64
Chapter 4
Step 1: Before Continuing with
Troubleshooting...
WARNING!
All electric power should be disconnected and
you should have already made sure that the compressor does
not have a ground fault (see “Checking for a Ground Fault”
on pages 47-48).
You should have also checked the windings
for continuity and proper resistance (see “Checking for Conti-
nuity and Proper Resistance” on pages 48-49), made sure the
system is getting proper voltage, and that the control, thermo-
stat, and contactor are working properly.
Step 2: Check Potential Relay
Before checking the relay, be sure it is mounted at the proper
position. (See pages 28-32.) Check the potential relay by mea-
suring continuity between:
a. Relay terminals 5 and 2. If there is no continuity, replace
the relay.
b. Relay terminals 2 and 1. If there is no continuity, then
the contacts are open. Replace the relay.
Possible reasons that a relay is not working properly include:
•
Use of incorrect relay. Replace with correct relay.
•
Line voltage is too high or low (greater than 110% or
less than 90% of rated voltage).
•
Excessive short cycling. Short cycling can be caused by
problems with the compressor’s thermal protector or sys-
tem components such as the thermostat, control, contac-
tor, or high or low pressure cut-out. For more information
on troubleshooting the thermal protector, see Step 5. For
troubleshooting the system components, refer to the OEM
service information.
•
Vibration due to loose relay mounting. Tighten relay
mounting.
•
Use of incorrect run capacitor. Replace with proper run
capacitor.
Step 3: Check Run Capacitor
CAUTION:
Using a 20,000 ohm resistor, discharge the
capacitor before removing it from the system to avoid damage
to measuring devices and risk of electric shock.
Disconnect
the run capacitor from the system. Use a capacitance meter to
check capacitor. Capacitance should be ±10% of the marked
capacitor value.
As an alternative, check the run capacitor by measuring conti-
nuity across the capacitor terminals:
a. Rx1 scale: If there is continuity, then the run capacitor is
shorted and needs to be replaced.