A LOOK AT SERVICE SAFETY
Servicing
49
Table 4-1: Checking for Proper Continuity and Resistance
Single Phase Compressors
3-Phase Compressors
Step 1: Allow
Thermal
Protector
to Reset
When servicing single compressors with
internal thermal protectors, be sure to
allow time for the thermal protector to
reset prior to starting these electrical
wiring checks. For some compressors,
the internal thermal protector may take
as long as an hour to reset.
When servicing 3-phase compressors
with internal thermal protectors, be sure
to allow time for the thermal protector to
reset prior to starting these electrical
wiring checks. For some compressors,
the internal thermal protector may take
as long as an hour to reset.
Step 2: Check
Continuity
Check the start winding by measuring
continuity between terminal pins C and
S. (See “Identification of Hermetic
Terminal” on page 34). If there is no
continuity, replace the compressor. See
“System Cleanup and Compressor
Replacement After Compressor Failure”
on pages 104-107.
Check the run winding by measuring
continuity between terminal pins C and
R. If there is no continuity, replace the
compressor.
Check the windings by measuring
continuity between each pair of terminal
pins: Leg
1
-Leg
2
, Leg
2
-Leg
3
, and Leg
1
-
Leg
3.
If there is no continuity, replace the
compressor. See “System Cleanup and
Compressor Replacement After
Compressor Failure” on pages 104-107.
Step 3: Measure
the
Resistance
Measure the resistance (ohms) between
each pair of terminal pins: C and S, C
and R, and S and R. Add the resistance
between C and S to the resistance
between C and R. This sum should
equal the resistance found between S
and R. A small deviation in this
comparison is acceptable. Proper
resistance may also be confirmed by
comparing measured resistance to the
resistance specifications for the specific
compressor model. Call 1-800-211-3427
to request resistance specifications.
If the resistance is not correct, replace
the compressor. See “System Cleanup
and Compressor Replacement After
Compressor Failure” on pages 104-107.
If the resistance is correct, leave the
leads off and follow the instructions in
the next section to check other
compressor electrical components.
Measure the resistance (ohms) between
each pair of terminal pins: Leg
1
-Leg
2
,
Leg
2
-Leg
3
, and Leg
1
-Leg
3
. The
resistance found between each of the
pairs Leg
1
-Leg
2
, Leg
2
-Leg
3
, and Leg
1
-
Leg
3
should all be greater than zero and
within about 10% of one another. Proper
resistance may also be confirmed by
comparing measured resistance to the
resistance specifications for the specific
compressor model. Call 1-800-211-3427
to request resistance specifications.
If the resistance of Leg
1
-Leg
2
, Leg
2
-
Leg
3
, and Leg
1
-Leg
3
does not
approximate the resistance of each
other, then there is a short circuit.
Replace the compressor. See “System
Cleanup and Compressor Replacement
After Compressor Failure” on pages
104-107.
If the resistance is correct and the 3-
phase compressor has external
components, leave the leads off and
follow the instructions in Section D on
page 81 to check other compressor
electrical components. If the 3-phase
compressor does not have any external
components, the compressor must be
replaced.