![Tecumseh AEA4440YXA Скачать руководство пользователя страница 75](http://html1.mh-extra.com/html/tecumseh/aea4440yxa/aea4440yxa_service-data-book_1073114075.webp)
A LOOK AT SERVICE SAFETY
Servicing
75
Step 1: Before Continuing with
Troubleshooting...
WARNING!
All electric power should be disconnected and you
should have already made sure that the compressor does not
have a ground fault (see “Checking for a Ground Fault” on
pages 47-48).
You should have also checked the windings for
continuity and proper resistance (see “Checking for Continuity
and Proper Resistance” on pages 48-49), made sure the system is
getting proper voltage, and that the control, thermostat, and con-
tactor are working properly.
NOTE: The compressor housing MUST be at 130°F or less for
the following checks. This temperature can be read by Tempstik
or is that temperature which will allow the hand to remain in
contact with the compressor housing without discomfort.
Step 2: Check Internal Thermal
Protector
Check for continuity across the thermal protector. If there is no
continuity, then the internal thermal protector may be tripped.
Wait for it to cool off and close. This may take more than an
hour. Check continuity again. If there is no continuity, replace
the compressor.
Step 3: Check Run Capacitor
CAUTION:
Using a 20,000 ohm resistor, discharge the capaci-
tor before removing it from the system to avoid damage to mea-
suring devices and risk of electric shock.
Disconnect the run
capacitor from the system. Use a capacitance meter to check
capacitor. Capacitance should be ±10% of the marked capacitor
value.
As an alternative, check the run capacitor by measuring continu-
ity across the capacitor terminals:
a. Rx1 scale: If there is continuity, then the run capacitor is
shorted and needs to be replaced.
b. Rx100,000 scale: If there is no needle deflection on an
analog meter or if a digital meter indicates infinite resis-
tance, then the run capacitor is open and needs to be
replaced.
Possible reasons that a run capacitor is not working properly
include:
•
Use of incorrect run capacitor. Replace with proper run
capacitor.
•
Line voltage is too high (greater than 110% of rated volt-
age).
Step 4: Reconnect Run Capacitor
Reconnect the run capacitor into circuit at terminals S and R.
(Marked terminal should go to R.)
Step 5: Continue Troubleshooting
If all above tests prove satisfactory and unit still fails to operate
properly, check for adequate compressor pumping as outlined in
the procedure on page 83.
Содержание AEA4440YXA
Страница 1: ...Service Data Book Sold By American Refrigeration Supplies Inc Wholesale Distribution North America...
Страница 84: ...84 Chapter 4...
Страница 120: ...120 Chapter 6...
Страница 125: ...A LOOK AT SERVICE SAFETY Appendix 125 Figure A 2 Internal view of typical air conditioning compressor...
Страница 132: ...132 Appendix...