background image

26 

        NT935BH 

 

  

     
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1.

 

Cable 20 x AWG 20/19 Cu/Sn 

2.

 

Section 0.55 mm² 

3.

 

Flame-protection insulation PVC105 

4.

 

Standards CEI 20.35 IEC 332.1 

5.

 

Maximum operating temperature: 90°C 

6.

 

Configuration: 4 triples of three twisted and coloured conductors  

7.

 

Screen on Cu/Sn 

8.

 

Fireproof PVC sheath 

9.

 

Outer diameter 12 mm 

10.

 

Standard configuration in 100 m coils 

  
 

TECHNICAL SPECIFICATIONS OF THE EXTENSION CABLE 
FOR Pt100  

 

  

The NT935 control unit has the selection n.o (normally open contact)/n.c (normally closed contact) for the ALARM, TRIP 
and FAULT relays, programming steps from 30 to 35 page 14. Selecting the YES/NO setting introduces the Fail Safe and 
No Fail Safe functions. 

 

ALARM AND TRIP   
By setting NO (NO Fail safe) the normally open contacts are in positions 5-7 Alarm and 8-10 Trip, they switch only when 
the pre-set temperature limits are reached. 

 

By setting YES (Fail safe), the normally closed contacts are in positions 5-7 Alarm and 8-10 Trip, they switch only when the 
pre-set temperature limits are reached or as a result of no voltage. 

 

FAULT 
By  setting  YES  (Fail  safe),  contact  11-12  is  positioned  as  normally  open,  switches  (closed)  when  a  fault  condition  is 
identified; see paragraph on alarms and ventilation on page 12.  

 

Setting  NO  (NO  Fail  safe)  the  contact  11-12  is  positioned  as  normally  closed,  switches  (open)  when  a  fault  condition  is 
identified; see paragraph on alarms and ventilation on page 12.  

 

If the fail safe function is disabled on the fault contact, the control unit will no longer be able to signal the fault due to power 
failure. In this case it is advisable to enable the Fail safe on the ALARM contact for the afore-mentioned indication. 

 

NOTE:  NOTE:  when  the control  unit  is  in one  of  the modes  indicated  below,  it  does  not  perform  any  thermal monitoring, 
moreover the relays will all be disabled

 

the FAULT led will flash.   

• Vis. display programming. 
• PRG programming. 
• Test of the relays. 

    The FAIL SAFE function is temporarily disabled and the FAULT relay switches. 

 

 
 
 
 

BARS/FANS STRUCTURE  
 

BIT 7 

BIT 6 

BIT 5 

BIT 4 

BIT 3 

BIT 2 

BIT 1 

 

 

-- 

 

 

Num. Bars 1;2 

 

 

-- 

 

 

Num. Motors for bar 1; 2; 3 

 

 
Bar programming TRBH Bit 5-4: 0 1=BAR1 
                                                   1 0=BAR1-2 

Programming of motors TRBH Bit 0-1: 0 1 = M1 
                                                              1 0 = M1-M2 
                                                              1 1 = M1-M2-M3 

TRBH MOTOR STATUS  

 

BIT 7 

BIT 6 

BIT 5 

BIT 4 

BIT 3 

BIT 2 

BIT 1 

-- 

-- 

-- 

Motor status Bar_2 

Motor status Bar_1 

 

TRBH motor status: 00=OK 

 

 

 

01=general motor fault 

 

10=overtemperature 

 

11= communication failure with the control box/bar 

 

FAIL SAFE FUNCTION  

Содержание NT935BH-D

Страница 1: ...s with ISO9001 certified quality system http www tecsystem it R 1 0 10 06 20 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT935...

Страница 2: ...NG NOTES 15 TEMPERATURE SENSORS MEASUREMENT SIGNAL TRANSFER TEMPERATURE SENSOR DIAGNOSTICS 16 VOTING FUNCTION PROGRAMMED DATA DIAGNOSTICS TEMPERATURE DIAGNOSTICS COOLING FAN CONTROL 17 FANS DIAGNOSTIC...

Страница 3: ...TA FRAME 19 DATA PACKET FUNCTION CODE CODE 3 10 CODE 16 10 NOTES FOR REMOTE PROGRAMMING ERROR CODES 20 UNACCEPTABLE DATA ILLEGAL DATA POLLING FREQUENCY MODBUS MAPPING TABLE 21 9 FAILSAFE FUNCTION 26 1...

Страница 4: ...e control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit use a dry cloth to dust it without any solvent or detergents...

Страница 5: ...ing torque 0 5Nm 1 Terminal 12 poles pitch 3 81 sensors Pt100 Code 2PL0420 Screw tightening torque 0 25Nm 1 Terminal 4 pitch poles 3 81 for BLDC output Code 2PL0368 Screws tightening torque 0 25Nm 1 T...

Страница 6: ...ation management relay SPST FAN 2 Output relays with 10A 250Vac res COS 1 contacts TRBH output FAN1 control bars B1 B2 RS485 output Modbus RTU DIMENSIONS 100x100 mm din43700 prof 131mm including termi...

Страница 7: ...te of FAN1 and FAN2 Temperature control from 0 C to 240 C 2 alarm thresholds for channels 1 2 3 2 alarm channels for channel 4 1 activation threshold FAN1 ON TRBH 2 ON OFF thresholds FAN 2 ventilation...

Страница 8: ...ication 5 FAULT red LED 16 3 digit channel display 6 FAN 1 TRBH signalling yellow 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode selection key 19 Au...

Страница 9: ...epairs 4 Pt Err This message appears when it is detected that one or more PT100 sensors are not working correctly FOC FCC and FCD indications in the temperature sensor diagnostics paragraph on page 16...

Страница 10: ...ks 1 Control unit 2 Panel hole dimensions 0 8 mm tolerance 3 Identification label 1 Control unit 3 Locking screws 2 Fixing blocks 4 Cross head screwdriver 1X100mm ASSEMBLY 1 1MN0007 REV 0 2 3 1 2 3 4...

Страница 11: ...sensors white red red 4 Relay FAN2 2 Power supply 85 260Vac cc 50 60Hz 5 FAN1 BLDC output Control Box connection 3 Relays ALARM TRIP FAULT 6 RS485 output Modbus RTU Pt100 CONNECTION EXAMPLE Note imag...

Страница 12: ...one of the methods described below does not monitor heat also the relay will all be banned The fault contact switches and the fault LED flashes Vis Programming display PRG programming Relay test The...

Страница 13: ...H4 is enabled with NO the CH4 is disabled 10 The ALARM threshold for CH4 is displayed the Alarm led flashes If CH4 NO jump to step 16 Default NO 11 Set the desired threshold Default 120 C 12 The TRIP...

Страница 14: ...FE info on page 26 31 Select YES or NO Default NO 32 FLS TRIP is displayed Blinking TRIP LED 33 Select YES or NO Default NO 34 FLS FAULT is displayed Blinking FAULT LED 35 Select YES or NO Default YES...

Страница 15: ...rcuit couples capacitively with the conductors in particular with unscreened cables The effect of this coupling creates a signal that overlaps the signal transmitted by the nearby conductors causing i...

Страница 16: ...se alarms generated by installation errors By activating the VOTING YES function the control unit compares the temperature values recorded on the monitored CH1 CH2 CH3 channels and enables the switchi...

Страница 17: ...1 C at 230 C range 0 C to 240 C or 1 C 190 C range 40 C to 200 C NOTE fan speed regulation rpm with selections different from B1 3 and B2 3 is managed with reference HOT channel the hottest channel of...

Страница 18: ...unication is temporarily deactivated DATA TRANSMISSION ON MODBUS NETWORK The MODBUS INSIDE internal module makes it possible to connect the NT935BH D control unit to an RS485 network with Modbus RTU p...

Страница 19: ...ng 00000000 xxxxxxx0 x n d Also in the remote programming phase via ModBus it must be considered that the Alarm thresholds must be lower than the Trip thresholds and that the Fan on thresholds must be...

Страница 20: ...Status Value FCD max see table SYSTEM Setting and Status Value Voting max see table SYSTEM Setting and Status Note If the value of Voting is higher than the max value expected for the model in questi...

Страница 21: ...channels 2 ASCII R 6 Options see note Options see note R 7 00 Wrong datum received R see tab 8 00 Info various causes R see tab 9 00 Controls W see tab SYSTEM Setting and Status Address LO 10 Data HI...

Страница 22: ...s 1 4 Address LO 10 Data HI Data LO Notes 1 Notes 2 R read W write RW read write 25 2 compl sign 2 compl Ch1 temper 10 C 240 C 48 C 200 C R 26 2 compl sign 2 compl Ch1 max temperat 0 C 240 C 0 C 200 C...

Страница 23: ...C 240 C 1 C 200 C AL RW 40 2 compl sign 2 compl Ch4 temper trip set point 1 C 240 C 1 C 200 C TRP RW 41 00 00 R 42 00 00 R 43 00 00 R 44 00 00 R 45 00 TRBH _1 speed M1 M6 motors R 46 00 TRBH _1 motors...

Страница 24: ...0 Ch4 Setting See Notes CHx RW 61 00 00 R 62 00 00 R 63 00 00 R 64 00 00 R CHANNELS 1 4 Status Address LO 10 Data HI Data LO Notes 1 Notes 2 R read W write RW read write 65 Ch1 story Ch1 status See No...

Страница 25: ...n STORY BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 TRIP ALARM FOC FCC RELAY STATUS coil energising status BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 Relay FAULT 1 ON TRIP Relay 1 ON ALARM Re...

Страница 26: ...tches closed when a fault condition is identified see paragraph on alarms and ventilation on page 12 Setting NO NO Fail safe the contact 11 12 is positioned as normally closed switches open when a fau...

Страница 27: ...al transfer on page 15 Identification of a sensor fault or faulty connection In case of a faulty connection or sensor fault a quick positive or negative variation in temperature might occur leading to...

Страница 28: ...eck the connections and the terminal board The temperature shown by one or more channels is wrong Contact the TECSYSTEM Technical Department Sudden trip of the main switch The temperature is on standa...

Страница 29: ...pean directive 2012 19 EU on electrical and electronic waste WEEE Any electrical or electronic equipment marked with this symbol must be disposed of separately from normal domestic waste Returning of...

Отзывы: