Chapter 3
II.
PSC Motor Starting
Tecumseh Products Company has pioneered in
encouraging the development of Permanent Split
Capacitor compressor motors. This type of motor
eliminates the need for potentially troublesome and
costly extra electrical components (start capacitors
and potential motor starting relays). (See Figure
Figure 3-7.)
To fully realize the capabilities of this simplified type
of compressor motor, it is necessary to understand
its starting and operating characteristics and the
field conditions which can affect it.
The following conditions affect PSC motor starting:
•
Low voltage: Reduces motor starting and run-
ning torque. A 10% voltage drop reduces a
motor’s starting ability by 19%. Low voltage
can cause no start, hard start, light flicker, and
TV screen flip flop.
Minimum starting voltage for the compressor
when it is attempting to start (locked rotor) is:
•
Unequalized system pressure: Head and suc-
tion pressures must be equal and not more than
170 psig. Refrigeration metering device (cap
tube or TX valve) should equalize system pres-
sures within 3 minutes. Unequal system pres-
sure may be caused by excessive refrigerant
charge, short cycling thermostat, or system
restriction.
•
Circuit breaker or fuse trips: Branch circuit
fuses or circuit breakers sized too small will
cause nuisance tripping (see “Fuse and Circuit
Breaker Sizing” on page 36). If the fuse or cir-
cuit breaker trips, see “Identifying Compressor
Electrical Problems” on page 47 for electrical
troubleshooting techniques.
•
Electrical components: A failed run capacitor
will not allow the compressor to start, and it
will trip the thermal protector. See “Identifying
Compressor Electrical Problems” on page 47
for electrical troubleshooting techniques.
Figure 3-7.
Circuit diagram for PSC compressors.
Compressor -
Unit Ground
External or Internal
Thermal Protector
Run Capacitor
Line 1
Line 2
Ground
Star
t
Winding
Main
Winding
Control
C
S
R
Table 3-7: Minimum Starting Voltage
Serial Label Voltage
Min. Voltage for Start
115
103
208
188
230
207
230/208
198
265
239