A LOOK AT SERVICE SAFETY
Compressor Motor and Component Information
21
B. “AN” Wiring on Typical 230/200 Volt
System with Electronic Protection
Module
The Model AN compressors are available with an
advanced solid state protection system. Sensors are
provided in each leg of the compressor motor wind-
ings to guard against overloading and single phasing.
Additionally, a sensor is in the internal discharge line
to detect excessive discharge gas temperatures.
Notes on the compressor electronic protection sys-
tem:
•
The compressor will not run if a jumper is
placed across terminals S and S
1
.
•
Terminals M
1
and M
2
are a normally closed
switch actuated by the motor sensor circuit.
Switch contacts are rated at 2.5 amps at 265
volts maximum.
•
Do not expose the protection module to pro-
longed ambient temperature higher then
150°F.
•
Module has built-in time delay. Power inter-
ruption or sensor trip will cause 3 to 5 minute
delay before restart.
•
If sensor circuit trips and motor feels cool,
check the return gas temperature. It should not
be more than 65°F entering the compressor.