861 1D133 4P845 L10P4ES WG 4P862 1D134 4P846 L10P4FS WG 4P863 1D133 4P845 L20P4ES WG 4P864 1D126 L20P4ES WG 4P865 1D134 4P846 L20P4FS WG 4RG99 1D131 4P843 L5P4CJL W...

Страница 15: ...one minute intervals no water 2 Gas or air in well water 2 Connect hose to service valve Run water thru hose submerged in water in clear jar Observe for air bubbles from hose outlet If tank is standar...

Страница 16: ...t circuit breakers may trip or fuses blow Ventilate or shade box Move away from heat source 5 If problem has not been found check motor and control box Use test procedures that follow Ground Insulatio...

Отзывы: