TROUBLESHOOTING 

 

CAUSES AND SOLUTIONS

 

The  control  unit  does  not  switch  on  and  the 
supply to terminals 40-42 is correct. 

Check  that:  the  connector  is  firmly  inserted  in  its  place,  the 
connection  wires  are  tight  and  that  there  are  no  obvious  signs  of 
burns  on  the  connectors.  Turn  off  the  power  supply  and  carry  out 
the above instructions, restore the voltage. 

CH4 is in FAULT for FOC  
(only the 3 Pt100 sensors are connected) 

Programming error of the CH4/YES control unit. 

Check and repeat 

the programming on page 13-14 select CH4 /NO.

 

One  of  the  three/four  channels  is  in  FAULT  for 
FOC/FCC 

Check the Pt100 probe connections, check the indications given in 
the  paragraphs: 

transfer  of  measurement  signals  and  temperature 

probe diagnostics on page 15-16.

 

When turned on, the indication "ECH" appears 

A  strong  disturbance  has  damaged  the  memory  data.  See  the 
paragraph for programmed data diagnostics on page 15.  

All the Pt100 sensors are in FCC. 

Incorrect  sensor  connection,  the  terminal  block  has  been  inserted 
upside down. 

Check the connections and the terminal board.

 

The  temperature  shown  by  one  or  more 
channels is wrong. 

Contact the 

TECSYSTEM

 Technical Department. 

Sudden trip of the main switch. The temperature 
is  on  standard  levels.  Just  one  channel  has 
caused the trip. 

Check  the  temperatures  recorded  in  T-MAX,  check  the  indications 
given  in  the  paragraphs: 

transfer  of  measurement  signals  and 

temperature probe diagnostics pag.15. Activate the FCD function.

 

FCD warning  

See the FCD function on page 27. 

The control unit signals BH ERR RS1  

 
Check the connection between the control unit and the Control box 
BAR B1, TRBH SYSTEM manual. 
 

The control unit signals BH ERR RS2  

 
Check the connection between the Control box BAR B1 and the 
Control box B2, TRBH SYSTEM manual. 
 

The control unit signals BH ERR B1 

 
Check the operating status and the connection of the motors 
installed on the B1 bar, TRBH SYSTEM manual. 
 

The control unit signals BH ERR B2 

 
Check  the  operating  status  and  connection  of  the  motors  installed 
on the B2 bar, TRBH SYSTEM manual. 
 

The control unit signals BH ERR B1-2 

 
Check  the  operating  status  and  connection  of  the  motors  installed 
on the B1-2 bars, TRBH SYSTEM manual. 
 

Contact the 

TECSYSTEM 

Technical Department if the problem persists. 

Содержание NT935BH-D

Страница 1: ...s with ISO9001 certified quality system http www tecsystem it R 1 0 10 06 20 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT935...

Страница 2: ...NG NOTES 15 TEMPERATURE SENSORS MEASUREMENT SIGNAL TRANSFER TEMPERATURE SENSOR DIAGNOSTICS 16 VOTING FUNCTION PROGRAMMED DATA DIAGNOSTICS TEMPERATURE DIAGNOSTICS COOLING FAN CONTROL 17 FANS DIAGNOSTIC...

Страница 3: ...TA FRAME 19 DATA PACKET FUNCTION CODE CODE 3 10 CODE 16 10 NOTES FOR REMOTE PROGRAMMING ERROR CODES 20 UNACCEPTABLE DATA ILLEGAL DATA POLLING FREQUENCY MODBUS MAPPING TABLE 21 9 FAILSAFE FUNCTION 26 1...

Страница 4: ...e control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit use a dry cloth to dust it without any solvent or detergents...

Страница 5: ...ing torque 0 5Nm 1 Terminal 12 poles pitch 3 81 sensors Pt100 Code 2PL0420 Screw tightening torque 0 25Nm 1 Terminal 4 pitch poles 3 81 for BLDC output Code 2PL0368 Screws tightening torque 0 25Nm 1 T...

Страница 6: ...ation management relay SPST FAN 2 Output relays with 10A 250Vac res COS 1 contacts TRBH output FAN1 control bars B1 B2 RS485 output Modbus RTU DIMENSIONS 100x100 mm din43700 prof 131mm including termi...

Страница 7: ...te of FAN1 and FAN2 Temperature control from 0 C to 240 C 2 alarm thresholds for channels 1 2 3 2 alarm channels for channel 4 1 activation threshold FAN1 ON TRBH 2 ON OFF thresholds FAN 2 ventilation...

Страница 8: ...ication 5 FAULT red LED 16 3 digit channel display 6 FAN 1 TRBH signalling yellow 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode selection key 19 Au...

Страница 9: ...epairs 4 Pt Err This message appears when it is detected that one or more PT100 sensors are not working correctly FOC FCC and FCD indications in the temperature sensor diagnostics paragraph on page 16...

Страница 10: ...ks 1 Control unit 2 Panel hole dimensions 0 8 mm tolerance 3 Identification label 1 Control unit 3 Locking screws 2 Fixing blocks 4 Cross head screwdriver 1X100mm ASSEMBLY 1 1MN0007 REV 0 2 3 1 2 3 4...

Страница 11: ...sensors white red red 4 Relay FAN2 2 Power supply 85 260Vac cc 50 60Hz 5 FAN1 BLDC output Control Box connection 3 Relays ALARM TRIP FAULT 6 RS485 output Modbus RTU Pt100 CONNECTION EXAMPLE Note imag...

Страница 12: ...one of the methods described below does not monitor heat also the relay will all be banned The fault contact switches and the fault LED flashes Vis Programming display PRG programming Relay test The...

Страница 13: ...H4 is enabled with NO the CH4 is disabled 10 The ALARM threshold for CH4 is displayed the Alarm led flashes If CH4 NO jump to step 16 Default NO 11 Set the desired threshold Default 120 C 12 The TRIP...

Страница 14: ...FE info on page 26 31 Select YES or NO Default NO 32 FLS TRIP is displayed Blinking TRIP LED 33 Select YES or NO Default NO 34 FLS FAULT is displayed Blinking FAULT LED 35 Select YES or NO Default YES...

Страница 15: ...rcuit couples capacitively with the conductors in particular with unscreened cables The effect of this coupling creates a signal that overlaps the signal transmitted by the nearby conductors causing i...

Страница 16: ...se alarms generated by installation errors By activating the VOTING YES function the control unit compares the temperature values recorded on the monitored CH1 CH2 CH3 channels and enables the switchi...

Страница 17: ...1 C at 230 C range 0 C to 240 C or 1 C 190 C range 40 C to 200 C NOTE fan speed regulation rpm with selections different from B1 3 and B2 3 is managed with reference HOT channel the hottest channel of...

Страница 18: ...unication is temporarily deactivated DATA TRANSMISSION ON MODBUS NETWORK The MODBUS INSIDE internal module makes it possible to connect the NT935BH D control unit to an RS485 network with Modbus RTU p...

Страница 19: ...ng 00000000 xxxxxxx0 x n d Also in the remote programming phase via ModBus it must be considered that the Alarm thresholds must be lower than the Trip thresholds and that the Fan on thresholds must be...

Страница 20: ...Status Value FCD max see table SYSTEM Setting and Status Value Voting max see table SYSTEM Setting and Status Note If the value of Voting is higher than the max value expected for the model in questi...

Страница 21: ...channels 2 ASCII R 6 Options see note Options see note R 7 00 Wrong datum received R see tab 8 00 Info various causes R see tab 9 00 Controls W see tab SYSTEM Setting and Status Address LO 10 Data HI...

Страница 22: ...s 1 4 Address LO 10 Data HI Data LO Notes 1 Notes 2 R read W write RW read write 25 2 compl sign 2 compl Ch1 temper 10 C 240 C 48 C 200 C R 26 2 compl sign 2 compl Ch1 max temperat 0 C 240 C 0 C 200 C...

Страница 23: ...C 240 C 1 C 200 C AL RW 40 2 compl sign 2 compl Ch4 temper trip set point 1 C 240 C 1 C 200 C TRP RW 41 00 00 R 42 00 00 R 43 00 00 R 44 00 00 R 45 00 TRBH _1 speed M1 M6 motors R 46 00 TRBH _1 motors...

Страница 24: ...0 Ch4 Setting See Notes CHx RW 61 00 00 R 62 00 00 R 63 00 00 R 64 00 00 R CHANNELS 1 4 Status Address LO 10 Data HI Data LO Notes 1 Notes 2 R read W write RW read write 65 Ch1 story Ch1 status See No...

Страница 25: ...n STORY BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 TRIP ALARM FOC FCC RELAY STATUS coil energising status BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 Relay FAULT 1 ON TRIP Relay 1 ON ALARM Re...

Страница 26: ...tches closed when a fault condition is identified see paragraph on alarms and ventilation on page 12 Setting NO NO Fail safe the contact 11 12 is positioned as normally closed switches open when a fau...

Страница 27: ...al transfer on page 15 Identification of a sensor fault or faulty connection In case of a faulty connection or sensor fault a quick positive or negative variation in temperature might occur leading to...

Страница 28: ...eck the connections and the terminal board The temperature shown by one or more channels is wrong Contact the TECSYSTEM Technical Department Sudden trip of the main switch The temperature is on standa...

Страница 29: ...pean directive 2012 19 EU on electrical and electronic waste WEEE Any electrical or electronic equipment marked with this symbol must be disposed of separately from normal domestic waste Returning of...

Отзывы: